| Plan Review Stops For Permit 16031393 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-30 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-03-30 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-03-30 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2016-03-30 18:49:16 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, AND PANEL SCHEDULES. | | | FURTHERMORE PLANS MUST BE SIGNED AND SEALED BY DESIGN | | | PROFFESIONAL. SHOW METER ENCLOSURE ON DIAGRAM TO CHECK | | | IF DISCONNECTING MEANS IS ON THE NEAREST POINT OF | | | ENTRY. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-30 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-03-30 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-03-29 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2016-03-30 11:28:00 | ELEC <5K |
|
|
|