Plan Review Details - Permit 16031072
Plan Review Stops For Permit 16031072
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-25 Cont ID  
Sent By hmoser Date 2016-03-25 Time 10:47 Rev Time 0.00
Received By hmoser Date 2016-03-23 Time 09:05 Sent To  
Notes
2016-03-24 09:05:33MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-03-25 Cont ID  
Sent By hmoser Date 2016-03-25 Time 10:29 Rev Time 0.00
Received By hmoser Date 2016-03-24 Time 14:18 Sent To  
Notes
2016-03-25 10:29:05PASS PROVISO
  
 1) TRANSFER GRILLS NOT REQUIRED IN UTILITY ROOM.
 BALANCED RETURN AIR
 REQUIRED FOR HABITABLE ROOMS ONLY SECTION M1602.4
 EXCEPTION #3
 BALANCED RETURN 2014 RESIDENTIAL CODE.
 2) USE CLIPS FROM BOTTOM OF UNIT TO SLAB. NOT CABLE
 OVER TOP OF
 UNIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  