Plan Review Details - Permit 16031309
Plan Review Stops For Permit 16031309
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-10 Cont ID  
Sent By   Date 2016-05-10 Time 17:30 Rev Time 0.00
Received By   Date 2016-05-10 Time 16:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-04-07 Time 06:45 Sent To  
Notes
2016-04-07 07:04:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16031309
 ADD: 600 BANYAN BLVD.
 CONT: JIJ CONSTRUCTION
 TEL: 561-574-5995
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 07/2016
 ACTION: DENIED
  
 1) NEW LINE DRAFTING DESIGN DOES NOT HAVE THEIR LICENSE
 NUMBER AS BEING EITHER A ARCHITECT NOR ENGINEER IN THE
 TITLE BLOCK. NEW LINE DRAFTING DESIGN ALSO DOES NOT
 HAVE THEIR CERTIFICATE OF AUTHORIZATION LISTED ON THE
 PLANS.
 61G15-30.003 ENGINEERING DOCUMENTS CLASSIFICATION.
 471.023 CERTIFICATION OF BUSINESS.
 61G1-16.004 TITLE BLOCK/ ARCHITECT. 481.2.19
 CERTIFICATION OF CORPORATION.
  
 2) SHEET A-2.0 DOES NOT INDICATE AS TO WHAT CODES THE
 PLANS WERE DEVELOPED, NOR DOES THE PLAN INDICATE UNDER
 THE EXISITNG BUILDING CODE WHAT METHOD OF COMPLIANCE
 WAS USED IN THE DESIGN CONCEPT. 2014 FBC-EXISITNG
 BUILDING CODE 301.1.
  
 3) THE PLANS DO NOT PROVIDE THE MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL PLAN REVIEW. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS
 OCCUPANCY TYPE
 MINIMUM BUILDING TYPE
 FIRE SPRINKLERED OR NOT
 OCCUPANCY LOAD/ EGRESS REQUIREMENTS SHALL INCLUDE:
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 4) SHEET A-2.0:
 4A) THE 1 HOUR FIRE RATED WALL DOES NOT PROVIDE TO WHAT
 ASSEMBLY THE WALL IS BUILT? 2014 FBC-B 703.2 FIRE
 -RESISTANCE RATINGS.
  
 4B) THE DESIGNER HAS INDICATED THE EXIT ACCESS CORRIDOR
 WALLS ARE TO BE 1 HOUR FIRE RATED. IN THE PROPOSED
 OFFICE USE SPACE THERE APPEARS TO BE 2 OPENINGS WITHOUT
 OPENING PROTECTIVES, POSSIBLY PASS THROUGH OPENINGS?
 SEE NOTE 5 NO IDENTIFICATION ON THE PLANS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2014 FBC-B TABLE 716.5. OPENING PROTECTIVES.
  
 4C) THE PLANS INDICATE THE INSTALLATION OF A 20 MINUTE
 RATED FIRE RATING OF GLASS AND FRAME. THE DESIGNER OF
 RECORD LIST EITHER THE OWNER OR CONTRACTOR PROVIDE UL
 APPROVED SHOP DRAWINGS. THE DESIGNER OF RECORD DOES NOT
 PROVIDE AS TO WHAT STANDARDS AND LISTINGS THE DESIGN IS
 TO BE TESTED TOO, INSUFFICIENT INFORMATION ON THE
 PLANS. 2014 FBC-B 716.2 FIRE RESISTANT RATED GLAZING.
  
 4D) THE PLANS INDICATE A NEW DOOR OPENING IN THE ONE
 HOUR FIRE RATED WALL. 2014 FBC-B TABLE 716.5.
  
 4E) THE NEW DOOR OPENING IN THE 1 HOUR FIRE RATED WALL
 DOES NOT INDICATE THE WIDTH OF THE NEW DOOR? 2014 FBC-B
 1008.1.1.
  
 4F) THERE IS NO DOOR SCHEDULE FOR THE EXISTING DOORS OR
 NEW DOOR WHICH WILL INDICATE THE TYPE OF HARDWARE TO BE
 INSTALLED ON THE FIRE RATED DOOR. FBC-B 716.5.
  
