Plan Review Details - Permit 16030552
Plan Review Stops For Permit 16030552
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-08-24 Cont ID  
Sent By jwitmer Date 2016-08-24 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2016-08-24 Time 09:31 Sent To  
Notes
2016-08-24 16:33:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030552
 ADD: 6901 OKEECHOBEE BLVD.
 CONT: RANDOLPH & DEWDNEY CONSTRUCTION
 TEL: 561-276-2889
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 DATE: WED. AUGUST 24/2016
 ACTION: BUILDING PROVIDO
  
 1) 2014 FBC-B 468.2.3 OUTDOOR WASTE CONTAINERS. A
 SMOOTH NONABSORBENT SURFACE SHALL BE PROVIDED FOR
 OUTDOOR WASTE CONTAINERS.
  
 2) 2014 FBC-B 468.3.4 DIAPER CHANGING STATIONS. A
 DIAPER CHANGING STATION SHALL BE LOCATED IN OR ADJACENT
 TO ANY CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN
 ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED
 WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE
 PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR
 TOUCHING A HANDLE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-08-01 Time 05:59 Sent To  
Notes
2016-08-01 07:00:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030552
 ADD: 6901 OKEECHOBEE BLVD.
 CONT: RANDOLPH & DEWDNEY CONSTRUCTION
 TEL: 561-276-2889
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 DATE: WED. AUGUST 24/2016
 ACTION: DENIED
  
 NEW DESIGNER OF RECORD, NEW DESIGN DOCUMENTS. 2ND
 REVIEW!!!!
  
 1A) 2ND REVIEW. SHEET S.2 UNDER THE HEADING CODES FOR
 PROJECT LIST THIS AS A LEVEL II ALTERATION. PLEASE NOTE
 THIS PLAN REVIEW WILL BE UNDER THE 2014 FBC- EXISTING
 BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY. 1001.3.1
 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A
 PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW
 OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
 PLEASE UPDATE YOUR PLANS ACCORDINGLY.
  
 1B) 2ND REVIEW COMMENT, NOT CHANGED. . SHEET S.2
 INDICATES THE TENANT SPACE HAVING 1152 SQ. FT. THE
 INTERIOR TENANT SPACE WALLS SCALES 29.75 X 73= 973
 GROSS SQ. FT. OF TENANT SPACE. FOR DAYCARE OCCUPANCY
 THE OCCUPANT LOAD IS SUPPOSED TO BE CALCULATED ON THE
 NET SQUARE FEET. FLOOR AREA, NET. THE AREAS USED FOR
 PERMANENT BUILDING COMPONENTS, SUCH AS SHAFTS, FIXED
 EQUIPMENT, THICKNESS OF WALLS, CORRIDORS STAIRWAYS,
 TOILET ROOMS, MECHANICAL ROOMS, AND CLOSETS ARE NOT
 INCLUDED IN NET FLOOR AREA.
 PLEASE PROVIDE AN ACCURATE NET OCCUPANT LOAD. WITH
 RESTROOMS AND WALL THICKNESS REMOVED TO A NET SQ.
 FOOTAGE OF APPROX. 807/35= 23 OCCUPANTS.
  
 1C) COMPLIED. OCCUPANT LOAD FIGURED AT 35 SQ. FEET PER
 OCCUPANT.
  
 1D) 2ND REVIEW COMMENT, NOT CHANGED. SHEET S.1
 INDICATES THE TOTAL NET AREA FOR THE A/C LOADS TO BE
 2,175 SQ. FT. WHEN THE TOTAL INTERIOR SQUARE FEET ARE
 973 SQ, FT./ NET OF 807 SQ. FT. APPROX. WHY THE BIG
 DISCREPANCY??????? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1E)2ND REVIEW COMMENT, NOT CHANGED. PLEASE SPECIFY
 WHICH OF THE CHILDREN FACTORS BELOW THESE PLANS WERE
 DESIGNED TOO, PLANS INDICATE GROUP E NORMAL HAZARD
 PLEASE IDENTIFY AS TO SPECIFIC AGE GROUP. SHEET S.2
 UNDER THE HEADING OF CODE ANALYSIS INDICATES THE
 OCCUPANCY AS AN (E) EDUCATIONAL OCCUPANCY. PLEASE
 INDICATE AS TO WHICH TYPE OF EDUCATIONAL FACILITY THIS
 USE WILL FALL INTO:
  
 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES
 BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED
 BY MORE THAN FIVE CHILDREN OLDER THAN 2 1/2 YEARS OF
 AGE WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL
 CARE SERVICES FOR FEWER THAN 24 HOURS PER DAY.
 OR
 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE
 FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO
 MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE,
 WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE
 LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS
 AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR
 DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP
 E.
 OR
 CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT
 ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT
 RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS
 WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN
 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS
 CHILD CARE FACILITIES AND CONSIDERED TO BE
 GROUP I-4.
  
