Plan Review Details - Permit 16031311
Plan Review Stops For Permit 16031311
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-21 Cont ID  
Sent By rmcdouga Date 2017-04-21 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2017-04-21 Time 17:34 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By rmcdouga Date 2016-07-26 Time 10:28 Rev Time 0.00
Received By rmcdouga Date 2016-07-26 Time 07:49 Sent To  
Notes
2016-07-26 08:33:34PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED (MINIMUM
 1/8 INCH SCALE) AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) FBC 107.3.4 - SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW
 WINDOWS, STRUCTURAL MULLIONS AND IMPACT PROTECTION
 DEVICES.
  
 3) IF WINDOWS ARE NOT LARGE MISSILE IMPACT RATED,
 IMPACT PROTECTION DEVICES ARE REQUIRED. TWO COPIES OF A
 KEY PLAN AND INSTALLATION SCHEDULE FOR THE STORM PANELS
 IS REQUIRED IN ADDITION TO THE PRODUCT APPROVALS. FBCR
 301.2.1.2
  
 4) THE NOTES ON THE PLANS HAVE CEMENTRY BOARD. IS THIS
 SUPPOSE TO BE CEMENT RATHER THAN CEMENTRY? PLEASE
 CLARIFY. FBC 107.2.1
  
 5) THE PROPERTY APPRAISER'S WEB SITE INDICATES THAT THE
 EXTERIOR WALL ARE CONCRETE BLOCK AND STUCCO. THE WALL
 REPAIR DETAIL SHOWS A CONCRETE TIE BEAM AND A
 MONOLITHIC SLAB FOUNDATION. THE CLOUDED AREA ON THE
 PLANS APPEAR TO SHOW THAT A LARGE AREA OF CBS WALL IS
 BEING REPLACED WITH WOOD FRAME BETWEEN THE SLAB AND TIE
 BEAM. IT IS UNCLEAR HOW MUCH WALL IS BEING FRAMED IN
 THIS MANNER. SEE COMMENT #1. UNLESS YOU ARE JUST
 FRAMING IN THE SPACE AT THE WINDOWS, A FLORIDA LICENSED
 ENGINEER IS REQUIRED TO SUBMIT SIGNED AND SEALED
 STRUCTURAL DRAWINGS. FBC 107.2.1.3.
  
 6) THE WALL SECTION SHOWS 1/2"PLYWOOD, 2 LAYERS OF 15#
 FELT, 1/2" CEMENT BOARD WITH 3/4" STUCCO. SUBMIT TWO
 SETS OF PRODUCT APPROVAL FOR THE CEMENT BOARD THAT
 ALLOWS IT TO BE USED AS A BACKER BOARD FOR 3/4" STUCCO
 WITHOUT WIRE LATH.
  
 7) THE SCOPE OF WORK SPECIFIES THAT THE FLOOR IS TO BE
 INSULATED WITH R-19. THE WALL REPAIR DETAIL SPECIES A
 CONCRETE SLAB FLOOR. CLARIFY. FBC 107.2.1 PLANS HAVE
 CONFLICTING INFORMATION. COORDINATE THE SCOPE OF WORK,
 NOTES AND DETAILS ON THE PLANS.
  
 8) THE FBC ENERGY R402.1 (PRESCRIPTIVE) REQUIRES R-30
 INSULATION IN THE CEILING AND R-13 IN WOOD FRAME WALLS.
 PLANS HAVE CONFLICTING INFORMATION. COORDINATE THE
 SCOPE OF WORK, NOTES AND DETAILS ON THE PLANS.
  
