Plan Review Details - Permit 16031390
Plan Review Stops For Permit 16031390
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By jgomez Date 2016-06-23 Time 17:32 Rev Time 0.00
Received By jgomez Date 2016-06-23 Time 17:32 Sent To  
Notes
2016-06-23 17:41:16BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
 RESPONSE: SECTION 4.2.2 OF ESR-1775 REPORT SUBMITTED
 REQUIRES WIND UPLIFT RESISTANCE DESIGN FOR BASIC WIND
 SPEEDS ABOVE 100MPH. PROVIDE DESIGN CRITERIA. DESIGNER
 OF RECORD TO SPECIFY ROOF TILE FASTENING METHOD AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY TYPE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT
 APPROVAL FOR THE ROOF TILE ADHESIVE.
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
 C) INSWING FRENCH DOORS AS SHOWN ON PLANS.
 RESPONSE: NOA 15-0409.03 SUBMITTED IS FOR "OUTSWING"
 DOORS. NEED PRODUCT APPROVAL FOR "INSWING" DOORS AS
 SHOWN ON PLANS.
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO BE USED TO VERIFY COMPLIANCE WITH
 CALCULATED DESIGN PRESSURES.
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 FRAMING PLANS AND DETAILS. MISSING SOME CONNECTOR'S
 PRODUCT APPROVALS.
 F) ALL PRECAST LINTELS AS SPECIFIED ON PLANS.
 2- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By jgomez Date 2016-06-06 Time 13:34 Rev Time 0.00
Received By jgomez Date 2016-06-06 Time 13:34 Sent To  
Notes
2016-06-06 13:42:41RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO:
 PROVISO MEANS THAT THE PERMIT MAY BE ISSUED WITH THE
 CONDITION THAT REQUESTED INFORMATION WILL BE PROVIDED
 BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME. COUNTY IMPACT FEE ASSESSMENT
 IS REQUIRED PRIOR TO ISSUING PERMIT. OTHERWISE, PLEASE
 RESUBMIT REQUIRED INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By jgomez Date 2016-04-28 Time 15:30 Rev Time 0.00
Received By jgomez Date 2016-04-28 Time 15:26 Sent To  
Notes
2016-04-28 15:37:28RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET S2:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL,
 5TH EDITION (2014), THIS BUILDING IS LOCATED IN
 EXPOSURE "C" NOT "B". REVISE THE DESIGN LOADING PER FBC
 2014 INFORMATION AND THE DESIGN CRITERIA. ALSO REVISE
 THE COMPONENTS AND CLADDING WIND PRESSURES ACCORDINGLY.
  
 B) DESIGN CRITERIA:
 (1) ROOF MATERIAL IS CONCRETE TILES NOT SHINGLES.
 REVISE AS REQUIRED. SEE PRODUCT APPROVAL SUBMITTED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 (2) CLARIFY WHY THE FLOOR DEAD LOAD IS 10PSF SHINGLES?.
 SEC. R301.A FBC-RESIDENTIAL.
  
 (3) REVISE ROOF PITCH TO MATCH ELEVATIONS ON SHEET A2.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 C) REVISE THE WIND ZONE WIDTH "A" OF THE DESIGN LOADING
 PER FBC 2014. ACCORDING TO NOTE OF FIGURE R301.2(7)
 FBC-RESIDENTIAL THE WIDTH OF "A" IS 4 FEET IN ALL
 CASES. REVISE AS REQUIRED.
  
 D) PROVIDE COMPLETE AND CLEAR DETAIL SHOWING
 CONSTRUCTION OF NEW CONCRETE PAD FOR THE NEW STEEL
 COLUMN. DETAIL #5 DOESN'T MATCH INFORMATION SHOWN ON
 THE EXISTING FOOTING LOCATION FLOOR PLAN ON SHEET S1.
 IT IS NOT CLEAR HOW THE NEW CONCRETE PAD IS GOING TO BE
 CONSTRUCTED WHERE THERE IS AND EXISTING FOOTING. THERE
 ARE NO SPECS HOW TO DEAL WITH THE EXISTING CONCRETE
 BLOCK WALL FOOTING. SEC. R301.1 FBC-RESIDENTIAL.
  