 4G) THE PROPOSED OFFICE USE SPACE AT THE 2 WINDOWS ON
 THE INTERIOR SIDE OF THE OPENING HAS SOMETHING NOT
 IDENTIFIED DESK
 EVIDENCE LOCKERS, DOES THIS HAVE TO COMPLY WITH 2014
 FBC-ACCESSIBILITY CODE 902.3. HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4H) PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 902.3 FOR THE PROPOSED EVIDENCE
 TECH DESK AREA.
  
 4I) THE DOOR LEADING FROM THE EXISTING EVIDENCE STORAGE
 AREA TO THE PROPOSED EVIDENCE TECH DESK AREA IN THE NEW
 WALL DOES NOT HAVE 18 INCHES ON THE LATCH SIDE OF THE
 DOOR.
  
 4J) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By vperez Date 2016-05-06 Time 07:23 Rev Time 0.00
Received By vperez Date 2016-05-06 Time 07:23 Sent To FIRE
Notes
2016-05-06 07:35:372ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO- SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE
 AND FIRE ALARM FOR ROLL UP SHUTTER. FBC 107.3.5
 2. AS-BUILT TO REFLECT WHAT BRANCH CIRCUITS WHERE USED
 FOR THE NEW POWER RECEPTACLES. FBC 107.3.5
 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 07:28 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 07:28 Sent To  
Notes
2016-03-31 07:41:30INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO- SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE
 AND FIRE ALARM FOR ROLL UP SHUTTER. FBC 107.3.5
 2. PROVIDE ONE EXTRA SHEET OF A-1.0 FOR STAMPS AND
 RECORD. A-2.0 SUBMITTED INADVERTENTLY ON SECOND SET
 3. AS-BUILT TO REFLECT WHAT BRANCH CIRCUITS WHERE USED
 FOR THE NEW POWER RECEPTACLES. FBC 107.3.5
 4. GENERAL NOTES TO MAINTAIN FIRE RATING AROUND FIRE
 RATED WALLS. NEC 300.21
 5. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By pleduc Date 2016-05-06 Time   Rev Time 0.00
Received By pleduc Date 2016-05-06 Time 16:16 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By pleduc Date 2016-03-31 Time   Rev Time 0.00
Received By pleduc Date 2016-03-31 Time 14:48 Sent To  
Notes
2016-03-31 15:09:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 1.0 - THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 2. SHEET A 1.0 - THE NATURE OF THE REMODEL REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR
 CONSTRUCTION OF WALLS REQUIRE AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3. SHEET A 1.0 - TWO NEW DOORS ARE INDICATED ON THE
 REMODLED FIRE WALL. THE SUBMITTED PALNS DO NOT INDICATE
 A DOOR OR HARDWARE SCHEDULE. THE NEW DOOR AND HARDWARE
 SET SHALL COMPLY WITH THE REQUIRMENTS EQUAL TO THE FIRE
 RATING OF THE WALL ASSEMBLY.
  
 4. SHEET A 2.0 - THERE ARE NO EXITS SIGNS INDICATED.
 PLEASE PROVIDE EXIT SIGNS ACCORDING TO THE LIFE SAFETY
 PLAN.
  
 5. SHEET A 2.0 - THERE IS A DIMENSION OF 1' 9" BETWEEN
 OFFICE FURNITURE/EQUIPMENT THAT ISOF INSUFFICIENT WIDTH
 FOR EXIT PATH EGRESS. PLEASE PROVIDE A MINIMUM
 COMPLIANT WIDTH OF 36" PER NFPA 101, CHAPTER 7, MEANS
 OF EGRESS.
  
 6. SHEET A 2.0 - THE 1-HOUR WALL DRAWING DOES NOT HAVE
 A U.L. LISTING NUMBER REFERENCE. PLEASE PROVIDE THE
 LISTING NUMBER.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-10 Cont ID  
Sent By   Date 2016-05-10 Time   Rev Time 0.00
Received By cpuell Date 2016-05-04 Time 06:38 Sent To  
Notes
2016-05-05 06:39:10VPEREZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-03-28 Time 16:22 Sent To  
Notes
2016-03-28 16:23:12B04