Plan Review Details - Permit 16030836
Plan Review Stops For Permit 16030836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-28 Cont ID  
Sent By shill Date 2016-05-28 Time 11:45 Rev Time 0.00
Received By shill Date 2016-05-28 Time 11:45 Sent To  
Notes
2016-05-28 11:48:14PROVISOS
 REVISION REQUIRED
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL, REVIEWED BY
 DESIGNER OF RECORD, TO BE SUBMITTED AS A REVISION PRIOR
 TO INSTALLATION.
  
 2. ENERGY CALCS PROVIDED REFERENCE FBC 2010. SEE
 MECHANICAL COMMENTS. A BUILDING REVIEW OF ENERGY CALCS
 WILL BE REQUIRED. PROVIDE COMPLIANT ENERGY CALC, FBC
 5TH EDITION ENERGY CONSERVATION C103.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-01 Cont ID  
Sent By jwitmer Date 2016-04-01 Time   Rev Time  
Received By jwitmer Date 2016-04-01 Time 08:33 Sent To  
Notes
2016-04-01 10:03:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030836
 ADD: 701 S. ROSEMARY AVE. SUITE # 123
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-213-6975
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. APRIL 1/ 2016
 ACTION: DENIED
  
 1) SHEET A101:
 1A) THE THE COVERSHEET LIST THE OCCUPANT LOAD OF 54
 OCCUPANTS WITH THE REQUIRED 2 EXITS. THERE IS NO LIFE
 SAFETY PLANS SHOWING WHERE THE 2ND REQUIRED EXIT IS
 LOCATED. WITH THE 2ND EXIT BEING A BACK OF HOUSE EXIT
 DISCHRGE INTO A EXIT PASSAGEWAY. ASSUMED DOOR # 4 BEING
 THE EXIT FROM THE TENNANT SPACEINTO THE 1 HOUR FIRE
 RATED EXIT PASSAGE WAY THE WALLS OF THE BACK OF HOUSE
 EXIT PASSAGEWAY SHOULD SHOW AS A ONE HOUR FIRE RATING
 WITH OPENING PROTECTIVE RATING AT DOOR # 4 EVEN IF
 EXISITNG SHOW RATING.
  
 2014 FBC-B 1023.3 CONSTRUCTION. EXIT PASSAGEWAY
 ENCLOSURES SHALL HAVE WALLS, FLOORS AND CEILINGS OF NOT
 LESS THAN A 1-HOUR FIRE-RESISTANCE RATING, AND NOT LESS
 THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR EXIT
 STAIRWAY OR RAMP. EXIT PASSAGEWAYS SHALL BE CONSTRUCTED
 AS FIRE BARRIERS IN ACCORDANCE WITH SECTION 707 .
  
 2014 FBC-B 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES.
  
 1B) NOTE ON THE PLAN INDICATING (E) EXISITING STEEL
 COLUMN WITH NEW SURROUND. 2 1/2 INCH STEEL STUDS WITH
 TYPE X 5/8 INCH GYPSUM BOARD TO DECK ABOVE. THE STEEL
 COLUMN AS SHOWN PENETRATES THE 1 HOUR FIRE RATED WALL.
 PLEASE NOT ONLY PROVIDE A UL NUMBER FOR WALL RATING BUT
 SHOW THE ACTUAL UL DETAIL ASSEMBLY FOR THE INSPECTOR
 WILL BE ABLE TO VIEW THE WALL CONSTRUCTION AS PER THE
 UL FIRE RATING.
 2014 FBC-B 708.4. CONTINUITY.
  
 1C) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 906.1 WHERE
 FIRE EXTINGUISHERS ARE REQUIRED.
  
 2) SHEET A102 THE REFLECTED CEILING PLAN (2) EXITS
 REQUIRED. THE PLANS SHOWS THE EXIT SIGN OVER THE FRONT
 ENTRY DOOR BUT NOT OVER THE DOORWAY LEADING TO THE BACK
 OF HOUSE AREA AND THE 2ND REQUIRED EXIT.
 2014 1015.1 TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT
 ACCESS DOORWAY.
 2014 FBC-B SECTION 1011 EXIT SIGNS 1011.1 WHERE
 REQUIRED.
  
 3) SHEET A201 DETAILS 1 & 5 SHOW THE ACCESSIBLE
 HANDRAIL CENTERLINE 33-36 INCHES WHEREAS THE 2014
 FBC-ACCESS. CODE 609.4 POSITION OF GRAB BAR IS MEASURED
 FROM FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE
 NOT THE CENTERLINE.
  
