Plan Review Details - Permit 16031217
Plan Review Stops For Permit 16031217
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By rmcdouga Date 2016-04-26 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2016-04-26 Time 09:40 Sent To  
Notes
2016-04-26 09:52:14RELOCATE EXISTING POOL HEATING EQUIPMENT. NOT A
 SUBSTANTIAL IMPROVEMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By rmcdouga Date 2016-04-05 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2016-04-05 Time 11:15 Sent To  
Notes
2016-04-05 11:43:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL HEATING EQUIPMENT IS REQUIRED TO RESIST
 WINDLOADS. SUBMIT POOL HEATER TIE DOWN DETAILS. FBCR -
 M1307.2
  
 2) PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 THE POOL HEATER IS REQUIRED TO BE INSTALLED AT OR ABOVE
 7.5' BFE. FBCR 322.1.6
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By rmcdouga Date 2016-04-26 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2016-04-26 Time 09:44 Sent To  
Notes
2016-04-26 09:45:40EXISTING ELECTRIC POOL HEATER IS BEING RELOCATED. SEE
 ELECTRICAL PERMIT #16030391

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By rmcdouga Date 2016-04-05 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2016-04-05 Time 13:37 Sent To  
Notes
2016-04-05 11:49:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS TO
 SHOW THAT THE EXISTING SEVICE IS ADEQUATE. FBCR -
 E3602.2 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE CALCULATIONS IS REQUIRED TO BE ON
 THE SUBMITTALS. FBC 107.2.1
  
 2) THE POOL HEATING EQUIPMENT IS REQUIRED TO BE
 GROUNDED AND BONDED. FBCR - E4205.1, FBCR - E4204.2
  
 3) AN ELECTRICAL SUB-PERMIT IS REQUIRED TO INSTALL
 POWER TO THE POOL HEATER. FBC 105.1
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 05:25 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 05:25 Sent To  
Notes
2016-04-04 05:25:47THIS IS AN ELECTRIC POOL HEATER.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-27 Cont ID  
Sent By tklarge Date 2016-04-27 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-04-14 Time 14:43 Sent To  
Notes
2016-04-14 14:43:35RESUB ROUTED TO AJONES VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-05 Cont ID  
Sent By rmcdouga Date 2016-04-05 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2016-03-25 Time 08:58 Sent To  
Notes
2016-03-25 08:59:00ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By tklarge Date 2016-04-27 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-04-27 Time 05:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 05:39 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 05:25 Sent To  
Notes
2016-04-04 05:39:501) A TIME SWITCH IS REQD. ON THE HEATER. 2014
 FBC-ENERGY SEC.R403.9.2 TIME SWITCHES.
 TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS
 ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON
 ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT
 HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH
 THIS REQUIREMENT.
  
 EXCEPTIONS:
  
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
  
 2. WHERE PUMPS ARE REQUIRED TO OPERATE SOLAR- AND
 WASTE-HEAT-RECOVERY POOL HEATING SYSTEMS.
  
 3. WHERE PUMPS ARE POWERED EXCLUSIVELY FROM ON-SITE
 RENEWABLE GENERATION.
  
 2) A VAPOR RETARDANT POOL COVER IS REQD. PER 2014
 FBC-ENERGY SEC.R403.9.3.
 3) THE HEATER SHALL BE PROVIDED WITH A MEANS OF
 RETAINING WATER IN THE HEATER WHEN THE PUMP IS NOT IN
 OPERATION.
 R4501.14.2 WATER RETENTION.
 IF A HEATER IS NOT EQUIPPED OR DESIGNED FOR AN APPROVED
 PERMANENT BYPASS OR ANTISIPHON DEVICE, AN APPROVED
 PERMANENT BYPASS OR ANTISIPHON DEVICE SHALL BE
 INSTALLED TO PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN THE PUMP IS NOT IN OPERATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-04-21 Cont ID  
Sent By ajones Date 2016-04-21 Time 14:30 Rev Time 0.00
Received By ajones Date 2016-04-21 Time 14:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By ajones Date 2016-03-31 Time 15:37 Rev Time 0.00
Received By ajones Date 2016-03-31 Time 15:37 Sent To B
Notes
2016-03-31 15:41:393-31-16- FAILED
  
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. THE POOL
 EQUIP. MUST BE 11 FEET FROM THE SIDE AND REAR PROPERTY
 LINE.