 2ND REVIEW COMMENT, PLEASE DEFINE IF THIS FACILITY IS
 TO BE CONSIDERED A I-4 FACILITY OR WHAT TYPE OF GROUP E
 DAY CARE FACILITY?
  
 1F) 2ND REVIEW COMMENT/ CHANGED SOMEWHAT. 2014 FBC-B
 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE FACILITIES,
 ROOMS OR SPACES WHERE CARE IS PROVIDED FOR MORE THAN 10
 CHILDREN THAT ARE 2 1/2 YEARS OF AGE OR LESS, SHALL
 HAVE ACCESS TO NOT LESS THAN TWO EXITS OR EXIT ACCESS
 DOORWAYS. THIS SET OF PLANS IS DEFICIENT IN NOT SHOWING
 THE COMPLETE SITE PLAN, THE ORIGINAL DESIGNER SHOWED
 BEHIND THE TENANT SPACE A FENCED IN PLAY GROUND AND THE
 2ND MEANS OF EGRESS TO THE PUBLIC WAY. THE CURRENT PLAN
 DOES NOT SHOW A 2ND MEANS OF EGRESS TO THE PUBLIC WAY.
  
 1G) COMPLIED. FBC-B466.2 CLOSET DOORS.
  
 1H) COMPLIED. FBC-B 466.3 BATHROOM DOORS.
  
 2) 2ND REQUEST, NOT CHANGED. SHEET S.1 SHOWS THE FRONT
 ENTRY GOING INTO AN EXISTING HALLWAY, PLEASE BE AWARE
 THIS IS AN OPEN MALL BUILDING, SEE 2014 FBC-B 402.1.
 PLEASE REVISE PLANS.
  
 3A) 2ND REQUEST. PLEASE SHOW CODE COMPLIANCE WITH 466.7
 DETECTION AND ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL
 BE PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 907 AND THIS SECTION, 466.7.1 & 466.7.1.1. FIRE
 ALARM LOW VOLTAGE BESIDES NEEDING TO BE ON THESE
 DOCUMENTS WILL ALSO REQUIRE A SEPARATE PERMIT.
  
 3B) COMPLIED. 2014 FBC-B 466.7.2 DETECTION.
  
 4) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE
 CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE
 REVIEWED FOR CODE COMPLIANCE.
  
 4A) 2ND REQUEST. 468.2.2 PLAYGROUNDS AND EQUIPMENT.
 PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY
 SOUND, VERMIN PROOF, AND SHALL NOT HAVE JAGGED OR SHARP
 PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO
 SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR
 DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD
 CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT,
 SLIDES, AND SWINGS.
  
 4B)2ND REQUEST. 468.2.3 OUTDOOR WASTE CONTAINERS. A
 SMOOTH NONABSORBENT SURFACE SHALL BE PROVIDED FOR
 OUTDOOR WASTE CONTAINERS.
  
 4C) 2ND REQUEST. NOT SHOWN ON THE PLANS, THE CODE IS
 JUST REPEATED ON THE PLANS. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING
 STATION SHALL BE LOCATED IN OR ADJACENT TO ANY
 CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN
 ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED
 WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE
 PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR
 TOUCHING A HANDLE.
  
 4D) 2ND REQUEST. 468.3.5.2 TEACHER TOILETS. FACULTY AND
 STAFF TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 4E) 2ND REQUEST. 468.3.5.5 WALLS. WALLS IN TOILET ROOMS
 SHALL BE IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET
 (1219 MM) ABOVE THE FLOOR. WALLS IN KITCHENS,
 SCULLERIES, CAN WASH AREAS, AND SHOWER ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 6 FEET (1829 MM)
 ABOVE THE FLOOR. TOILET AND SHOWER PARTITIONS SHALL BE
 IMPERVIOUS.
  
 4F) SEMI-COMPLIED, DOES NOT INDICATE THE AGE OF THE
 KIDS USING THESE FACILITIES. 2014 FBC-ACCESS. CODE
 604.1 GENERAL. WATER CLOSETS AND TOILET COMPARTMENTS
 SHALL COMPLY WITH 604.2 THROUGH 604.8. EXCEPTION: WATER
 CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE
 SHALL BE PERMITTED TO COMPLY WITH 604.9. 604.9 WATER
 CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
 4G-I) DELETED SHOWER.
  
 5) COMPLIED. 2014FBC-B1008.1.10 PANIC AND FIRE EXIT
 HARDWARE
  
 6) 2ND REQUEST. THERE ARE NEW WALLS WITHIN THE TENANT
 SPACE, FIRE SPRINKLERS MAY NEED TO BE MOVED TO ACHIEVE
 PROPER COVERAGE. PLEASE PROVIDE THE NEW FIRE SPRINKLER
 LAYOUT CEILING PLAN. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 SCHEMATIC FIRE SPRINKLERS.
  
 7) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 8 ) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time 14:35 Rev Time 0.00
Received By jwitmer Date 2016-06-28 Time 11:53 Sent To  
Notes
2016-06-28 14:35:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030552
 ADD: 6901 OKEECHOBEE BLVD.
 CONT: RANDOLPH & DEWDNEY CONSTRUCTION
 TEL: 561-276-2889
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 28/2016
 ACTION: DENIED
  
 NOTICE: 6/28/2016 CALLED CONTRACTOR, NO MECHANICAL
 SHEETS SUBMITTED, WILL ACCEPT NEW MECH. SHEETS AT
 MID-REVIEW, OK?ED BY S. KENNEDY.
  
 NEW DESIGNER OF RECORD, NEW DESIGN DOCUMENTS.
  
 1A) SHEET S.2 UNDER THE HEADING CODES FOR PROJECT LIST
 THIS AS A LEVEL II ALTERATION. PLEASE NOTE THIS PLAN
 REVIEW WILL BE UNDER THE 2014 FBC- EXISTING BUILDING
 CODE CHAPTER 10 CHANGE OF OCCUPANCY. 1001.3.1 PARTIAL
 CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A PORTION OF
 AN EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1B) SHEET S.2 INDICATES THE TENANT SPACE HAVING 1152
 SQ. FT. THE INTERIOR TENANT SPACE WALLS SCALES 29.75 X
 73= 973 GROSS SQ. FT. OF TENANT SPACE. FOR DAYCARE
 OCCUPANCY THE OCCUPANT LOAD IS SUPPOSED TO BE
 CALCULATED ON THE NET SQUARE FEET. FLOOR AREA, NET. THE
 AREAS USED FOR PERMANENT BUILDING COMPONENTS, SUCH AS
 SHAFTS, FIXED EQUIPMENT, THICKNESS OF WALLS, CORRIDORS
 STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS, AND CLOSETS
 ARE NOT INCLUDED IN NET FLOOR AREA.
 PLEASE PROVIDE AN ACCURATE NET OCCUPANT LOAD.
  
 1C) SHEET S.2 UNDER THE PROJECT DATA ALSO INDICATES THE
 OCCUPANT LOAD IS TO BE FIGURED AT 30 SQ. FT. AS TABLE
 1004.1.1. PLEASE REFER TO THE 2014 FBC-B TABLE 1004.1.2
 UNDER THE HEADING FUNCTION OF SPACE: DAYCARE
 THE OCCUPANT LOAD IS TO BE FIGURED AT 35 SQ. FT. NET.
 PLEASE UPDATE PLANS WITH THE NET SQUARE FEET AND
 OCCUPANT LOAD FIGURED AT 35 SQ. FEET PER OCCUPANT.
  
 1D) SHEET S.1 INDICATES THE TOTAL NET AREA FOR THE A/C
 LOADS TO BE 2,175 SQ. FT. WHEN THE TOTAL INTERIOR
 SQUARE FEET ARE 973 SQ, FT. WHY THE BIG
 DISCREPANCY??????? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1E) SHEET S.2 UNDER THE HEADING OF CODE ANALYSIS
 INDICATES THE OCCUPANCY AS AN (E) EDUCATIONAL
 OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF
 EDUCATIONAL FACILITY THIS USE WILL FALL INTO:
  
 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES
 BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED
 BY MORE THAN FIVE CHILDREN OLDER THAN 2 1/2 YEARS OF
 AGE WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL
 CARE SERVICES FOR FEWER THAN 24 HOURS PER DAY.
 OR
 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE
 FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO
 MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE,
 WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE
 LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS
 AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR
 DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP
 E.
 OR
 CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT
 ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT
 RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS
 WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN
 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS
 CHILD CARE FACILITIES AND CONSIDERED TO BE
 GROUP I-4.
  