 4) SHEET A300 INDICATES NEW STOREFRONT WINDOW UNITS AS
 WELL AS NEW STORFRONT DOORS. PLEASE SHOW COMPLIANCE
 WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. /MULLIONS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS/ MULLIONS
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 13:49 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 13:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-21 Cont ID  
Sent By mvaldes Date 2016-03-21 Time 18:18 Rev Time 0.00
Received By mvaldes Date 2016-03-21 Time 18:18 Sent To  
Notes
2016-03-21 18:19:29PASSED WITH A PROVISO
  
  
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE. ACCORDING TO
 THE CHART 1.4 WATTS PER SQUARE FEET IS THE ALLOWANCE
 FOR RETAIL THEREFORE YOUR DESIGN OF 3156 WATTS IS
 NON-COMPLIANT. REEVALUATE AND ADJUST.
 - SHOW WINDOWS SHALL BE CALCULATED AT 125 % FOR
 CONTINUOUS LOAD DEMANDS , HOWEVER THIS DOESN?T
 INFLUENCE THE LOAD CAPACITY BUT SINCE CALCULATION WERE
 ITEMIZED IT WILL COMPROMISE THE INTEGRITY OF THE PRINT
 RE-ADJUST ACCORDINGLY. NEC 220 AND DEFINITIONS ARTICLE
 100 ?CONTINUOUS LOAD?.
 - NEC 110.16,110.24 PROVIDE ARC-FLASH HAZARD WARNING
 LABEL AND AVAILABLE FAULT CURRENT MARKING.
  
  
 REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By pleduc Date 2016-05-24 Time   Rev Time 0.00
Received By pleduc Date 2016-05-23 Time 12:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 10:31 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 16:10 Rev Time 0.00
Received By ccole Date 2016-06-14 Time 13:01 Sent To  
Notes
2016-06-14 13:01:28RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-14 Cont ID  
Sent By skennedy Date 2016-06-14 Time 08:47 Rev Time 0.00
Received By skennedy Date 2016-05-19 Time 13:29 Sent To  
Notes
2016-05-20 13:30:07B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-14 Cont ID  
Sent By eschneid Date 2016-04-14 Time 15:44 Rev Time 0.00
Received By eschneid Date 2016-03-18 Time 14:58 Sent To  
Notes
2016-03-18 14:58:14B28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-01 Cont ID  
Sent By jwitmer Date 2016-04-01 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2016-04-01 Time 08:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 16:10 Rev Time 0.00
Received By ccole Date 2016-06-14 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-26 Cont ID  
Sent By ccole Date 2016-05-26 Time 08:46 Rev Time 0.00
Received By ccole Date 2016-05-26 Time 08:46 Sent To  
Notes
2016-05-26 08:54:182ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030836
 5/26/16
  
 1) THE REVISED PLAN INDICATES A NEW PLENUM SPACE ABOVE
 THE CEILING IN THE BACK ROOM AREAS- PLEASE PLACE NOTES
 ON THE PLANS PURSUANT TO SECTIONS 602 FBC-14
 MECHANICAL, AND SECTION C403.2.7.3 FBC-14 ENERGY
 CONSERVATION.
 2) SUBMIT UPDATED ENERGY CALCULATIONS- THE SUBMITTED
 FORM IS OUTDATED. THE CURRENT CODE IN EFFECT IS 2014-
 SEE SECTION C401.2 FBC-14 ENERGY CONSERVATION FOR
 COMPLIANCE PATHS. PLEASE NOTE THAT TWO COPIES OF ALL
 SUBMITTALS IS REQUIRED.
 3) INDICATE HOW ACCESS FOR SERVICE AND MAINTENANCE OF
 AHU-1 WILL BE PROVIDED- SECTION 306.1 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-25 Cont ID  
Sent By ccole Date 2016-03-25 Time 11:20 Rev Time 0.00
Received By ccole Date 2016-03-25 Time 11:20 Sent To  
Notes
2016-03-25 11:26:501ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030836
 3/25/16
  
 1) THE 24"X24" TRANSFER GRILL IS UNDERSIZED PER SECTION
 601.5 FBC-14 MECHANICAL. THE GRILL SHALL HAVE A MINIMUM
 OF 1325 SQ. INCHES OF FREE AIR SPACE TO RETURN 2650
 CFMS OF SUPPLY AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By gjohnson Date 2016-05-31 Time 14:57 Rev Time 0.00
Received By gjohnson Date 2016-05-31 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-14 Cont ID  
Sent By gjohnson Date 2016-04-14 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2016-04-14 Time 13:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2016-08-16 Cont ID  
Sent By eschneid Date 2016-08-16 Time 09:50 Rev Time 0.00
Received By eschneid Date 2016-08-16 Time 09:49 Sent To  
Notes
2016-08-16 09:50:52ERROR STOP ADDED HERE INSTEAD OF THE REVISION.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-25 Cont ID  
Sent By eschneid Date 2016-05-25 Time 13:54 Rev Time 0.25
Received By eschneid Date 2016-05-24 Time 16:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By eschneid Date 2016-04-14 Time 15:39 Rev Time 0.25
Received By eschneid Date 2016-04-14 Time 15:39 Sent To  
Notes
2016-04-14 15:44:20FAILED
  
 1) PLEASE PROVIDE AN ELEVATION DRAWING OR PHOTO OF THE
 EXISTING BAY STOREFRONT, WITH DIMENSIONS, SO THAT
 ZONING STAFF CAN VERIFY THAT THE STOREFRONT GLAZING IS
 NOT BEING REDUCED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.