Plan Review Details - Permit 16031416
Plan Review Stops For Permit 16031416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2016-05-06 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 08:15 Rev Time  
Received By jwitmer Date 2016-04-11 Time 07:31 Sent To  
Notes
2016-04-11 08:15:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16031416
 ADD: 1793 PALM BEACH LAKES BLVD
 CONT: ANDERSON MOORE
 TEL: 561-662-1819
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 NOTE: PALM BEACH OUTLET MALL: BEFORE PLAN SUBMITTAL TO
 THE BUILDING DEPARTMENT, THE PLANS ARE SUPPOSED TO HAVE
 THE STAMPED LANDLORD APPROVAL BY NEW ENGLAND
 DEVELOPMENT PALM BEACH OUTLETS SKY GROUP TENANT
 COORDINATOR.
 PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
 PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE
 NUMBER WITHIN THE DOCUMENT.
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK TENANT BUILD OUT. THE PLANS DO NOT
 SHOW ANY WORK BEING COMPLETED AS A TENANT BUILD OUT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 LIFE SAFETY PLAN
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503)
 LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 FIRE SPRINKLERED OR NOT?
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 2) IN THE REAR OF THE TENANT AREA THERE ARE 2 DOORS
 MARKED AS EXITS BUT THERE IS A LOADING DOCK ON THE
 EXTERIOR OF THE BUILDING. IS THIS A RAISED LOADING
 DOCK, THERE ARE NO STAIRS SHOWN ON THE LOADING DOCK.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET LS01 INDICATES NOT MORETHAN 50% OF THE
 OCCUPANT LOAD CAN TRAVEL THROUGH THE STORAGE ROOM. NO
 STORAGE ROOM IS SHOWN ON THE PLANS. 2014 FBC-B 1014.2
 EXCEPTION # 2: MEANS OF EGRESS ARE NOT PROHIBITED
 THROUGH STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF
 THE FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 4) THE PLANS DO NOT INDICATE THE USE OF CASH WRAPS?
 2014 FBC-ACCESS. CODE 904.3.2 COUNTER.
 THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 5) THE PLANS DO NOT SHOW WHAT TYPE OF MERCANTILE STORE
 IS GOING TO OCCUPY THIS SPACE, IF DRESSING ROOM/
 CHANGING ROOMS ARE TO BE CREATED THEN COMPLIANCE WITH:
 2014 FBC-ACCESS. CODE :
 803.2 TURNING SPACE. TURNING SPACE COMPLYING WITH 304
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 5A) 803.3 DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
  
 5B) 803.4 BENCHES. A BENCH COMPLYING WITH 903 SHALL BE
 PROVIDED WITHIN THE ROOM.
  
 5C) 803.5 COAT HOOKS AND SHELVES. COAT HOOKS PROVIDED
 WITHIN THE ROOM SHALL BE LOCATED WITHIN ONE OF THE
 REACH RANGES SPECIFIED IN 308. SHELVES SHALL BE 40
 INCHES (1015 MM) MINIMUM AND 48 INCHES (1220 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5D) 903.1 GENERAL. BENCHES SHALL COMPLY WITH 903.
  
 5E) 903.2 CLEAR FLOOR OR GROUND SPACE. CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 SHALL BE PROVIDED AND
 SHALL BE POSITIONED AT THE END OF THE BENCH SEAT AND
 PARALLEL TO THE SHORT AXIS OF THE BENCH.
  
 5F) 903.3 SIZE. BENCHES SHALL HAVE SEATS THAT ARE 42
 INCHES (1065 MM) LONG MINIMUM AND 20 INCHES (510 MM)
 DEEP MINIMUM AND 24 INCHES (610 MM) DEEP MAXIMUM.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-29 Cont ID  
Sent By vperez Date 2016-04-29 Time 12:14 Rev Time 0.00
Received By vperez Date 2016-04-29 Time 12:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 12:22 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 12:22 Sent To  
Notes
2016-03-31 12:23:08INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE CLARIFY NOTE THAT SHOWS ELECTRICAL AS N/A ON
 SHEET A001, BUT SHEET D100 SHOWS SCOPE REGARDING THE
 SAFE OFF OF ELECTRICAL DEVICES PER DEMO SHOWN.
 ELECTRICAL TO BE PERMITTED PER SCOPE. FBC 107.3.5
 2. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By scaldero Date 2016-04-26 Time 17:00 Rev Time 0.00
Received By scaldero Date 2016-04-26 Time 17:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-05 Cont ID  
Sent By scaldero Date 2016-04-05 Time 12:38 Rev Time 0.00
Received By scaldero Date 2016-04-05 Time 12:35 Sent To  
Notes
2016-04-05 12:38:22PERMIT #16031416
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) PLEASE NOTE THAT FIRE ALARM DEVICES IN THIS SPACE
 WAS INSTALLED FOR THE WHITE BOX, ONLY. ADDITIONAL
 DEVICES MAY BE REQUIRED TO MEET FIRE CODE REQUIREMENTS
 FOR OCCUPANCY TYPE. SUB-PERMITS REQUIRED FOR ALL WORK
 DONE RELATED TO THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 3) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 5) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 6) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 7) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 09:23 Sent To  
Notes
2016-04-22 09:23:46C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-15 Cont ID  
Sent By eschneid Date 2016-04-15 Time 10:57 Rev Time 0.00
Received By eschneid Date 2016-03-30 Time 14:45 Sent To  
Notes
2016-03-30 14:45:47C07

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By eschneid Date 2016-05-06 Time 11:06 Rev Time 0.25
Received By eschneid Date 2016-05-06 Time 10:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By eschneid Date 2016-04-15 Time 10:56 Rev Time 0.25
Received By eschneid Date 2016-04-15 Time 10:56 Sent To  
Notes
***NONE***