 2ND REVIEW COMMENT, PLEASE DEFINE IF THIS FACILITY IS
 TO BE CONSIDERED A I-4 FACILITY OR WHAT TYPE OF GROUP E
 DAY CARE FACILITY?
  
 1F) 2ND REVIEW COMMENT. 2014 FBC-B 1015.6 DAY CARE
 MEANS OF EGRESS. DAY CARE FACILITIES, ROOMS OR SPACES
 WHERE CARE IS PROVIDED FOR MORE THAN 10 CHILDREN THAT
 ARE 2 1/2 YEARS OF AGE OR LESS, SHALL HAVE ACCESS TO
 NOT LESS THAN TWO EXITS OR EXIT ACCESS DOORWAYS. THIS
 SET OF PLANS IS DEFICIENT IN NOT SHOWING THE FENCED IN
 PLAY GROUND AND THE 2ND MEANS OF EGRESS TO THE PUBLIC
 WAY.
  
 1G) FBC-B466.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH
 SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE CLOSET.
  
 1H) FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR
 LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED
 DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING
 DEVICE SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 2) SHEET S.1 SHOWS THE FRONT ENTRY GOING INTO AN
 EXISTING HALLWAY, PLEASE BE AWARE THIS IS A OPEN MALL
 BUILDING, SEE 2014 FBC-B 402.1. PLEASE REVISE PLANS.
  
 3) PLEASE SHOW CODE COMPLIANCE WITH 466.7 DETECTION AND
 ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907
 AND THIS SECTION, 466.7.1 & 466.7.1.1.
  
 4) 2014 FBC-B 466.7.2 DETECTION. A SMOKE DETECTION
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 WITH PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF
 DOORS TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL
 FLOORS OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS
 ALSO SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS
 AND SLEEPING ROOMS IN THE DAY CARE OCCUPANCY.
  
 4) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE
 CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE
 REVIEWED FOR CODE COMPLIANCE.
 4A) 468.2.2 PLAYGROUNDS AND EQUIPMENT.
 PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY
 SOUND, VERMIN PROOF, AND SHALL NOT HAVE JAGGED OR SHARP
 PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO
 SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR
 DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD
 CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT,
 SLIDES, AND SWINGS.
  
 4B) 468.2.3 OUTDOOR WASTE CONTAINERS. A SMOOTH
 NONABSORBENT SURFACE SHALL BE PROVIDED FOR OUTDOOR
 WASTE CONTAINERS.
  
 4C) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING
 STATION SHALL BE LOCATED IN OR ADJACENT TO ANY
 CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN
 ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED
 WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE
 PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR
 TOUCHING A HANDLE.
  
 4D) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF
 TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 4E) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM)
 ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN
 WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A
 HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR.
 TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS.
  
 4F) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS
 AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH
 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH
 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
 4G) THE SHOWER IN ROOM IN THE NEW BATHROOM WILL NEED TO
 COMPLY WITH: 2014 ACCESS. CODE 213. BATHING ROOMS.
 WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING ROOM
 SHALL COMPLY WITH 603.
 603.2 CLEARANCES. CLEARANCES SHALL COMPLY WITH 603.2.
  
 4G)(1)603.2.1 TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 4G)(2) 603.2.2 OVERLAP. REQUIRED CLEAR FLOOR SPACES,
 CLEARANCE AT FIXTURES, AND TURNING SPACE SHALL BE
 PERMITTED TO OVERLAP. THIS NOTE IS FOR THE SINGLE
 BATHROOM, MISSING CLEARANCE AROUND THE WATER CLOSET.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 4H) 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER
 TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY
 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT
 THE CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH (915 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE
 SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES (915 MM)
 WIDE MINIMUM BY 48 INCHES (1220 MM) LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 4I) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. IN
 TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE PROVIDED
 ACROSS THE CONTROL WALL AND BACK WALL TO A POINT 18
 INCHES (455 MM) FROM THE CONTROL WALL.
  
