Plan Review Details - Permit 16031201
Plan Review Stops For Permit 16031201
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By tklarge Date 2016-03-28 Time 14:29 Rev Time 0.00
Received By tklarge Date 2016-03-28 Time 14:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 08:34 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 08:19 Sent To  
Notes
2016-03-26 08:34:071) CLEARLY SHOW THE DEVELOPED LENGTH AND THE BTU LOAD
 OF THE 2 PSI SYSTEM ON THE GAS DRAWING. THE TOP OF THE
 DRAWING IS CUT OFF AND THE INFORMATION IS NOT CLEAR.
 FBC 107.2.1.
 2) CLEARLY IDENTIFY/LABEL THE STEP DOWN REGULATORS ON
 THE GAS DRAWING.
 3) EXPLAIN WHAT THE LETTERS "A" & "B" ON THE GAS
 DRAWING ARE FOR.
 4) INDICATE THE PIPE MATERIAL FOR THE 2 PSI 3/4" LINE
 FROM THE PE PIPE TO THE FUTURE SKILLET & THE FUTURE
 OVEN.IS THIS ALSO PE PIPE?
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-28 Cont ID  
Sent By tklarge Date 2016-03-28 Time 14:29 Rev Time 0.00
Received By tklarge Date 2016-03-28 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 08:34 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 08:38 Sent To  
Notes
2016-03-25 08:38:48REVISION ROUTED TO TKLARGE