 9) THE VALUE FOR THE SCOPE OF WORK SHOWN ON THE PLANS
 FAR EXCEEDS $1500.00. ADD THE TOTALS OF THE VALUATIONS
 FOR ALL OF THE SUB PERMITS UNDER THIS MASTER AND
 PROVIDE AN ACCURATE VALUATION BASED ON THE FOLLOWING.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 THE VALUE FOR ALL OF THE PROPOSED BUILDING, MECHANICAL,
 PLUMBING AND ELECTRICAL WORK SHOULD BE $15,000.00 OR
 MORE. THEREFORE, THE VALUE HAS BEEN ADJUSTED TO
 $15,000.00.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By rmcdouga Date 2016-04-28 Time 18:14 Rev Time 0.00
Received By rmcdouga Date 2016-04-28 Time 10:08 Sent To  
Notes
2016-04-28 11:14:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED (MINIMUM
 1/8 INCH SCALE) AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) SPECIFY THE SIZE AND TYPES OF WINDOWS THAT ARE TO BE
 REPLACED ON THE PLANS. FBCR 107.2.1 NOTE: THE WINDOWS
 IN ROOMS THAT ARE USED FOR SLEEPING ARE REQUIRED TO
 COMPLY WITH FBCR 310.1 FOR EMERGENCY ESCAPE AND RESCUE.
  
 3) FBC 107.3.4 - SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW
 WINDOWS, STRUCTURAL MULLIONS AND IMPACT PROTECTION
 DEVICES.
  
 4) IF WINDOWS ARE NOT LARGE MISSILE IMPACT RATED,
 IMPACT PROTECTION DEVICES ARE REQUIRED. TWO COPIES OF A
 KEY PLAN AND INSTALLATION SCHEDULE FOR THE STORM PANELS
 IS REQUIRED IN ADDITION TO THE PRODUCT APPROVALS. FBCR
 301.2.1.2
  
 5) SPECIFY THE WIND DESIGN DATA AND THE OPENING DESIGN
 PRESSURES ON THE PLANS. FBCR 301.2.1
  
 6) SPECIFY THE REQUIRED EMBED DEPTH OF THE 1/2"
 EXPANSION BOLT SHOWN IN THE WALL REPAIR DETAIL ON SHEET
 A. FBCR 301.1
  
 7) THE PROPERTY APPRAISER'S WEB SITE INDICATES THAT THE
 EXTERIOR WALL ARE CONCRETE BLOCK AND STUCCO. THE WALL
 REPAIR DETAIL SHOWS A CONCRETE TIE BEAM AND A
 MONOLITHIC SLAB FOUNDATION. THE CLOUDED AREA ON THE
 PLANS APPEAR TO SHOW THAT A LARGE AREA OF CBS WALL IS
 BEING REPLACED WITH WOOD FRAME BETWEEN THE SLAB AND TIE
 BEAM. IT IS UNCLEAR HOW MUCH WALL IS BEING FRAMED IN
 THIS MANNER. SEE COMMENT #1. UNLESS YOU ARE JUST
 FRAMING IN THE SPACE AT THE WINDOWS, A FLORIDA LICENSED
 ENGINEER IS REQUIRED TO SUBMIT SIGNED AND SEALED
 STRUCTURAL DRAWINGS. FBC 107.2.1.3.
  
 8) THE SCOPE OF WORK SPECIFIES THAT THE FLOOR IS TO BE
 INSULATED WITH R-19. THE WALL REPAIR DETAIL SPECIES A
 CONCRETE SLAB FLOOR. CLARIFY. FBC 107.2.1
  
 9) THE FBC ENERGY R402.1 (PRESCRIPTIVE) REQUIRES R-30
 INSULATION IN THE CEILING AND R-13 IN WOOD FRAME WALLS.
  