  
 5) SHEET S.1 NOR S.2 SHOW THE HARDWARE TYPE ON THE
 FRONT AND REAR DOOR. PLEASE NOTE THIS IS A CHANGE IN
 OCCUPANCY FROM MERCANTILE TO EDUCATIONAL. UNDER THE
 2014 EXISTING BUILDING CODE 1012.4 MEANS OF EGRESS.
 EXST. BLDG CODE 1012.4.2 MEANS OF EGRESS FOR CHANGE OF
 USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL OR LESSER
 HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE
 1012.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 905 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 6) THERE ARE NEW WALLS WITHIN THE TENANT SPACE, FIRE
 SPRINKLERS MAY NEED TO BE MOVED TO ACHIEVE PROPER
 COVERAGE. PLEASE PROVIDE THE NEW FIRE SPRINKLER LAYOUT
 CEILING PLAN. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 SCHEMATIC FIRE SPRINKLERS.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By jwitmer Date 2016-03-17 Time 12:58 Rev Time  
Received By jwitmer Date 2016-03-17 Time 08:32 Sent To  
Notes
2016-03-17 12:54:44 
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030552
 ADD: 6901 OKEECHOBEE BLVD.
 CONT: RANDOLPH & DEWDNEY CONSTRUCTION
 TEL: 561-276-2889
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAR. 17/2016
 ACTION: DENIED
  
 1A) SHEET A-0.00 UNDER THE HEADING OF CODE ANALYSIS
 INDICATES THE OCCUPANCY AS AN (E) EDUCATIONAL
 OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF
 EDUCATIONAL FACILITY THIS USE WILL FALL INTO:
  
 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES
 BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED
 BY MORE THAN FIVE CHILDREN OLDER THAN 21/2 YEARS OF AGE
 WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL CARE
 SERVICES FOR FEWER THAN 24 HOURS PER DAY.
  
  
 308.6.1 CLASSIFICATION AS GROUP E.
 A CHILD DAY CARE FACILITY THAT PROVIDES CARE FOR MORE
 THAN FIVE BUT NO MORE THAN 100 CHILDREN 21/2 YEARS OR
 LESS OF AGE, WHERE THE ROOMS IN WHICH THE CHILDREN ARE
 CARED FOR ARE LOCATED ON A LEVEL OF EXIT DISCHARGE
 SERVING SUCH ROOMS AND EACH OF THESE CHILD CARE ROOMS
 HAS AN EXIT DOOR DIRECTLY TO THE EXTERIOR, SHALL BE
 CLASSIFIED AS GROUP E.
  
 CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT
 ABLE TO RECONIZE AN EMERGENCY SITUATION, MAY NOTRESPOND
 APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS WITHOUT
 ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN 5
 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS
 CHILD CARE FACILITES AND CONSIDERED TO BE GROUP I-4.
  
 THE COVERSHEET INDICATES THIS TO BE A EARLY CHILDHOOD
 LEARNING CENTER. PLEASE DEFINE IF THIS FACILITY IS TO
 BE CONSIDERED A I-4 FACILITY OR GROUP E DAY CARE
 FACILITY?
  
 1B) 2014 FBC-B 1015.6 DAY CARE MEANS OF EGRESS. DAY
 CARE FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED
 FOR MORE THAN 10 CHILDREN THAT ARE 21/2 YEARS OF AGE OR
 LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORWAYS.
  
 1C) FBC-B466.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH
 SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE CLOSET.
  
 1D) FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR
 LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED
 DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING
 DEVICE SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
  
 2) PLEASE SHOE CODE COMPLIANCE WITH 466.7 DETECTION AND
 ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907
 AND THIS SECTION, 466.7.1 & 466.7.1.1.
  
 3) 2014 FBC-B 466.7.2 DETECTION. A SMOKE DETECTION
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 WITH PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF
 DOORS TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL
 FLOORS OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS
 ALSO SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS
 AND SLEEPING ROOMS IN THE DAY CARE OCCUPANCY.
  
 4) 2014 FBC-B 466.8 CORRIDORS. EVERY INTERIOR CORRIDOR
 SHALL BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING.
 EXCEPTION:
 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTIONS 901.6 AND 903.3.1.1, CORRIDOR WALLS SHALL
 NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710.
  
 2. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING
 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
  
 5) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE
 CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE
 REVIEWED FOR CODE COMPLIANCE.
  
 6) SHEET A-1.01 THE FRONT DOOR EXISTING (000) AND REAR
 EXTERIOR DOOR (011) ALSO EXISTING ARE SHOWN ON THIS
 PLAN. SHEET A-1.02 THE DOOR SCHEDULE INDICATES THESE
 DOORS WITH DOOR HARDWARE TYPE 5 EXISITNG DOOR, FRAME
 AND HARDWARE.
  
