Plan Review Details - Permit 16030755
| Plan Review Stops For Permit 16030755 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2016-04-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-04-06 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-04-06 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-04-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-04-02 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-04-02 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2016-04-02 11:03:23 | RE-ROOF THIRD BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | | | | 1- RAS 117 CALCULATIONS SUBMITTED: | | | A) THE NAIL ENHANCEMENT PATTERN SPECIFIED BY THE | | | ENGINEER FOR ZONE 1 IS LESS THAN THE THE NAILING | | | PATTERN SPECIFIED ON NEW ASSEMBLY W-62. THE NAILING | | | PATTERN CAN NOT BE LESS THAN THE PATTERN SPECIFIED BY | | | THE SELECTED ASSEMBLY. SEE SEC. 8.1 OF RAS 117. (REPEAT | | | COMMENT). | | | | | | B) NAIL SPACING FOR ZONE #3 CAN NOT BE LESS THAN 4" | | | O.C.. SEE RAS 117 SEC. 8.1. | | | | | | C) THE DESIGN PRESSURES SHOWN ON THE ACTUAL RAS 117 | | | CALCULATIONS SUBMITTED DON'T MATCH THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER ON THE COVER PAGE SUBMITTED. | | | REVISE AS REQUIRED. SEC. 1609.1 OF FBC-BUILDING, 5TH | | | EDITION (2014). | | | | | | D) THE BASE SHEET WIDTH SHOWN ON THE ACTUAL RAS 117 | | | CALCULATIONS IS INCORRECT. SEE GLASBASE BASE SHEET | | | TECHNICAL INFORMATION AND REVISE AS REQUIRED. INCORRECT | | | SIZE MAY AFFECT THE CALCULATIONS. SEC. 1609.1 OF | | | FBC-BUILDING, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-03-23 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-03-23 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2016-03-23 08:26:58 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- THE DESIGN PRESSURES OF SELECTED ASSEMBLY W-58 ARE | | | -45PSF. THESE PRESSURES ARE LOWER THAN THE ENGINEER'S | | | CALCULATED DESIGN PRESSURES SUBMITTED FOR ROOF ZONE #1. | | | THE SELECTED ASSEMBLY CAN NOT BE USED. SEE NOTE #8 OF | | | FLORIDA PRODUCT APPROVAL FL2533-R5 SUBMITTED AND SEC. | | | 8.1 OF RAS 117. REVISE AS REQUIRED TO COMPLY. | | | | | | RESPONSE: | | | THE NAIL ENHANCEMENT PATTERN SPECIFIED BY THE ENGINEER | | | IS LESS THAN THE THE NAILING PATTERN SPECIFIED ON NEW | | | ASSEMBLY W-61. THE NAILING PATTERN CAN NOT BE LESS THAN | | | THE PATTERN SPECIFIED BY THE SELECTED ASSEMBLY. SEE | | | SEC. 8.1 OF RAS 117. ENGINEER TO PROVIDE COMPLETE RAS | | | 117 CALCULATIONS AS REQUIRED BY SEC. 107.2.1.3 CITY | | | AMENDMENTS. | | | NOTE: CALCULATIONS SUBMITTED REFER TO ASCE 7-05. | | | ENGINEER TO PROVIDE CALCULATIONS USING ASCE 7-10 WHICH | | | IS THE CURRENT EDITION ADOPTED BY FBC-2014. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-03-18 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-03-18 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2016-03-18 11:00:04 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- THE DESIGN PRESSURES OF SELECTED ASSEMBLY W-58 ARE | | | -45PSF. THESE PRESSURES ARE LOWER THAN THE ENGINEER'S | | | CALCULATED DESIGN PRESSURES SUBMITTED FOR ROOF ZONE #1. | | | THE SELECTED ASSEMBLY CAN NOT BE USED. SEE NOTE #8 OF | | | FLORIDA PRODUCT APPROVAL FL2533-R5 SUBMITTED AND SEC. | | | 8.1 OF RAS 117. REVISE AS REQUIRED TO COMPLY. | | | | | | 2- ROOF ASSEMBLY COMPONENTS SPECIFIED BY THE ENGINEER | | | DON'T MATCH COMPONENTS SHOWN ON THE SELECTED APPROVED | | | ASSEMBLY W-58 SUBMITTED. ENGINEER TO MATCH | | | SPECIFICATIONS WITH SELECTED ASSEMBLY. ALSO, COORDINATE | | | WITH ITEM #1 ABOVE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 3- | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-04-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-04-02 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-03-30 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2016-03-30 11:31:13 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-03-17 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-03-17 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2016-03-17 14:58:07 | JGOMEZ |
|
|
|