Plan Review Details - Permit 16030649
Plan Review Stops For Permit 16030649
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 11:11 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 10:30 Sent To  
Notes
2016-05-07 10:54:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030649
 ADD: 6620 S. DIXIE HWY.
 CONT: JORGE E. HERNANDEZ
 TEL: 954-678-7580
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. MAY07/ 2016
 ACTION: DENIED
  
  
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. THE ENGINEER OF RECORD DOES INDICATE
 THE 3 PRODUCT APPROVALS THAT HE HAS APPROVED BUT THE 3
 PRODUCT APPROVALS WERE NOT SUBMITTED BY THE CONTRACTOR.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 4) 2ND REQUEST. THE ENGINEER OF RECORD DOES INDICATE
 THE 3 PRODUCT APPROVALS THAT HE HAS APPROVED BUT THE 3
 PRODUCT APPROVALS WERE NOT SUBMITTED BY THE CONTRACTOR.
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5-6) COMPLIED.
  
 7) SEMI-COMPLIED. IN THE 2ND ROUND OF REVIEWS THE DOOR
 SIZES ARE PROVIDED. THE DOOR LEADING TO THE LADIES
 RESTROOM IS LABELED A 2'-8" DOOR. PLEASE PROVIDE
 CONFORMANCE WITH THE 2014 FBC-ACCESSIBLITY CODE,
 SECTION 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 2014 FBC-ACCESS. CODE 202.4.1 202.4.1 DISPROPORTIONATE
 COST. WILL REQUIRE THE CONTRACTOR TO SPEND UP TO AN
 ADDITIONAL $1150.00 DOLLARS IN ACCESSIBLE UPGRADES.
 THIS AMOUNT OF FUNDS SHOULD ALLOW FOR THE LARGER DOOR
 SIZE.
 2014 FBC-ACCESS. CODE 202.4.1 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By jwitmer Date 2016-03-21 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2016-03-21 Time 15:42 Sent To  
Notes
2016-03-22 07:57:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030649
 ADD: 6620 S. DIXIE HWY.
 CONT: JORGE E. HERNANDEZ
 TEL: 954-678-7580
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21/ 2016
 ACTION: DENIED
  
 1) THE RESIDENTIAL DESIGNER ERVIN KEEL CANNOT HAVE
 THEIR NAME ADDRESS, TELEPHONE NUMBER NOR E-MAIL ADDRESS
 ON THESE PLANS SINCE THEY ARE NOT LICENSED FOR
 COMMERCIAL WORK, THIS IS CONSIDERED ADVERTISING.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 2) THE PLANS INDICATE A TOTAL OF 6 NEW WINDOWS 4 ON THE
 SOUTH ELEVATION AND 2 ON THE WEST ELEVATION. THE PLANS
 INDICATE THE USE OF # 5 REBARS VERTICALLY IN THE
 ADJACENT BLOCK CELLS OF THE WINDOW BUT THE PLANS DO NOT
 INDICATE HOW THE REBAR IS GOING TO BE ATTACHED INTO THE
 BEAM OR THE MONOLITHIC SLAB NOR DOES THE PLAN INDICATE
 THE MINIMUM LAP FOR THE REBARS. 2014 FBC-B 2107.2.1.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) THE DESIGNER HAS DESIGNED THE WIND DESIGN EXPOSURE
 TO A HIGHER EXPOSURE D WITH HIGHER PRESSURES ASSOCIATED
 WITH THIS EXPOSURE. WE WILL REVIEW TO THE DESIGNERS
 HIGHER PRESSURES AS EXPRESSED IN THE DESIGN. THE
 UNKNOWN IS IF THE -65/+60 IS VULT OR VASD, NOT GIVEN?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE PLANS INDICATE ON THE SOUTH SIDE OF THE BUILDING
 1 WINDOW IS TO BE BLOCKED IN. THE PLANS DO NOT INDICATE
 THE USE OF ANY HORIZONTAL LADDER TYPE WALL
 RE-INFORCEMENT. FBC-B 2107.1/ ACI 530 12.7.4 JOINT
 RE-INFORCEMENT.
  
 7) THE PLANS DO NOT INDICATE ON THE INTERIOR WHAT WALLS
 ARE EXISTING AND WHAT WALLS ARE NEW NOR DOES THE PLANS
 INDICATE ANY OF THE DOOR SIZES. 107.3.5.1.1 MINIMUM
 CRITERIA FOR COMMERCIAL PLAN REVIEW.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 11:04 Rev Time 0.00
Received By mvaldes Date 2016-06-06 Time 10:33 Sent To  
Notes
2016-06-06 11:05:40JOB PERMIT NUMBER: 16030649
 JOB ADDRESS: 6620 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: JUNE 6 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. (
 ADDRESSING RESPONSES 2ND REQUEST )
  
 - THE SCOPE OF WORK IS AN ALTERATION LEVEL 2 THEREFORE
 EMERGENCY & EXIT LIGHTING SHALL BE PROVIDED IN THE
 ELECTRICAL ROOM. FBC-B1006.2, FBC-B1011. SHOW
 ILLUMINATION BY THE ELECTRICAL SERVICE AND PANEL BOARD
 EQUIPMENT NEC 110.26(D).
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. MAKE A GENERAL
 NOTE SINCE NOT INDICATED ON THE FLOOR PLANS.
 - ON THE RISER DIAGRAMS SHOWS DEMO OF EXISTING PANELS
 AND CONDUITS FROM PANEL ?A? THEREFORE SEALING THESE
 UNUSED OPENINGS WILL BE REQUIRED IN ACCORDANCE WITH NEC
 110.12. PANEL SCHEDULE IS MISSING AIC AND SCR OF
 ELECTRICAL APPARATUS NEC 110.9, 110.10. ARC-FLASH
 HAZARD WARNING LABELS & AVAILABLE FAULT CURRENT
 MARKINGS NEC 110.16, 110.24.
 - AGAIN IF NEW LIGHTING IS BEING INSTALLED MINIMUM
 ENERGY CODE REQUIREMENTS SUCH AS MANDATORY LIGHTING
 CONTROLS WILL APPLY. FBC-E C405.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By mvaldes Date 2016-03-16 Time 10:37 Rev Time 0.00
Received By mvaldes Date 2016-03-16 Time 10:37 Sent To  
Notes
2016-03-16 10:39:30JOB PERMIT NUMBER: 16030649
 JOB ADDRESS: 6620 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MARCH 16 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - MISSING EMERGENCY LIGHTING & EXIT SIGNAGE BY DOUBLE
 DOOR ON THE WEST SIDE OF BUILDING AND INTERIOR OF
 ELECTRICAL ROOM. FBC-B1006.2 , FBC-B1011
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - PROVIDE A NOTE STATING ALL UNUSED OPENINGS ON
 ELECTRICAL PANELBOARD CABINET A WILL BE ADEQUATELY
 SEALED SINCE DEMO OF PANEL EQUIPMENT B & C. NEC 110.12
 A
 - PROVIDE AIC RATING OF ELECTRICAL APPARATUS ALONG WITH
 EXISTING LOAD CALCULATIONS AND SERVICE / FEEDER
 CONDUCTOR / CONDUIT SIZES. NEC 215.5 , ARC-FLASH HAZARD
 WARNING LABEL & AVAILABLE FAULT CURRENT MARKING IS
 REQUIRED. NEC 110.16 , 110.24
 - IF NEW LIGHTING IS BEING INSTALLED MINIMUM ENERGY
 CODE REQUIREMENTS SUCH AS MANDATORY LIGHTING CONTROLS
 WILL APPLY ? PLEASE CLARIFY ? FBC-E C405
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By pleduc Date 2016-05-04 Time   Rev Time 0.00
Received By pleduc Date 2016-05-04 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-16 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-06 Cont ID  
Sent By mvaldes Date 2016-06-06 Time 11:07 Rev Time 0.00
Received By mvaldes Date 2016-04-26 Time 08:53 Sent To  
Notes
2016-04-27 08:53:43B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By jwitmer Date 2016-03-22 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 13:14 Sent To  
Notes
2016-03-15 13:14:27B03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 14:48 Rev Time 0.00
Received By ccole Date 2016-04-28 Time 14:48 Sent To  
Notes
2016-04-28 14:57:522ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030649
 3/22/16
  
 COMMENTS FROM THE 1ST REVIEW STILL EXIST. PLEASE NOTE
 THAT THE SUBMITTED HEAT LOAD CALCULATIONS ARE NOT
 VENTILATION CALCULATIONS- SEE COMMENT #2
  
 1) SHOW THE LOCATIONS OF THE RETURN GRILLS IN THE DOORS
 AND INDICATE THEIR SIZES AND CFM CAPACITIES (PLEASE
 REVIEW THE PERMIT APPLICATION- RETURN GRILLS IN THE
 INTERIOR DOORS IS LISTED IN THE WORK DESCRIPTION).
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES OF THE PROPOSED OCCUPANCY IN
 COMPLIANCE WITH SECTION 809.2 FBC-14 EXISTING BUILDING
 AND TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 3) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE
 PLANS WITH CORREPONDING DRAWINGS AND DETAILS ( THE
 REMOVED DROP CEILING AND NEW ROOM LAYOUTS- AS NOTED IN
 THE PERMIT APPLICATION WORK DESCRIPTION- WILL MOST
 LIKELY AFFECT THE EXISTING HVAC SYSTEM).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 07:03 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 06:56 Sent To  
Notes
2016-03-22 07:16:091ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030649
 3/22/16
  
 1) SHOW THE LOCATIONS OF THE RETURN GRILLS IN THE DOORS
 AND INDICATE THEIR SIZES AND CFM CAPACITIES.
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES OF THE PROPOSED OCCUPANCY IN
 COMPLIANCE WITH SECTION 809.2 FBC-14 EXISTING BUILDING
 AND TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 3) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE
 PLANS WITH CORREPONDING DRAWINGS AND DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  