 PLEASE NOTE THIS IS A CHANGE IN OCCUPANCY FROM
 MERCANTILE TO EDUCATIONAL. UNDER THE 2014 EXISTING
 BUILDING CODE 1012.4 MEANS OF EGRESS.
 EXST. BLDG CODE 1012.4.2 MEANS OF EGRESS FOR CHANGE OF
 USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL OR LESSER
 HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE
 1012.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 905 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 2014 EXST. BLDG. CODE. 805.4.4.1 SUPPLEMENTAL
 REQUIREMENTS FOR PANIC HARDWARE. WHERE THE WORK AREA
 EXCEEDS 50 PERCENT OF THE FLOOR AREA, PANIC HARDWARE
 SHALL COMPLY WITH SECTION 805.4.4 THROUGHOUT THE FLOOR.
  
 7) SHEET A-1.01 THE REAR EXIT LEADS INTO A FENCED
 EXTERIOR PLAYGROUND WITH A GATE. THERE IS A NOTE THAT
 THE GATE WILL HAVE A VERTICAL PULL GATE LATCH.
  
 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF
 EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF
 EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR
 DOORS.
  
 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 8) SHEET A-0.00 THE CODE ANALYSIS INDICATES AN OCCUPANT
 LOAD OF 59 OCCUPANTS. SECTION 1015.1(1) OF THE
 FBC-BUILDING CODE REQUIRES 2 MEANS OF EGRESS WHEN A
 OCCUPANT LOAD IS GREATER THAN 49. PLEASE REVIEW THE
 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE MET FROM THE
 REAR EXIT DOOR (EXIT DISCHARGE) TO THE PUBLIC WAY.
  
 9) SHEET A-1.02 DETAIL #5 SHOWS THE 3 COMPARTMENT SINK
 AT A HEIGHT OF 36 INCHES PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-ACCESS. CODE 606.3 HEIGHT OF 34 INCHES TO THE
 RIM OR COUNTER SURFACE.
  
 10) SHEET A-1.01 THE RESTROOMS IF THIS IS A FACILITY
 FOR YOUNG CHILDREN ARE GOING TO BE FACILITIES AGE
 APPROPRIATE FACILIIES THAT WILL SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBLITY CODE 604.9.
  
 11) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-07-28 Cont ID  
Sent By mvaldes Date 2016-07-28 Time 09:27 Rev Time 0.00
Received By mvaldes Date 2016-07-28 Time 08:33 Sent To  
Notes
2016-07-28 09:29:01REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 - NEC 760.41(B) THE BRANCH CIRCUIT SUPPLYING FIRE ALARM
 EQUIPMENT SHALL SUPPLY NO OTHER LOADS AND BE
 PERMANENTLY MARKED IN RED AND IDENTIFIED AS: FIRE ALARM
 CIRCUIT? AND BE ACCESSIBLE ONLY TO QUALIFIED PERSONNEL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-07 Cont ID  
Sent By mvaldes Date 2016-07-07 Time 19:08 Rev Time 0.00
Received By mvaldes Date 2016-07-07 Time 19:08 Sent To  
Notes
2016-07-07 19:09:46JOB PERMIT NUMBER: 16030552
 JOB ADDRESS: 6901 OKEECHOBEE BLVD.
 WEST PALM BEACH FLORIDA
 DATE: JULY 7 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - CHANGE OF OCCUPANCY, CHANGE OF CONTRACTOR AND CHANGE
 OF ENGINEER OF RECORD. NEW PLANS WILL BE REVIEWED AS A
 NEW DESIGN.
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
 - SHOW EXISTING LIGHTING ON FLOOR PLANS TO VERIFY MEANS
 OF EGRESS ILLUMINATION FBC 1006.1
 - ALL CIRCUITS BEING RE LOCATED IF CHANGED MUST BE RE
 IDENTIFIED AT THE PANELBOARD AND THE LEGEND SHALL MADE
 WITH SUFFICIENT DETAIL TO DISTINGUISH CIRCUITS FROM
 OTHERS. NEC 408.4(A) INSPECTOR WILL CHECK IN THE FIELD
 !
 - ADD A NOTE FOR ARC FLASH WARNING LABEL AND AVAILABLE
 FAULT CURRENT MARKINGS NEC 110.16, 110.24
 - SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE AND FIRE
 ALARM.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By mvaldes Date 2016-03-24 Time 17:49 Rev Time 0.00
Received By mvaldes Date 2016-03-24 Time 17:49 Sent To  
Notes
2016-03-24 17:51:24JOB PERMIT NUMBER: 16030552
 JOB ADDRESS: 6901 OKEECHOBEE BLVD.
 WEST PALM BEACH FL 33411
 DATE: MARCH 24 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 422.52 ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT
 CIRCUIT ?INTERRUPTER PROTECTION (GFI).
 - NEC 210.8 GROUND FAULT CIRCUIT-INTERRUPTER
 PROTECTION. 6 FOOT AROUND SINKS (B) OTHER THAN DWELLING
 UNITS.
 - FIRE ALARM IF REQUIRED SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT. FIRE OFFICIAL TO DETERMINE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-08-17 Cont ID  
Sent By Mgonzale Date 2016-08-17 Time   Rev Time 1.00
Received By mgonzale Date 2016-08-17 Time   Sent To I
Notes
2016-08-17 13:47:47SEPARATE ENGINEERING SUBMITTAL HAS BEEN APPLIED FOR,
  
 IF CANOPY STRUCTURE IS PERMANENT THEN IT MUST BE
 ORIENTED OUTSIDE OF PUBLIC UNDERGROUND UTILITY
 EASEMENT.
  
 CALL 811 BEFORE DIGGING.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-08-30 Cont ID  
Sent By scaldero Date 2016-08-30 Time 10:53 Rev Time 0.00
Received By scaldero Date 2016-08-30 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2016-08-02 Cont ID  
Sent By scaldero Date 2016-08-02 Time 08:23 Rev Time 0.00
Received By scaldero Date 2016-08-02 Time 08:21 Sent To  
Notes
2016-08-02 08:23:04PERMIT #16030552
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 3RD REVIEW:
  
 1) SEE BUILDING DEPT. COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 11:44 Rev Time 0.00
Received By scaldero Date 2016-07-11 Time 11:36 Sent To  
Notes
2016-07-11 11:41:34PERMIT #16030552
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW:
  
 1) SEE BUILDING DEPT. COMMENTS AS THEY RELATE TO
 OCCUPANT LOAD, MEANS OF EGRESS, DOOR LOCKS, FIRE ALARM
 SYSTEM, AND SMOKE DETECTION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-30 Cont ID  
Sent By scaldero Date 2016-03-30 Time 11:29 Rev Time 0.00
Received By scaldero Date 2016-03-30 Time 11:11 Sent To  
Notes
2016-03-30 11:24:03PERMIT # 16030552
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) DRAWING NOTE ON SHEET A1.01 INDICATES THAT ALL FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS TO REMAIN. A LIFE
 SAFETY ENGINEER SHOULD COMPLETE A FORMAL EVALUATION TO
 VERIFY THAT NO MODIFICATIONS ARE NEEDED TO THE EXISTING
 FIRE AND LIFE SAFETY SYSTEMS. SHOULD MODIFICATIONS BE
 REQUIRED, SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 5) SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
  
 6) AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 7) FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED
 MONTHLY BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER
 WHICH A COPY OF THE LATEST INSPECTION REPORT SHALL BE
 POSTED IN A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
 IT SHALL BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS
 DAILY TO ENSURE THAT ALL DOORS AND EXIT PATHS ARE
 MAINTAINED CLEAR OF OBSTRUCTIONS.
  
