Plan Review Details - Permit 16030728
Plan Review Stops For Permit 16030728
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By jwitmer Date 2016-05-04 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2016-05-04 Time 06:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 06:46 Sent To  
Notes
2016-03-21 08:23:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030728
 ADD: 525 S. FLAGLER DR. PH2AB
 CONT: STELLAR CONSTRUCTION MANAGEMENT
 TEL: 561-832-4950
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21/ 2016
 ACTION: DENIED
  
 1) SHEET A550 INDICATES POSITIVE AND NEGATIVE
 PRESSURES, THERE IS NO WIND DESIGN CRITERIA GIVEN TO
 VALIDATE PRESSURES, PRESSURES ARE NOT INDICATED IF VULT
 OR VASD. MEAN ROOF HEIGHT OF THE BUILDING NOT GIVEN, IF
 THE OPENINGS ARE LOCATED IN A ZONE 4 OR 5, NOR THE
 EXPOSURE.
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) THE 3 MIAMI-DADE NOA?S TECHNICAL SHEETS ARE CUT OFF,
 THE FULL SHEET IS NOT REPRESENTED, VALUES OF THESE 3
 PRODUCT APPROVALS CAN NOT BE APPROVED AT THIS TIME.
 WHEN COPIED THE PERSON COPYING THESE REPORTS SHOULD
 HAVE WENT TO PRINT PREVIEW AND REDUCE TO 70% FOR THE
 FULL TECHNICAL SHEET TO BE REPRODUCED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 3) SHEET A100 INDICATES THE INSTALLATION OF NEW WOOD
 FLOORS AS WELL AS MARBLE FLOORS.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS FOR WOOD AND FOR MARBLE
 FLOORS SHOWING COMPLIANCE WITH:
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By vperez Date 2016-05-09 Time 15:47 Rev Time 0.00
Received By vperez Date 2016-05-09 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By vperez Date 2016-04-13 Time 14:44 Rev Time 0.00
Received By vperez Date 2016-04-13 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-18 Cont ID  
Sent By vperez Date 2016-03-18 Time 09:18 Rev Time 0.00
Received By vperez Date 2016-03-18 Time 09:18 Sent To  
Notes
2016-03-18 09:28:39INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO TO SHOW ON REVISION A NOTE TO INDICATE THE
 REQUIRED SEPARATE PERMITS FOR ANY LOW VOLTAGE SYSTEMS.
 2. ADD NOTE AT THE PANEL LOCATIONS TO INDICATE FBC RES
 E3405.1 EQUIPMENT LOCATIONS AND CLEARANCE. A NOTE WILL
 SUFFICE
 3. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 11:13 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-09 Cont ID  
Sent By vperez Date 2016-05-09 Time 15:48 Rev Time 0.00
Received By vperez Date 2016-05-09 Time 15:48 Sent To  
Notes
2016-04-08 14:05:32B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 08:04 Rev Time 0.00
Received By tklarge Date 2016-03-16 Time 12:51 Sent To  
Notes
2016-03-17 12:52:14B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 06:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By ccole Date 2016-05-09 Time 10:59 Rev Time 0.00
Received By ccole Date 2016-05-09 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-14 Cont ID  
Sent By ccole Date 2016-04-14 Time 07:25 Rev Time 0.00
Received By ccole Date 2016-04-14 Time 07:25 Sent To  
Notes
2016-04-14 07:39:042ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030728
 4/14/16
  
 1) SHEET D100 & M100: PLEASE REVISE THE PLAN SHEETS TO
 INCLUDE DETAILS FOR MECHANICAL DEMOLTION AND
 RE-CONSTRUCTION, AND PROVIDE A SCOPE OF WORK FOR THE
 PROJECT . IT APPEARS THAT DUE TO THE RE-CONFIGURATION
 OF THE UNIT LAYOUT, TWO EXISTING HEAT PUMPS ARE BEING
 REPLACED IN THE SAME LOCATIONS, AND TWO ADDITIONAL IN
 NEW LOCATIONS ARE BEING INSTALLED.
 2) PROVIDE AC LOAD CALCULATIONS FOR THE NEW HEAT PUMP
 SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 3) PROVIDE A WATER PIPING LAYOUT PLAN AND PIPING
 INSTALLATION DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By ccole Date 2016-03-21 Time 13:56 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 13:56 Sent To  
Notes
2016-03-21 14:21:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030728
 3/21/16
  
 1) CLARIFY HOW OUTDOOR AIR IS BEING SUPPLIED TO THE
 HEAT PUMPS- REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING AND PROVIDE CALCULATIONS IN ACCORDANCE WITH
 TABLE 403.3 FBC-14 MECHANICAL.
 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS FOR ALL
 OF THE HP CLOSETS.
 3) PROVIDE THE SUPPLY CFM'S FOR THE 6X6 DIFFUSER IN THE
 ELEVATOR HALL.
 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SECTION 603 FBC-14 MECHANICAL.
 5) A NEW CU IS SPECIFIED ON SHEET M301: INDICTE THE
 LOCATION OF THE UNIT AND PROVIDE ENGINEERED
 INSTALLATION DETAILS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-05-02 Cont ID  
Sent By gjohnson Date 2016-05-02 Time 13:34 Rev Time 0.00
Received By gjohnson Date 2016-05-02 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-14 Cont ID  
Sent By gjohnson Date 2016-04-14 Time 16:13 Rev Time 0.00
Received By gjohnson Date 2016-04-14 Time 16:13 Sent To  
Notes
2016-04-14 16:33:37PLUMBING COMMENTS:
  
 1. SHT.P401 WATER RISER.
 (A) MISSING COLD WATER DROP FOR SHOWER 135
 (B) MISSING COLD WATER DROP FOR SHOWER 110
 (C) MISSING COLD WATER DROP FOR LAUNDRY SINK 121
 (D) AT BAR SINK THE HOT LOOP IS TIED TOGETHER AT THE
 MAIN , IT SHOULD BE SEPARATED IF YOUR TRYING TO CREATE
 CIRCULATED WATER TO BAR SINK.
 (E) THE FLOW DIRECTION ARROW ON HOT LOOP BETWEEN
 LAUNDRY SINK AND KITCHEN IS REVERSED.
 PLEASE CORRECT THESE OMISSIONS . PER WPB AMEND.TO FBC
 SEC.107.2.1
  
 2. SHT. P400 SANITARY RISERS.
 (A) SANITARY RISER S/3 SHALL BE SIZED. PER WPB AMEND.TO
 FBC SEC.107.2.1
 (B) SANITARY RISER S/9 THE WASHING MACHINE STAND PIPE
 IS NOT VENTED SHALL COMPLY WITH.
 FBC PL SEC.901.2 AND 901.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 08:04 Rev Time 0.00
Received By tklarge Date 2016-03-27 Time 07:41 Sent To  
Notes
2016-03-27 07:59:15PROVIDE A SANITARY AND WATER RISER DIAGRAM FOR ALL THE
 CHANGES BEING MADE TO THE PLUMBING SYSTEM.FBC
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  