| Plan Review Stops For Permit 16030643 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-05-23 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-05-23 |
Time |
12:32 |
Sent To |
P |
|
| Notes |
| 2016-05-23 12:47:44 | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- WINDOWS MARK ON SHEET A2.1 WAS REVISED. NOW, IT | | | DOESN'T MATCH MARK SHOWN ON WINDOW SCHEDULE ON SHEET | | | A6.0. REVISE AS REQUIRED TO MATCH. | | | 2- REVISE WINDOW NOA NUMBER AND EXPIRATION DATE SHOWN | | | ON SHEET A6.0 TO MATCH NOA SUBMITTED. | | | 3- ARCHITECT TO SIGN AND SEAL LETTER SUBMITTED LISTING | | | ALL THE PRODUCT APPROVALS THAT WERE REVIEWED/APPROVED. | | | ALSO. REVISE WINDOW NOA NUMBER TO MATCH NOA SUBMITTED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-04-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-04-18 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-04-18 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2016-04-19 11:34:36 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE INFORMATION FOR THE NEW STEPS | | | SHOWING COMPLIANCE WITH SEC. R311.7.5 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). PLANS DON'T SHOW | | | ANY DIMENSIONS. | | | | | | 2- A) PROVIDE COMPLETE INFORMATION FOR THE NEW | | | HANDRAILS SHOWING COMPLIANCE WITH THE LIVE LOAD OF | | | TABLE R301.5 AND THE REQUIREMENTS OF SEC. R311.7.8 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). PLANS DON'T | | | PROVIDE ANY INFORMATION. | | | | | | B) PROVIDE COMPLETE INFORMATION FOR THE NEW PORCH | | | GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOAD OF | | | TABLE R301.5 AND THE REQUIREMENTS OF SEC. R312.1 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). PLANS DON'T | | | PROVIDE ANY INFORMATION. | | | | | | 3- GENERAL NOTES ON SHEET A1.0 REFER TO THE 2010 FBC. | | | THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION | | | (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA | | | STATUTE. | | | | | | 4- THE NUMBERS KEYED ON THE EXTERIOR ELEVATIONS ON | | | SHEET A2.0 ARE NOT LEGIBLE. REVISE AS REQUIRED. SEC. | | | 107.2.1.4 CITY AMENDMENTS. | | | | | | 5- SHEET S-1: PROVIDE COMPLETE SPECIFICATIONS AND | | | DETAILS FOR THE FASTENING OF THE NEW 6 X 4 WOOD BEAM TO | | | BE REPLACED ON THE FLOOR FRAMING PLAN. SEC. R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. | | | | | | B) REAR EXTERIOR DOOR AS SHOWN ON PLANS. | | | | | | 7- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS TO REVISED SET. | | | SUBMIT OLD DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-03-17 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-17 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
destabro |
Date |
2016-05-13 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-05-13 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2016-05-13 13:42:34 | 5/13/16 - REMOVE MENTION OF INSTALLATION OF WHITE VINYL | | | PICKET FENCE FROM PLANS; 4' METAL CHAIN LINK APPROVED | | | WITH VEGETATIVE SCREENING.3/1-LIGHT WINDOWS APPROVED | | | FOR INSTALLATION (NOT CONSISTENT IN PLANS). - DE |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-04-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-04-11 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-04-11 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2016-04-11 12:30:20 | PLANS SHOW VINYL FENCE - NOT PERMITTED INHISTORIC | | | DISTRICT, DISCREPENCY ON PLANS WITH WINDOW MATERIAL - | | | NO VINYL PERMITTED, CHANGE WINDOW PATTERN TO 1/1 OR | | | 3/1, ALSO RAFTR TAILS NOT INDICATED ON ALL ELEVATIONS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-24 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-05 |
Time |
14:18 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-04-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-04-18 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-03-15 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2016-04-14 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-04-14 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-04-14 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2016-04-14 16:11:56 | PROVIDE AHRI AT JOBSITE FOR INSPECTOR TO VERIFY | | | EQUIPMENT. | | | | | | M1503.4 MAKEUP AIR REQUIRED. | | | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF | | | 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED | | | WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE | | | EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE | | | EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE | | | AUTOMATICALLY CONTROLLED TO START AND OPERATE | | | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-24 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-24 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2016-05-23 12:29:51 | IRRIGATION PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-03-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-03-28 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-03-28 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-04-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-04-18 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-04-18 |
Time |
17:59 |
Sent To |
|
|
| Notes |
| 2016-04-18 17:59:53 | SHINGLES NOA 14-1022.16. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-24 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
destabro |
Date |
2016-05-13 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2016-05-13 13:40:50 | 5/13/16 - 50% LANDSCAPE REQUIREMENT MET. ENSURE METAL | | | CHAIN LINK FENCE IS OBSCURED BY VEGETATIVE PLANTINGS. - | | | DE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-04-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-04-11 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-04-11 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2016-04-11 12:31:03 | DEMONSTRTE GREEN SPACE REQUIREMENT IS MET IN FRONT | | | YARD, POSSIBLY REDUCE WALKWAY. |
|
|