Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-10 Cont ID  
Sent By rmcdouga Date 2016-05-10 Time 17:22 Rev Time 0.00
Received By rmcdouga Date 2016-05-10 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-25 Cont ID  
Sent By rmcdouga Date 2016-03-25 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2016-03-25 Time 07:26 Sent To  
Notes
2016-03-25 16:03:16REVISION DENIED BY MECHANICAL
  
 1) THE CFMS ARE NOT SPECIFIED FOR THE LIVING ROOM. FBC
 1007.2.1
  
 2) SEVERAL OF THE DUCT SIZES ARE NOT SPECIFIED ON THE
 DRAWINGS. SPECIFY ALL DUCT SIZES. FBC 107.2.1
  
 3) IT APPEARS THAT ONE OF THE SUPPLY DUCTS TO THE
 KITCHEN WAS MEANT TO BE DELETED. THERE ARE THREE
 SUPPLIES SHOWN AT THE KITCHEN. PLEASE CLARIFY. FBC
 107.2.1
  
 4) THE WALL RETURN IS REQUIRED TO BE DUCTED.
 FBCR-M1602.2