 E) PARTIAL EXTERIOR WALL SECTION IS SHOWN INCORRECTLY.
 THE FLOOR TRUSSES ARE REPRESENTED AS STEEL BAR JOISTS
 NOT FLOOR TRUSSES. THIS IS MISLEADING THE TYPE OF
 CONSTRUCTION. REVISE AS REQUIRED TO REPRESENT WOOD
 FLOOR TRUSSES.. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) WHERE IS DETAIL #4 TAKEN AT?. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE PLATE SUPPORTING THE W14 X 43
 STEEL BEAM. PROVIDE COMPLETE INFORMATION SHOWING HOW IS
 THE CONCRETE BLOCK BLOCK SUPPORTED BY THIS BEAM. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 G) WHERE IS DETAIL #3 TAKEN AT?. CLARIFY WHY SPECIFYING
 SIMPSON CCCQ-SDS 2.5 FOR ONLY ONE BEAM TO POST
 CONNECTION. SEE PICTURE OF SPECIFIED CONNECTOR. ALSO,
 CLARIFY WHY ANCHORING WOOD POST BASE WITH TWIST STRAP.
 PROVIDE ENGINEERING ANALYSIS SHOWING HOW THE LATERAL
 LOADS ARE RESISTED. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH CONNECTOR SCHEDULE ON SHEET S1.
  
 H) PROVIDE COMPLETE SPECIFICATIONS FOR NEW CONCRETE
 BEAM SPECIFIED ON DETAILS #2, AND #7. SEC. R301.1
 FBC-RESIDENTIAL.
  
 3- SHEET S1:
 A) PROVIDE COMPLETE BEAM AND LINTEL SCHEDULE THAT
 REFLECTS BEAMS/LINTELS SHOWN ON THE SECOND AND ROOF
 FRAMING PLANS. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) CLEARLY SPECIFY THE CONNECTORS AT THE ENDS OF ALL
 BEAMS. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) REVISE CONNECTORS SPECIFIED FOR THE ROOF TRUSSES
 ABOVE THE NEW BALCONY. CONNECTOR SPECIFIED IS FOR
 MASONRY CONSTRUCTION NOT FOR WOOD BEAMS. REVISE AS
 REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 D) CLEARLY SPECIFY TOP AND BOTTOM CONNECTORS FOR THE
 NEW BALCONY WOOD POSTS. COORDINATE WITH DETAIL #3 ON
 SHEET S2. SEC. R301.1 FBC-RESIDENTIAL.
  
 E) CLARIFY CONNECTOR U3 SPECIFIED ON THE CONNECTOR
 SCHEDULE. WHY USING THIS TYPE OF HANGER FOR A PRECAST
 LINTEL. SEE NOTE U3 BELOW THE CONNECTOR SCHEDULE AND
 LEGEND FOR RB1 ON SAME SHEET. SEC. R301.1
 FBC-RESIDENTIAL.
  
 F) ROOF PLAN NOTES: CLARIFY WHY THE LIVE LOAD TOP CHORD
 ON NOTE #11 OF ROOF PLAN NOTES IS "20PSF REDUCIBLE".
 ALSO, COORDINATE ALL LOADS WITH THE DESIGN CRITERIA ON
 SHEET S2. COORDINATE WITH ITEM # 2(C) ABOVE. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 4- SHEET D-1: UPDATE GENERAL NOTE #1 THE CURRENT CODE
 IS 2014 NOT 2010. CHAPTER 553 F.S.
  
 5- SHEET A-1: UPDATE GENERAL NOTE #8 THE CURRENT CODE
 IS 2014 NOT 2001. CHAPTER 553 F.S.
  
 6- SHEET A-3:
 A) UPDATE GENERAL NOTE #8 THE CURRENT CODE IS 2014 NOT
 2001. CHAPTER 553 F.S.
  
 B) THE ROOF SLOPE SHOWN ON THE ROOF FRAMING PLAN
 DOESN'T MATCH ROOF SLOPE SHOWN ON THE EXTERIOR
 ELEVATIONS. REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 7- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF ALL
 BEDROOMS (INCLUDING 1ST FLOOR) AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CEILING CONSTRUCTION ABOVE GARAGE TO SHOW COMPLIANCE
 WITH TABLE R302.6 FBC-RESIDENTIAL.
  
