Plan Review Details - Permit 16030838
Plan Review Stops For Permit 16030838
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-31 Cont ID  
Sent By cthroop Date 2016-05-31 Time 14:56 Rev Time 0.00
Received By cthroop Date 2016-05-31 Time 14:56 Sent To  
Notes
2016-05-31 15:01:43CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 DATE: 5/31/16
 ACTION: FAIL
  
 1. VALUE APPEARS LOW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 2. PROVIDE PRODUCT APPROVALS FOR ALL EXTERIOR DOORS AND
 WINDOWS SUBJECT TO WIND LOAD.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 11:38 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 11:38 Sent To  
Notes
2016-03-22 11:49:391ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
  
 PER THE MINIMUM PLAN REVIEW REQUIREMENTS FOUND IN FBC
 107, YOU MUST DECLARE THE CODE REFERENCE AND LEVEL OF
 WORK. FOR YOUR CONVENIENCE, THE APPLICABLE CODE IS: THE
 FBC 2014 5TH ED EXISTING BUILDING. IT SEEMS THE LEVEL
 OF WORK IS EITHER A REPAIR OR MORE LIKELY AN ALTERATION
 LEVEL I. PLEASE SEE SECTIONS 502 & 503 BELOW SO YOU MAY
 MAKE A DETERMINATION.
 SECTION 502 REPAIRS
  
 502.1 SCOPE.
 REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE PATCHING
 OR RESTORATION OR REPLACEMENT OF DAMAGED MATERIALS,
 ELEMENTS, EQUIPMENT OR FIXTURES FOR THE PURPOSE OF
 MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND CONDITION
 WITH RESPECT TO EXISTING LOADS OR PERFORMANCE
 REQUIREMENTS.
  
 502.2 APPLICATION.
 REPAIRS SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 6.
  
 502.3 RELATED WORK.
 WORK ON NONDAMAGED COMPONENTS THAT IS NECESSARY FOR THE
 REQUIRED REPAIR OF DAMAGED COMPONENTS SHALL BE
 CONSIDERED PART OF THE REPAIR AND SHALL NOT BE SUBJECT
 TO THE PROVISIONS OF CHAPTER 7, 8, 9, 10 OR 11.
  
 SECTION 503 ALTERATION?LEVEL 1
  
 503.1 SCOPE.
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT
 OR THE COVERING OF EXISTING MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE.
  
 503.2 APPLICATION.
 LEVEL 1 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 7.
  
 PLEASE ALSO INDICATE THE OCCUPANCY CLASSIFICATION AND
 TYPE OF CONSTRUCTION OF THE BUILDING AS DEFINED IN FBC
 CHAPTERS 3 & 6. FOR YOUR CONVENIENCE, THE OCCUPANCY
 CLASSIFICATION IS R-3.
  
 ADDITIONALLY, YOU MUST PRINT YOUR NAME AND LICENSE
 NUMBER ON THE PLAN AND SIGN THE DRAWING PER FBC 107.2.1
 PLEASE ALSO PROVIDE A MORE COMPREHENSIVE SCOPE OF WORK.
 A COPY OF YOUR CONTRACT OR CONTRACTS MAY BE HELPFUL IF
 THEY CONTAIN A SCOPE OF WORK. ALSO, IF ELECTRICAL
 FIXTURES, PLUMBING FIXTURES AND CABINETRY & TOPS ARE
 BEING REPLACED, INDICATE TO WHAT EXTENT AND IF THE
 LAYOUT IS TO BE ALTERED OR NOT. PLEASE IDENTIFY THE
 MATERIALS TO BE USED TO ASSURE COMPLIANCE WITH THE
 DESIGN PARAMETERS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-31 Cont ID  
Sent By cthroop Date 2016-05-31 Time 14:56 Rev Time 0.00
Received By cthroop Date 2016-05-26 Time 12:51 Sent To  
Notes
2016-05-27 12:52:10RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 11:38 Rev Time 0.00
Received By cthroop Date 2016-03-18 Time 08:58 Sent To  
Notes
2016-03-21 08:58:16BLDG <5K - NO PLANS SUBMITTED.