| 2016-03-24 06:15:56 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030967 |
| | ADD: 1631 42ND ST. |
| | CONT: ALPHA SOUTH CONSTRUCTION |
| | TEL: 561-306-3183 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MARCH 24/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR SUBMITTED A MIAMI-DADE NOA 14-0224.03 |
| | CERTAIN TEED MODIFIED BITUMEN ROOF SYSTEMS OVER WOOD |
| | DECK. THE CONTRACTOR DID NOT IDENTIFY WHICH SUB-SYSTEM |
| | AND ASSOCIATED PRESSURE WAS GOING TO BE USED IN THE |
| | INSTALLATION. |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. IF |
| | SO RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A |
| | FLORIDA ARCHITECT OR ENGINEER. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 2) THIS INFORMATION CAN BE E-MAILED TO THE ADDRESS |
| | BELOW. |
| | |