 9- VALUATION DECLARED IN-THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $37,448. THE PERMIT FEE BALANCE IS $843.33.
  
 10- PLANS TO BE COORDINATED WITH THE ENERGY
 CALCULATIONS. SPECIFY THE CEILINGS, FLOORS AND WALLS
 R-VALUE SPECIFIED ON THE ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 BALCONY GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE
 LOADS OF TABLE R301.5 FBC-RESIDENTIAL.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 INCLUDING BUILDER NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: THE JURISDICTION IS NOT PALM
 BEACH COUNTY.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES)AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) INSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO BE USED TO VERIFY COMPLIANCE WITH
 CALCULATED DESIGN PRESSURES.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR. OR DESIGNER OF RECORD TO LIST THE
 CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 F) ALL PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 19:34 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 18:45 Rev Time 0.00
Received By mvaldes Date 2016-03-31 Time 18:45 Sent To  
Notes
2016-03-31 19:15:16JOB PERMIT NUMBER: 16031390
 JOB ADDRESS: 2163 REGENTS CIRCLE
 WEST PALM BEACH FLORIDA
 DATE: MARCH 31 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SITE CURRENT APPLICABLE CODE STANDARD NEC 2011
 - PROVIDE INTERSYSTEM BONDING TERMINAL AND SHOW WATER
 BEING BONDED TO GROUNDING ELECTRODE ON RISER DIAGRAM
 NEC 250
 - PANEL ? S ? REFLECTS AN INCORRECT BREAKER SIZE ON
 PANEL SCHEDULE ? A ? AS A 20 AMP ? FURTHERMORE PROVIDE
 OVERCURRENT PROTECTION SIZES ON PANEL SCHEDULE ? A ?
 FOR AC UNITS , WATER HEATER , DRYER AND RANGE.
 - BALCONIES REQUIRE A GFCI RECEPTACLE OUTSIDE PER NEC
 210.52 E 3
 - STAIRWAY LIGHTING MUST BE ON A 3 WAY SWITCH PER NEC
 210.70 2 C
 - ATTIC ENTRANCE MUST HAVE A LIGHT PER NEC 210.70 3 AND
 MAKE SURE PROPER WORKING CLEARANCE FOR ATTIC AC IS
 PROVIDED.
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-17 Cont ID  
Sent By jgomez Date 2016-06-17 Time 09:40 Rev Time 0.00
Received By jgomez Date 2016-05-20 Time 15:26 Sent To  
Notes
2016-05-20 15:32:26R33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-29 Cont ID  
Sent By jgomez Date 2016-04-29 Time 16:50 Rev Time 0.00
Received By jgomez Date 2016-03-29 Time 15:00 Sent To  
Notes
2016-03-30 15:00:54R14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By jgomez Date 2016-06-23 Time 17:53 Rev Time 0.00
Received By jgomez Date 2016-06-23 Time 17:53 Sent To  
Notes
2016-06-23 17:56:05NO FEES DUE. MU-2016-15466.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By jgomez Date 2016-06-06 Time 13:43 Rev Time 0.00
Received By jgomez Date 2016-06-06 Time 13:43 Sent To  
Notes
2016-06-06 13:43:501- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By jgomez Date 2016-04-29 Time 10:29 Rev Time 0.00
Received By jgomez Date 2016-04-29 Time 10:29 Sent To  
Notes
2016-04-29 10:29:441- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By hmoser Date 2016-06-16 Time 15:27 Rev Time 0.00
Received By hmoser Date 2016-06-16 Time 15:18 Sent To B
Notes
2016-06-16 15:27:25PASS PROVISO
 REFER TO SECTION R403.2.4 AIR HANDLING UNITS
 FLORIDA ENERGY CODE 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By hmoser Date 2016-04-05 Time 11:49 Rev Time 0.00
Received By hmoser Date 2016-04-05 Time 10:47 Sent To  
Notes
2016-04-05 11:49:01PLAN DENIED
 1) SHOW ACCESS TO AIR HANDLER UNITS IN ATTIC.
 REFER TO SECTION 403.2.4 FLORIDA RESIDENTIAL
 ENERGY CODE 2014
 2) SHOW SERVICE ACCESS TO AIR HANDLER 1 AND 2.
 REFER TO SECTION M1305.1 APPLIANCE ACCESS.
 2014 RESIDENTIAL CODE
 3) PROVIDE BALANCED RETURN AIR FOR BEDROOM
 #3 PER SECTION M1602.4 2014
 4) IF BEDROOM #2 IS A MASTER RETURN AIR IS TOO
 SMALL PER SECTION M1602.4
 5) CABLE OVER CONDENSER FOR TIEDOWN IS NOT ACCEPTED
 DO TO SERVICE ACCESS
 6) SHOW LOCATION OF CONDENSER ON THE PLAN. PER SECTION
 107 FBC 2014
 7) REFER TO SECTION R403.2.4 AIR HANDLER UNITS
 FLORIDA ENERGY CODE 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By gjohnson Date 2016-06-01 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By gjohnson Date 2016-04-13 Time 14:06 Rev Time 0.00
Received By gjohnson Date 2016-04-13 Time 14:06 Sent To  
Notes
2016-04-13 14:16:54PLUMBING COMMENTS:
  
