| 2016-06-30 10:45:12 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DATE: 6/30/16 |
| | |
| | 1. EQUIPTMENT TO BE LOCATED IN FLOOD HAZARD AREA AE |
| | WITH A MINIMUM BASE FLOOD ELEVATION OF 7.0 FEET. |
| | 2. INSTALL EQUIPTMENT PER FBCM 301.16. |
| | 3. PROVIDE DESIGN THAT COMPLIES WITH FBC 1612.4 |
| | 4. ESTABLISH ELEVATION PER FBC 1612.5 |
| | 5. PROVIDE FLOOD ELEVATION CERTIFICATE. |
| | |
| | [B] 301.16 FLOOD HAZARD. |
| | FOR STRUCTURES LOCATED IN FLOOD HAZARD AREAS, |
| | MECHANICAL SYSTEMS, EQUIPMENT AND APPLIANCES SHALL BE |
| | LOCATED AT OR ABOVE THE ELEVATION REQUIRED BY SECTION |
| | 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR |
| | UTILITIES AND ATTENDANT EQUIPMENT. |
| | |
| | 1612.4 DESIGN AND CONSTRUCTION. |
| | THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES |
| | LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH |
| | HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF |
| | ASCE 7 AND WITH ASCE 24. |
| | |
| | 1612.5 FLOOD HAZARD DOCUMENTATION. |
| | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL: |
| | |
| | 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN |
| | COASTAL HIGH HAZARD AREAS: |
| | 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING |
| | BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND |
| | THE FINAL INSPECTION IN SECTION 110.3. |
| | |
| | 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD |
| | ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC |
| | ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM |
| | REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC |
| | FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE |
| | 24. |
| | |
| | |