 10) THE VALUE FOR THE SCOPE OF WORK SHOWN ON THE PLANS
 FAR EXCEEDS $1500.00. ADD THE TOTALS OF THE VALUATIONS
 FOR ALL OF THE SUB PERMITS UNDER THIS MASTER AND
 PROVIDE AN ACCURATE VALUATION BASED ON THE FOLLOWING.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 14:08 Rev Time 0.00
Received By jleahy Date 2017-06-26 Time 13:59 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-05 Time 10:24 Rev Time 0.00
Received By jleahy Date 2017-06-05 Time 10:24 Sent To M
Notes
2017-06-06 06:58:20ONLY ONE E1 SHEET SUBMITTED. NEED ONE MORE TO ISSUE
 PERMIT. JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-04-24 Cont ID  
Sent By vperez Date 2017-04-24 Time 09:56 Rev Time 0.00
Received By vperez Date 2017-04-24 Time 09:55 Sent To  
Notes
2017-04-24 09:57:29PLEASE ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL
 APPPROVAL.
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 08:21 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 08:03 Sent To  
Notes
2016-03-31 08:30:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO- SHOW CLEARANCE FOR AC DISCONNECT. NEC
 110.26
 2. NOTE AT THE KITCHEN TO COMPLY WITH REQUIRED SPACING
 REQUIREMENTS OF FBC RES E3901.2.4
 3. VERIFY WATER MAIN IS BONDED AT SERVICE PER FBC RES
 E3606
 4. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 14:08 Rev Time 0.00
Received By jleahy Date 2017-06-20 Time 13:01 Sent To  
Notes
2017-06-21 13:01:16RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-06-05 Cont ID  
Sent By hmoser Date 2017-06-05 Time 13:52 Rev Time 0.00
Received By hmoser Date 2017-06-01 Time 17:12 Sent To  
Notes
2017-06-01 17:12:58JLEAHY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-24 Cont ID  
Sent By vperez Date 2017-04-24 Time 09:57 Rev Time 0.00
Received By vperez Date 2017-04-24 Time 09:57 Sent To  
Notes
2017-03-15 11:07:38R15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-26 Cont ID  
Sent By rmcdouga Date 2016-07-26 Time 10:28 Rev Time 0.00
Received By rmcdouga Date 2016-07-05 Time 10:22 Sent To  
Notes
2016-07-06 10:22:43RESUB ROUTED TO JVALDIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-28 Cont ID  
Sent By rmcdouga Date 2016-04-28 Time 18:14 Rev Time 0.00
Received By rmcdouga Date 2016-03-28 Time 16:00 Sent To  
Notes
2016-03-28 16:00:18R13

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2017-06-05 Cont ID  
Sent By jleahy Date 2017-06-06 Time 07:05 Rev Time 0.00
Received By hmoser Date 2017-06-05 Time 13:23 Sent To E
Notes
2017-06-05 13:52:22NO MECHANICAL WORK AT THIS TIME HM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-04-19 Cont ID  
Sent By hmoser Date 2017-04-19 Time 11:33 Rev Time 0.00
Received By hmoser Date 2017-04-19 Time 11:33 Sent To  
Notes
2017-04-19 11:37:19PLAN DENIED
 NO MECHANICAL PLAN SUBMITTED. CALLED LEFT A
 MESSAGE WITH THE CONTRACTOR 3ED REVIEW HM.
 THERE IS A MECHANICAL APPLICATION IN THE PACKAGE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-06 Cont ID  
Sent By jvalido Date 2016-07-06 Time 18:07 Rev Time 0.00
Received By jvalido Date 2016-07-06 Time 18:02 Sent To  
Notes
2016-07-06 18:06:38CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 BECAUSE THE PERMIT IS BEING PROCESSED AS A MECH SUB:
  
 (1) PROVIDE EQUIPMENT SCHEDULE ON PLANS OF NEW HVAC
 EQUIPMENT.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-30 Cont ID  
Sent By jvalido Date 2016-03-30 Time 19:25 Rev Time 0.00
Received By jvalido Date 2016-03-30 Time 19:11 Sent To  
Notes
2016-03-30 19:24:21107.2.1 - PROVIDE (2) COMPLETED A/C CHANGE-OUT
 COMPLIANCE FORMS

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-04-03 Cont ID  
Sent By gjohnson Date 2017-04-03 Time 10:19 Rev Time 0.00
Received By gjohnson Date 2017-03-31 Time 14:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By gjohnson Date 2016-07-08 Time 14:51 Rev Time 0.00
Received By gjohnson Date 2016-07-08 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-13 Cont ID  
Sent By gjohnson Date 2016-04-13 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2016-04-13 Time 13:50 Sent To  
Notes
***NONE***