 1. SHT.P-1 THE WATER AND SANITARY RISER DIAGRAM DOES
 NOT MATCH FLOOR PLAN. THE RISER SHOWS A KITCHEN SINK,
 WASHING MACHINE AND A UTILITY SINK
 PLEASE PROVIDE RISER THAT MATCHES FLOOR PLAN. PER WPB
 AMEND. TO FBC SEC 107.3.5.3 (11)
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By jgomez Date 2016-06-23 Time 18:49 Rev Time 0.00
Received By jgomez Date 2016-06-23 Time 18:48 Sent To  
Notes
2016-06-23 18:49:38BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
 RESPONSE: SECTION 4.2.2 OF ESR-1775 REPORT SUBMITTED
 REQUIRES WIND UPLIFT RESISTANCE DESIGN FOR BASIC WIND
 SPEEDS ABOVE 100MPH. PROVIDE DESIGN CRITERIA. DESIGNER
 OF RECORD TO SPECIFY ROOF TILE FASTENING METHOD AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY TYPE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT
 APPROVAL FOR THE ROOF TILE ADHESIVE.
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By jgomez Date 2016-06-06 Time 18:22 Rev Time 0.00
Received By jgomez Date 2016-06-06 Time 18:22 Sent To  
Notes
2016-06-06 18:25:301- PROVIDE PRODUCT APPROVAL (2 COPIES)AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
 RESPONSE: SECTION 4.2.2 OF ESR-1775 REPORT SUBMITTED
 REQUIRES WIND UPLIFT RESISTANCE DESIGN FOR BASIC WIND
 SPEEDS ABOVE 100MPH. PROVIDE DESIGN CRITERIA. DESIGNER
 OF RECORD TO SPECIFY ROOF TILE FASTENING METHOD AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY TYPE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT
 APPROVAL FOR THE ROOF TILE ADHESIVE.
  
 A(1) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 ORIGINAL COMMENT:
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: PRODUCT APPROVALS WERE APPROVED BY THE
 ARCHITECT NOT THE ENGINEER OF RECORD. THE ENGINEER IS
 THE ONE RESPONSIBLE FOR THE STRUCTURAL DESIGN. PRODUCT
 APPROVALS NEED TO BE REVIEWED BY THE STRUCTURAL
 ENGINEER TO VERIFY COMPLIANCE WITH THE STRUCTURAL
 DESIGN.
  
  
 ROOF TILE FLORIDA PRODUCT APPROVAL SUBMITTED FL3505-R7

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By jgomez Date 2016-04-29 Time 16:50 Rev Time 0.00
Received By jgomez Date 2016-04-29 Time 16:49 Sent To  
Notes
2016-04-29 16:50:421- PROVIDE PRODUCT APPROVAL (2 COPIES)AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By ajones Date 2016-05-23 Time 17:48 Rev Time 0.00
Received By ajones Date 2016-05-23 Time 17:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By ajones Date 2016-04-11 Time 14:30 Rev Time 0.00
Received By ajones Date 2016-04-11 Time 14:30 Sent To  
Notes
***NONE***