| 2016-04-07 07:04:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16031309 |
| | ADD: 600 BANYAN BLVD. |
| | CONT: JIJ CONSTRUCTION |
| | TEL: 561-574-5995 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. APRIL 07/2016 |
| | ACTION: DENIED |
| | |
| | 1) NEW LINE DRAFTING DESIGN DOES NOT HAVE THEIR LICENSE |
| | NUMBER AS BEING EITHER A ARCHITECT NOR ENGINEER IN THE |
| | TITLE BLOCK. NEW LINE DRAFTING DESIGN ALSO DOES NOT |
| | HAVE THEIR CERTIFICATE OF AUTHORIZATION LISTED ON THE |
| | PLANS. |
| | 61G15-30.003 ENGINEERING DOCUMENTS CLASSIFICATION. |
| | 471.023 CERTIFICATION OF BUSINESS. |
| | 61G1-16.004 TITLE BLOCK/ ARCHITECT. 481.2.19 |
| | CERTIFICATION OF CORPORATION. |
| | |
| | 2) SHEET A-2.0 DOES NOT INDICATE AS TO WHAT CODES THE |
| | PLANS WERE DEVELOPED, NOR DOES THE PLAN INDICATE UNDER |
| | THE EXISITNG BUILDING CODE WHAT METHOD OF COMPLIANCE |
| | WAS USED IN THE DESIGN CONCEPT. 2014 FBC-EXISITNG |
| | BUILDING CODE 301.1. |
| | |
| | 3) THE PLANS DO NOT PROVIDE THE MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL PLAN REVIEW. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS |
| | OCCUPANCY TYPE |
| | MINIMUM BUILDING TYPE |
| | FIRE SPRINKLERED OR NOT |
| | OCCUPANCY LOAD/ EGRESS REQUIREMENTS SHALL INCLUDE: |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | |
| | 4) SHEET A-2.0: |
| | 4A) THE 1 HOUR FIRE RATED WALL DOES NOT PROVIDE TO WHAT |
| | ASSEMBLY THE WALL IS BUILT? 2014 FBC-B 703.2 FIRE |
| | -RESISTANCE RATINGS. |
| | |
| | 4B) THE DESIGNER HAS INDICATED THE EXIT ACCESS CORRIDOR |
| | WALLS ARE TO BE 1 HOUR FIRE RATED. IN THE PROPOSED |
| | OFFICE USE SPACE THERE APPEARS TO BE 2 OPENINGS WITHOUT |
| | OPENING PROTECTIVES, POSSIBLY PASS THROUGH OPENINGS? |
| | SEE NOTE 5 NO IDENTIFICATION ON THE PLANS. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2014 FBC-B TABLE 716.5. OPENING PROTECTIVES. |
| | |
| | 4C) THE PLANS INDICATE THE INSTALLATION OF A 20 MINUTE |
| | RATED FIRE RATING OF GLASS AND FRAME. THE DESIGNER OF |
| | RECORD LIST EITHER THE OWNER OR CONTRACTOR PROVIDE UL |
| | APPROVED SHOP DRAWINGS. THE DESIGNER OF RECORD DOES NOT |
| | PROVIDE AS TO WHAT STANDARDS AND LISTINGS THE DESIGN IS |
| | TO BE TESTED TOO, INSUFFICIENT INFORMATION ON THE |
| | PLANS. 2014 FBC-B 716.2 FIRE RESISTANT RATED GLAZING. |
| | |
| | 4D) THE PLANS INDICATE A NEW DOOR OPENING IN THE ONE |
| | HOUR FIRE RATED WALL. 2014 FBC-B TABLE 716.5. |
| | |
| | 4E) THE NEW DOOR OPENING IN THE 1 HOUR FIRE RATED WALL |
| | DOES NOT INDICATE THE WIDTH OF THE NEW DOOR? 2014 FBC-B |
| | 1008.1.1. |
| | |
| | 4F) THERE IS NO DOOR SCHEDULE FOR THE EXISTING DOORS OR |
| | NEW DOOR WHICH WILL INDICATE THE TYPE OF HARDWARE TO BE |
| | INSTALLED ON THE FIRE RATED DOOR. FBC-B 716.5. |
| | |
| | 4G) THE PROPOSED OFFICE USE SPACE AT THE 2 WINDOWS ON |
| | THE INTERIOR SIDE OF THE OPENING HAS SOMETHING NOT |
| | IDENTIFIED DESK |
| | EVIDENCE LOCKERS, DOES THIS HAVE TO COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY CODE 902.3. HEIGHT. THE TOPS OF WORK |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 4H) PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| | FBC-ACCESSIBILITY CODE 902.3 FOR THE PROPOSED EVIDENCE |
| | TECH DESK AREA. |
| | |
| | 4I) THE DOOR LEADING FROM THE EXISTING EVIDENCE STORAGE |
| | AREA TO THE PROPOSED EVIDENCE TECH DESK AREA IN THE NEW |
| | WALL DOES NOT HAVE 18 INCHES ON THE LATCH SIDE OF THE |
| | DOOR. |
| | |
| | 4J) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |