| 2016-03-22 09:36:16 | RESIDENTIAL (R2) FLOORING ALTERATION. SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | INFORMATION SUBMITTED WAS THE SAME INFORMATION THAT WAS |
| | SUBMITTED ORIGINALLY. SAME COMMENTS APPLY AGAIN. |
| | |
| | |
| | 1- SOUND INSULATION MATERIAL SUBMITTED: |
| | A) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014). |
| | NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| | CONSTRUCTION. INFORMATION SUBMITTED IS FOR 8" CONCRETE |
| | SLAB WITH SUSPENDED ACOUSTICAL CEILING. THERE IS NOT |
| | SUSPENDED ACOUSTICAL CEILING IN THIS BUILDING. |
| | |
| | B) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014). |
| | NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| | CONSTRUCTION. INFORMATION SUBMITTED IS FOR 8" CONCRETE |
| | SLAB WITH SUSPENDED ACOUSTICAL CEILING. THERE IS NOT |
| | SUSPENDED ACOUSTICAL CEILING IN THIS BUILDING. . |
| | |
| | C) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION |
| | (2014). |
| | NOTE: TEST SAMPLE TO MATCH PROPOSED INSTALLATION. |
| | |
| | |