Plan Review Details - Permit 16031374
Plan Review Stops For Permit 16031374
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-05 Time 17:11 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 17:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By ccole Date 2016-04-05 Time 17:12 Rev Time 0.00
Received By scaldero Date 2016-03-31 Time 09:32 Sent To M
Notes
2016-03-31 10:21:34PERMIT #16031374
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SCOPE OF WORK ON PLANS LISTS THAT WORK TO BE DONE IS
 ON 187 HEADS WITHIN GUEST ROOMS ON FLOORS 1-8. THE PLAN
 SHEETS SUBMITTED ONLY SHOW LAYOUTS FOR THE 1ST FLOOR
 AND TYPICAL FLOOR PLAN FOR WHAT IS ASSUMED TO BE FLOORS
 2-8. PLAN DOES NOT INDICATE WHICH HEADS ARE BEING
 REPLACED. ADDITIONALLY, FLOORS 9 AND 10 HAVE BEEN
 OMMITTED.
 PLEASE PROVIDE A FLOOR PLAN FOR EACH FLOOR, INDICATING
 WHICH SPECIFIC HEADS ARE BEING REPLACED AND WITH WHAT.
  
 2) CUT SHEETS FOR THE REPLACEMENT HEADS NOT PROVIDED.
 PLEASE INCLUDE IN RESUBMITTAL.
  
 3) ON 7/30/2014 IT WAS CONFIRMED THAT PAINTED SPRINKLER
 HEADS ON FLOORS 9 AND 10 WERE REPLACED WITHOUT A
 PERMIT. THIS INCLUDED 13 HEADS ON THE 10TH FLOOR THAT
 WERE REPLACED ON 7/28/2014. AT THAT TIME THE MARRIOTT
 WAS ADVISED TO CEASE ALL WORK AND HAVE THE CONTRACTOR
 APPLY FOR AND OBTAIN THE PROPER PERMITS. ON 1/13/2016
 IT WAS CONFIRMED THAT ALL WORK IN THE TOWER WAS
 COMPLETED AND A PERMIT WAS NEVER OBTAINED. DURING THE
 ANNUAL INSPECTION ON 1/28/2016, THIS WAS AGAIN
 DISCUSSED AND CONFIRMED. A FINE OF 4 TIMES THE PERMIT
 FEE HAS BEEN ASSESSED FOR THIS PROJECT.
  
 4) THIS PERMIT JOB VALUE IS UNDERVALUED. THE TOTAL
 PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS AND LABOR.
 PLEASE PROVIDE A COPY OF THE SIGNED CONTRACT.
  
 5) THE SCOPE OF WORK FOR THIS PERMIT IS FOR THE
 REPLACEMENT OF PAINTED HEADS WITHIN THE LISTED GUEST
 ROOMS, ONLY. ANY ADDITIONAL WORK DONE ON THE PROPERTY
 AND NOT PROPERLY REFELCTED IN THE RESUBMITTAL WILL
 REQUIRE A NEW PERMIT.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-05 Time 17:12 Rev Time 0.00
Received By ccole Date 2016-03-29 Time 10:56 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-05 Time 17:12 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 17:12 Sent To  
Notes
2016-04-05 17:17:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16031374
 4/5/16
  
 1) PROVIDE PRODUCT DATA SHEETS FOR THE SPRINKLER HEADS.
 2) COMPLY WITH FIRE DEPT. COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  