Plan Review Details - Permit 16031268
Plan Review Stops For Permit 16031268
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-03-30 Cont ID  
Sent By tklarge Date 2016-03-30 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-03-30 Time 05:41 Sent To  
Notes
2016-03-30 06:37:141) INDICATE TYPE OF VENT MATERIAL FOR THE VENTS.
 2) SUBMIT A COPY OF THE INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER.FBC 107.2.1.
 3) SHOW THE HEIGHT OF THE VENTS ABOVE THE FINISH GRADE.
 COMPLY WITH THE INSTALLATION MANUAL.
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE NEW WATER
 HEATERS PER 2014 FUEL GAS CODE SEC.304.1.
 5) SUBMIT A GAS RISER DIAGRAM FOR CHANGES BEING MADE TO
 THE GAS PIPING. FBC 107.1.SHOW THE TOTAL DEVELOPED
 LENGTH FROM THE SOURCE OF DELIVERY ( METER) TO THE MOST
 REMOTE OUTLET.
 7) INDICATE ON THE PLANS THE TYPE OF GAS PIPE BEING
 INSTALLED.FBC 107.2.1.
 8) INDICATE ON THE PLANS THE PSI OF THE GAS SYSTEM.2014
 FGC SEC.402.2.
 9) A SEPARATE PERMIT IS REQUIRED FOR ELECTRIC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-30 Cont ID  
Sent By tklarge Date 2016-03-30 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-03-25 Time 10:21 Sent To  
Notes
2016-03-28 10:21:16PLUMB <5K

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-31 Cont ID  
Sent By ajones Date 2016-03-31 Time 15:23 Rev Time 0.00
Received By ajones Date 2016-03-31 Time 15:22 Sent To  
Notes
***NONE***