Plan Review Details - Permit 16031389
Plan Review Stops For Permit 16031389
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-19 Cont ID  
Sent By cpuell Date 2016-04-19 Time 17:03 Rev Time 0.00
Received By cpuell Date 2016-04-18 Time 10:15 Sent To  
Notes
2016-04-19 10:15:18RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-31 Cont ID  
Sent By lmarchan Date 2016-03-31 Time 09:03 Rev Time 0.00
Received By lmarchan Date 2016-03-29 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-19 Cont ID  
Sent By jvalido Date 2016-04-19 Time 15:53 Rev Time 0.00
Received By jvalido Date 2016-04-19 Time 15:48 Sent To  
Notes
2016-04-19 15:48:48PROVIDE AHRI AND EQUIPMENT CHANGE OUT OF COMPLIANCE
 FORMS FOR EACH OF THE SPECIFIC SYSTEMS BEING CHANGED
 OUT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-30 Cont ID  
Sent By jvalido Date 2016-03-30 Time 18:10 Rev Time 0.00
Received By jvalido Date 2016-03-30 Time 17:49 Sent To  
Notes
2016-03-30 18:05:21107.2.1 - PROVIDE SIZES OF STAIRWELL AND BATHROOM
 SUPPLY DUCTS. SHOW HOW THE BATHROOM SUPPLY DUCT
 CONNECTS TO THE A/C SYSTEM. PROVIDE AHRI AND EQUIPMENT
 CHANGE OUT OF COMPLIANCE FORMS FOR EACH OF THE SPECIFIC
 SYSTEMS BEING CHANGED OUT. CONFIRM EXHAUST REQUIREMENTS
 FOR 2ND FLOOR BATHROOM.