Plan Review Details - Permit 16031153
Plan Review Stops For Permit 16031153
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 13:58 Rev Time 0.00
Received By mvaldes Date 2016-06-01 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By albarran Date 2016-03-31 Time 16:01 Rev Time 0.00
Received By albarran Date 2016-03-31 Time 15:01 Sent To  
Notes
2016-03-31 16:08:05ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. ACCORDING TO THE MANUFACTURER?S INSTRUCTIONS THIS
 SYSTEM REQUIRES THAT IT BE HARD WIRED AND TIED IN TO
 THE POOL?S EQUIPOTENTIAL BONDING GRID.
 2. PROVIDE A WIRING DIAGRAM INDICATING PROPER OVER
 CURRENT AND GFI PROTECTION AND SYSTEM BONDING.
 3. INDICATE WHETHER THIS WILL BE POWERED USING 120 OR
 240 VAC.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 14:00 Rev Time 0.00
Received By mvaldes Date 2016-05-05 Time 13:17 Sent To  
Notes
2016-05-05 13:18:11TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-05 Cont ID  
Sent By tklarge Date 2016-04-05 Time 05:15 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 09:28 Sent To  
Notes
2016-03-25 09:28:36ROUTED TO POOL INBOX PER SKENNEDY - MAY ONLY NEED
 PLUMBING REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-09 Cont ID  
Sent By tklarge Date 2016-05-09 Time 05:56 Rev Time 0.00
Received By tklarge Date 2016-05-09 Time 05:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-05 Cont ID  
Sent By tklarge Date 2016-04-05 Time 05:15 Rev Time 0.00
Received By tklarge Date 2016-04-05 Time 04:58 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved