Plan Review Details - Permit 16030858
Plan Review Stops For Permit 16030858
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By jwitmer Date 2016-06-01 Time   Rev Time 0.00
Received By jwitmer Date 2016-06-01 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 10:48 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time 07:45 Sent To  
Notes
2016-04-06 10:48:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030858
 ADD: 255 EVERNIA ST. SUITE: MU-4
 CONT: COMPLETE PROPERTY MANAGEMENT
 TEL: 561-626-2778
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 06/2016
 ACTION: DENIED
  
 1) SHEET LS.01 IT APPEARS THIS TENNANT SPACE IS A MIXED
 USE OCCUPANCY WITH OVER 50 OCCUPANTS.
 THE DESIGNER OF RECORD INDICATES:
 42 SEATS
 04 EMPLOYEES
 05 OCCUPANTS MEZZANINE LEVEL
 -----------
 51 OCCUPANTS TOTAL
  
 THE PLANS ONLY SHOW 40 SEATS, THERE IS NO SQUARE
 FOOTAGE TAKEN FOR THE KIOSK, FIGURED 25 SQ. FT. PER
 KIOSK X 7= 175 SQ. FT/ 30= 6 PLUS THE 2 KITCHEN PLUS
 THE 500 SQ. FT. MEZZANINE/ 100= 5 OCCUPANTS.
 40 SEATS
 06 KIOSK
 02 KITCHEN
 05 MEZZANINE
 ---------------
 53 OCCUPANTS.
  
 WHEN OVER 49 OCCUPANTS (2) EXITS WILL BE REQUIRED. 2014
 FBC-B TABLE 1015.1.
  
 2) IT IS ONLY ASSUMED THE MEZZANINE LEVEL IS GOING TO
 BE A BUSINESS OCCUPANCY.SHEET LS.02 INDICATES AN
 EXISITNG OFFICE, IS THIS STILL BE THE SAME USE? IF THE
 USAGE CHANGES TO A HIGHER OCCUPANT LOAD THEN VERTICAL
 ACCESSIBILITY WILL BECOME A ISSUE,
 2014 FBC-ACCESIBLITY CODE 201.1.1 MAYBE EXEMPT UNDER
 (3) OCCUPIABLE SPACES THAT ARE NOT OPEN TO THE PUBLIC
 AND HOUSE NOT MORE THAN 5 PERSONS.
  
 3) NEITHER THE LIFE SAFETY PLANS OR 1ST FLOOR PLANS
 SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE;
 3A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2B) SHOW ACCESSIBLE SEATING AT TABLES AS WELL AS THE
 COUNTER. 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3) SHEET P.01 THE NEW RESTROOM DETAILS SHOW THE GRAB
 BARS DIMENSIONED 33-36 INCHES CENTERLINE FROM FINISH
 FLOOR. THIS IS A CHANGE IN THE 2014 FBC-B NOTE THE GRAB
 BARS ARE MEASURED FROM FINISH FLOOR TO THE TOP OF THE
 GRASPING SURFACE NOT CENTERLINED. 2014
 FBC-ACCESSIBILITY CODE 609.4 POSITION OF GRAB BARS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By vperez Date 2016-05-24 Time 13:42 Rev Time 0.00
Received By vperez Date 2016-05-24 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By vperez Date 2016-03-24 Time 06:53 Rev Time 0.00
Received By vperez Date 2016-03-23 Time 06:00 Sent To  
Notes
2016-03-24 06:57:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO ELECTRICAL SHEET- PLEASE REFLECTS CURRENT
 BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION
 FAMILY, NEC 2011.
 2. PLEASE PROVIDE A NOTE PER NEC 210.8B (2)(5) GFCI
 PROTECTION AT BAR AREA AND FOOD PREPARATION AREAS
 REQUIRED.
 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By pleduc Date 2016-05-24 Time   Rev Time 0.00
Received By pleduc Date 2016-05-23 Time 12:13 Sent To  
Notes
2016-05-23 12:32:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET LS.01, A.01 & A.02 - IN LIEU OF THE SIGN "NOT
 AN EXIT" PROVIDE A SIGN THAT STATES "EMERGENCY EXIT
 ONLY, ALARM WILL SOUND" AND PROVIDE AN PANIC HARDWARE
 THAT WILL ALRM WHEN PUSHED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 11:03 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 10:33 Sent To  
Notes
2016-03-24 11:03:35255 EVERNIA STREET SUITE MU-4
 PERMIT #16030858
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 SHEET LS-01: THE PLAN INDICATES A MERCANTILE OCCUPANCY
 UTILIZING AN OCCUPANCY LOAD FACTOR OF 30 SQ.FT. PER
 PERSON; HOWEVER, THIS OCCUPANCY IS AN ASSEMBLY
 OCCUPANCY REQUIRING AN OCCUPANT LOAD FACTOR OF 15
 SQ.FT. PER PERSON. AN ASSEMBLY OCCUPANCY IS DEFINED IN
 THE FIRE CODE AS, "AN OCCUPANCY USED FOR A GATHERING OF
 50 OR MORE PERSONS FOR DELIBERATION, WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR SIMILAR USES." TWO EXITS EQUIPPED
 WITH PANIC HARDWARE WILL BE REQUIRED. THE COMMON PATH
 OF TRAVEL FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD OF MORE THAN 50 PERSONS IS LIMITED TO 20 FEET.
  
 SUB-PERMITS: SEPARATE PLANS AND PERMITS ARE REQUIRED
 FOR THE INSTALLATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-23 Cont ID  
Sent By ccole Date 2016-06-23 Time 17:20 Rev Time 0.00
Received By ccole Date 2016-06-21 Time 10:15 Sent To  
Notes
2016-06-22 10:15:37RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-07 Cont ID  
Sent By cpuell Date 2016-06-07 Time 11:40 Rev Time 0.00
Received By cpuell Date 2016-05-13 Time 15:18 Sent To  
Notes
2016-05-16 15:18:28B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-18 Cont ID  
Sent By tklarge Date 2016-04-18 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-03-21 Time 10:44 Sent To  
Notes
2016-03-21 10:44:42B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By ccole Date 2016-06-23 Time 17:15 Rev Time 0.00
Received By ccole Date 2016-06-23 Time 17:15 Sent To  
Notes
2016-06-23 17:20:43MECHANICAL PROVISO
 PERMIT #16030858
 6/23/16
  
 1) THE SUBMITTED PLAN APPEARS INCOMPLETE WITH MUCH OF
 THE DUCTWORK NOT SHOWN ON BOTH THE 1ST AND 2ND FLOORS.
 PRIOR TO FINAL INSPECTION AND TO RECEIVING A CO, A
 REVISION TO THE MECHANICAL PLAN WILL BE REQUIRED TO
 SHOW ALL REQUIRED ALTERATIONS MADE TO THE EXISTING
 SYSTEMS TO ACCOMODATE THE NEW OCCUPANCY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-23 Cont ID  
Sent By ccole Date 2016-05-23 Time 07:46 Rev Time 0.00
Received By ccole Date 2016-05-23 Time 07:46 Sent To  
Notes
2016-05-23 07:50:422ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030858
 5/23/16
  
 1) THE RE-SUBMITTED MECHANICAL PLANS HAVE NOT BEEN
 REVISED OR CORRECTED COMPLETELY IN RESPONSE TO THE 1ST
 REVIEW COMMENTS, AND NO NARRATIVE RESPONSE WAS
 SUBMITTED TO EITHER REBUT THE COMMENTS OR CLARIFY THE
 SCOPE OF WORK. I AM RE-PRINTING THE COMMENTS BELOW FOR
 REVIEW:
 1ST REVIEW COMMENT #1) THE PLANS APPEAR TO INDICATE A
 CHANGE USE OR OCCUPANCY AS DEFINED IN THE FBC-14
 EXISTING BUILDING CODE. PLEASE REFER TO SECTION 1009.1
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED NEW BAR AND KITCHEN AREAS, AND ALL OTHER
 OCCUPIED ROOMS AND SPACES- SEE TABLE 403.3 FBC-14
 MECHANCIAL AND PROVIDE A SCHEDULE THAT INCLUDES THE
 REQUIRED CFMS OF OUTDOOR AIR AND THE CFMS PROVIDED.
 PLEASE NOTE THE EXISTING AC SYSTEM(S) MAY HAVE TO BE
 ENLARGED TO PROVIDE ADEQUATE FRESH AIR AND CONDITIONING
 TO THE SPACE DUE TO THE INCREASED OCCUPANT LOAD- SUBMIT
 AC CALCULATIONS.
 1ST REVIEW COMMENT #2) SHEET M0.1: PROVIDE A SCOPE OF
 WORK ON THE PLAN WITH CORRESPONDING DRAWINGS AND
 DETAILS INDICATING ALL ALTERATIONS TO THE EXISTING HVAC
 SYSTEMS. PLEASE NOTE THAT THE NEW KITCHEN WILL REQUIRE
 AN EXHAUST SYSTEM WITH A MINIMUM CAPACTITY OF .7 CFM
 PER SQ. FT.
 1ST REVIEW COMMENT #3) PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE NEW BATH EXHAUST FAN AND SHOW THE EXHAUST DUCT
 RUN AND TERMINATION LOCATION.
 1ST REVIEW COMMENT #4) PLEASE NOTE THAT ADDITIONAL
 MECHANICAL COMMENTS MAY FOLLOW AFTER THE PLANS HAVE
 BEEN CORRECTED IN ACCORDANCE WITH ALL DEVELOPMENT
 DEPARTMENT REVIEWS.
 2) PLEASE SHOW THE POINT OF CONNECTION FOR THE TWO
 TOILET ROOM EXHAUST DUCTS TO THE MAIN EXHAUST DUCT- THE
 CURRENT PLAN SHOWS ONE EXHAUST DUCT CONNECTING TWO
 FANS. PLEASE SEE TABLE 403.3 FOOTNOTE E AND INDICATE IF
 THE EXHAUST WILL RUN INTERMITTENLY OR CONTINUOUSLY WHEN
 OCCUPIED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-25 Cont ID  
Sent By ccole Date 2016-03-25 Time 11:59 Rev Time 0.00
Received By ccole Date 2016-03-25 Time 13:55 Sent To  
Notes
2016-03-25 12:29:071ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT 16030858
 3/25/16
  
 1) THE PLANS APPEAR TO INDICATE A CHANGE USE OR
 OCCUPANCY AS DEFINED IN THE FBC-14 EXISTING BUILDING
 CODE. PLEASE REFER TO SECTION 1009.1 AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR THE PROPOSED NEW
 BAR AND KITCHEN AREAS, AND ALL OTHER OCCUPIED ROOMS AND
 SPACES- SEE TABLE 403.3 FBC-14 MECHANCIAL AND PROVIDE A
 SCHEDULE THAT INCLUDES THE REQUIRED CFMS OF OUTDOOR AIR
 AND THE CFMS PROVIDED. PLEASE NOTE THE EXISTING AC
 SYSTEM(S) MAY HAVE TO BE ENLARGED TO PROVIDE ADEQUATE
 FRESH AIR AND CONDITIONING TO THE SPACE DUE TO THE
 INCREASED OCCUPANT LOAD- SUBMIT AC CALCULATIONS.
 2) SHEET M0.1: PROVIDE A SCOPE OF WORK ON THE PLAN WITH
 CORRESPONDING DRAWINGS AND DETAILS INDICATING ALL
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS. PLEASE NOTE
 THAT THE NEW KITCHEN WILL REQUIRE AN EXHAUST SYSTEM
 WITH A MINIMUM CAPACTITY OF .7 CFM PER SQ. FT.
 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW BATH
 EXHAUST FAN AND SHOW THE EXHAUST DUCT RUN AND
 TERMINATION LOCATION.
 4) PLEASE NOTE THAT ADDITIONAL MECHANICAL COMMENTS MAY
 FOLLOW AFTER THE PLANS HAVE BEEN CORRECTED IN
 ACCORDANCE WITH ALL DEVELOPMENT DEPARTMENT REVIEWS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By gjohnson Date 2016-06-23 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2016-06-23 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 16:31 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 16:31 Sent To  
Notes
2016-05-18 16:52:102ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: IT APPEARS THAT COMMENTS FROM FIRST
 REVIEW WERE NOT ADDRESSED THIS IS THE SECOND REQUEST.
  
 1) SHT. LS.01 - THE OCCUPANCY OF THIS SPACE IS NOTED AS
 "MERCHANT" & "M" AND THE WORD "ASSEMBLY" IS HANDWRITTEN
 IN. ALSO, SHT. A.01 LISTS THE OCCUPANCY AS A-2.CLARIFY
 THE OCCUPANCY OF THIS SPACE PER 2014 FBC SEC.302.
 2) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. IT
 APPEARS AS THOUGH THE OCCUPANT LOAD WILL EXCEED 50
 PERSONS.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC - ACCESSIBILITY SEC.
 609.4.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE UNDER
 THE SINK GREASE TRAP AND SUBMIT SIZING CALCULATIONS PER
 THE FPC SEC.1003.2, 1003.3.4.
 5) SHT. P.01 - AS DRAWN, THE URINAL IN THE MEN'S
 RESTROOM IS ON A WET VENT.ONLY THE FIXTURES IN A
 BATHROOM GROUP ARE PERMITTED ON A WET VENT PER THE 2014
 FPC SEC.912.1 ( REFER TO THE DEFINITION OF "BATHROOM
 GROUP" IN THE DEFINITIONS OF THE FPC.)
 6) SUBMIT AN EXPANDED SANITARY RISER FOR THE THREE
 COMPARTMENT SINK. IT IS EXTREMELY DIFFICULT TO REVIEW.
 FBC 107.2.1.
 7) THE WATER RISER SHOWS THE INSTALLATION OF AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED FOR THE CONTROL
 OF WATER HAMMER. WATER HAMMER ARRESTORS ARE REQUIRED
 AND SHALL COMPLY WITH 2014 FPC SEC.604.9.
 8) IS THIS A CHANGE OF OCCUPANCY? IF SO, THEN TWO
 DRINKING FOUNTAINS ARE REQUIRED PER THE FAC. SEC. 211.2
 AND FOOTNOTE # ( E ) OF TABLE 403.1 OF 2014 FPC.
  
 ADDITIONAL COMMENTS:
  
 9. URINAL SHALL COMPLY WITH FBC ACC SEC. 605.2 HEIGHT
 AND DEPTH.
 URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE
 WITH THE RIM 17 INCHES (430 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES
 (345 MM) DEEP MINIMUM MEASURED FROM THE OUTER FACE OF
 THE URINAL RIM TO THE BACK OF THE FIXTURE.
  
 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED.
  
 605.4 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 SHOW DIMENSION ON PLAN PER WPB AMEND TO FBC 107.2.1
  
 10. DRINKING FOUNTAIN SHALL COMPLY WITH FBC ACC SEC.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 SHOW DIMENSIONS ON PLAN PER WPB AMEND TO FBC 107.2.1
  
 11. LAVATORY'S SHALL COMPLY WITH FBC ACC SEC. 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 SHOW DIMENSION ON PLAN PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By tklarge Date 2016-04-18 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-04-15 Time 05:09 Sent To  
Notes
2016-04-18 06:32:551) SHT. LS.01 - THE OCCUPANCY OF THIS SPACE IS NOTED AS
 "MERCHANT" & "M" AND THE WORD "ASSEMBLY" IS HANDWRITTEN
 IN. ALSO, SHT. A.01 LISTS THE OCCUPANCY AS A-2.CLARIFY
 THE OCCCUPANCY OF THIS SPACE PER 2014 FBC SEC.302.
 2) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. IT
 APPEARS AS THOUGH THE OCCUPANT LOAD WILL EXCEED 50
 PERSONS.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC - ACCESSIBILITY SEC.
 609.4.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE UNDER
 THE SINK GREASE TRAP AND SUBMIT SIZING CALCULATIONS PER
 THE FPC SEC.1003.2, 1003.3.4.
 5) SHT. P.01 - AS DRAWN, THE URINAL IN THE MEN'S
 RESTROOM IS ON A WET VENT.ONLY THE FIXTURES IN A
 BATHROOM GROUP ARE PERMITTED ON A WET VENT PER THE 2014
 FPC SEC.912.1 ( REFER TO THE DEFINITION OF "BATHROOM
 GROUP" IN THE DEFINITIONS OF THE FPC.)
 6) SUBMIT AN EXPANDED SANITARY RISER FOR THE THREE
 COMPARTMENT SINK. IT IS EXTREMELY DIFFICULT TO REVIEW.
 FBC 107.2.1.
 7) THE WATER RISER SHOWS THE INSTALLATION OF AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED FOR THE CONTROL
 OF WATER HAMMER. WATER HAMMER ARRESTORS ARE REQUIRED
 AND SHALL COMPLY WITH 2014 FPC SEC.604.9.
 8) IS THIS A CHANGE OF OCCUPANCY? IF SO, THEN TWO
 DRINKING FOUNTAINS ARE REQUIRED PER THE FAC. SEC. 211.2
 AND FOOTNOTE # ( E ) OF TABLE 403.1 OF 2014 FPC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-07 Cont ID  
Sent By aaponte Date 2016-06-07 Time 09:46 Rev Time 0.00
Received By aaponte Date 2016-06-07 Time 09:46 Sent To  
Notes
2016-06-07 10:04:13ALCOHOL REGS APPLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By aaponte Date 2016-04-12 Time 12:26 Rev Time 0.00
Received By aaponte Date 2016-04-12 Time 12:26 Sent To  
Notes
2016-04-12 12:26:39ALCOHOL REGULATIONS APPLY.