Plan Review Details - Permit 16030772
Plan Review Stops For Permit 16030772
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 16:29 Rev Time  
Received By jwitmer Date 2016-03-24 Time 2:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-17 Cont ID  
Sent By rlecky Date 2016-03-17 Time 12:12 Rev Time 0.00
Received By rlecky Date 2016-03-17 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 10:10 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 10:26 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 14:54 Sent To  
Notes
2016-04-05 14:54:55ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 05:18 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 05:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 16:29 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 10:26 Rev Time 0.00
Received By ccole Date 2016-04-11 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By ccole Date 2016-03-21 Time 11:46 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 11:46 Sent To  
Notes
2016-03-21 12:13:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030772
 3/21/16
  
  
 1) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE
 REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE
 LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR
 ACTIVATES.
 2) M1: THE 10" FLEX DUCTS SUPPLYING 350 CFMS FOR AHU'S
 #1, 2, & 6 NEED TO INCREASE TO 12".
 3) M1: THE EXHAUST FROM EF-1 SHALL DISCHARGE TO THE
 OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14
 MECHANICAL.
 4) M2: THERE IS A DETAIL FOR TIE DOWN OF A AC CONDENSER
 UNIT TO AN EXISTING ROOF STAND, HOWEVER THERE ARE NO
 NEW CONDENSERS SHOWN ON THE PLANS: PLEASE CLARIFY
 5) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR
 SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND
 MOTORIZED DAMPERS WILL BE PROVIDED.
 6) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION
 DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-09 Cont ID  
Sent By tklarge Date 2016-04-09 Time 03:56 Rev Time 0.00
Received By tklarge Date 2016-04-09 Time 03:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 05:18 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 05:08 Sent To  
Notes
2016-03-26 05:18:141) PROVIDE SANITARY & WATER RISER DIAGRAMS FOR ALL
 CHANGES TO THE PLUMBING SYSTEM. CLARIFY.FBC
 107.3.5.1.3.
 2) THE WATER SUPPLY TO THE COFFEE MACHINES SHALL BE
 PROTECTED AGAINST BACKFLOW PER 2014 FBC-PLUMBING
 SEC.608.16.10.
 3) HOT WATER SHALL BE SUPPLIED TO THE BREAKROOM SINK
 PER 2014 FBC-PLUMBING SEC.607.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2016-03-17 Cont ID  
Sent By rlecky Date 2016-03-17 Time 12:14 Rev Time 0.00
Received By rlecky Date 2016-03-17 Time 12:13 Sent To  
Notes
2016-03-17 12:16:10ZONING APPROVAL WITH PERMIT # 16030424 AS BOTH SUITES
 WERE INCLUDED WITH THE INITIAL APPLICATION. RL