 8) REVIEW AND ADDRESS COMMENTS LISTED UNDER BUILDING
 PLAN REVIEW.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-30 Cont ID  
Sent By skennedy Date 2016-08-30 Time 16:29 Rev Time 0.00
Received By skennedy Date 2016-08-22 Time 12:48 Sent To  
Notes
2016-08-22 12:48:10B25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-18 Cont ID  
Sent By cpuell Date 2016-08-18 Time 09:56 Rev Time 0.00
Received By cpuell Date 2016-07-21 Time 11:30 Sent To  
Notes
2016-07-22 11:30:21B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-12 Cont ID  
Sent By scaldero Date 2016-07-12 Time 04:41 Rev Time 0.00
Received By tklarge Date 2016-06-23 Time 14:04 Sent To  
Notes
2016-06-23 14:04:02B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-29 Cont ID  
Sent By cpuell Date 2016-04-29 Time 08:06 Rev Time 0.00
Received By cpuell Date 2016-03-14 Time 10:36 Sent To  
Notes
2016-03-15 10:36:40B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-08-31 Cont ID  
Sent By skennedy Date 2016-08-31 Time 12:32 Rev Time 0.00
Received By skennedy Date 2016-08-31 Time 12:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-08-01 Time 06:00 Sent To  
Notes
2016-08-01 07:00:512ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-06-28 Cont ID  
Sent By jwitmer Date 2016-06-28 Time 14:34 Rev Time 0.00
Received By jwitmer Date 2016-06-28 Time 14:34 Sent To  
Notes
2016-06-28 14:34:41BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By jwitmer Date 2016-03-17 Time 12:59 Rev Time  
Received By jwitmer Date 2016-03-17 Time 08:32 Sent To  
Notes
2016-03-17 12:59:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-30 Cont ID  
Sent By jvalido Date 2016-08-30 Time 16:19 Rev Time 0.00
Received By jvalido Date 2016-08-30 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-11 Cont ID  
Sent By jvalido Date 2016-08-11 Time 17:18 Rev Time 0.00
Received By jvalido Date 2016-08-11 Time 16:49 Sent To  
Notes
2016-08-11 17:02:50CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE (2) SETS OF MECHANICAL PLANS
 (2) PLANS MUST SHOW CONDITIONED AIR TO ALL AREAS. MANY
 SUPPLY DROPS ARE SHOWN IN WALLS. NEW OFFICE HAS NO
 SUPPLY DROP. RECEPTION AREA HAS NO SUPPLY DROP.
 (3) PROVIDE EXISTING DUCT SIZES AND GRILL SIZES.
 (4) SHOW EXHAUST SYSTEM FOR BATHROOMS.
 (5) PROVIDE EQUIPMENT SCHEDULE WITH EXISTING RTU.
 (6) PROVIDE PROPER AIR RETURN TO RTU.
  
 FLORIDA ENERGY CODE FBC 2014
  
 C101.4.4 CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 (7) PROVIDE ENERGY CALCULATIONS
 (8) PROVIDE HEAT LOAD CALCULATIONS
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-03-28 Cont ID  
Sent By jvalido Date 2016-03-28 Time 10:36 Rev Time 0.00
Received By jvalido Date 2016-03-28 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-08-30 Cont ID  
Sent By gjohnson Date 2016-08-30 Time 09:50 Rev Time 0.00
Received By gjohnson Date 2016-08-30 Time 09:50 Sent To  
Notes
2016-08-30 10:19:41 
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PROVISO
 2014 FLORIDA ACCESSIBILITY CODE
 UNISEX BATHROOM
  
  
  
 1. THE OVERALL WIDTH OF ACCESSIBLE TOILET ROOMS SHOULD
 BE MIN OF 85IN MIN TO ACCOMMODATE THE 60 IN CLEARANCE
 OF THE TOILET AND THE SPACE NEEDED FOR THE LAV. WPB
 AMEND. TO FBC 107.2.1
  
 2. PLEASE SHOW CLEARANCE AROUND TOILETS TO COMPLY WITH.
 FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3. PLEASE SHOW CLEAR FLOOR SPACE FOR LAVS. TO COMPLY
 WITH. FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED 305.3 SIZE.
 THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30 INCHES (760
 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM.
  
 4. ALL GRAB BARS SHALL BE MEASURED FROM THE FLOOR TO
 THE TOP OF THE GRIPING SURFACE. PER FBC ACC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 5. TOILET PAPER DISPENSER SHALL COMPLY WITHFBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 6. THE BOTTOM OF THE MIRROR IS SHOWN AS 42IN OF
 FINISHED FLOOR IT SHALL BE 40IN MAX OF THE FLOOR. PER
 FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTER SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7. PLEASE SHOW GRAB BAR COMPLIANCE WITH FBC ACC 604.5.1
 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 8. THE CHILDREN'S TOILET COMPARTMENTS SHALL COMPLY WITH
 FBC ACC 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
  
 ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE.
 THE REQUIREMENTS IN 604.9 ARE TO BE FOLLOWED WHERE THE
 EXCEPTION FOR CHILDREN?S WATER CLOSETS IN 604.1 IS
 USED. THE FOLLOWING TABLE PROVIDES ADDITIONAL GUIDANCE
 IN APPLYING THE SPECIFICATIONS FOR WATER CLOSETS FOR
 CHILDREN ACCORDING TO THE AGE GROUP SERVED AND REFLECTS
 THE DIFFERENCES IN THE SIZE, STATURE, AND REACH RANGES
 OF CHILDREN AGES 3 THROUGH 12. THE SPECIFICATIONS
 CHOSEN SHOULD CORRESPOND TO THE AGE OF THE PRIMARY USER
 GROUP. THE SPECIFICATIONS OF ONE AGE GROUP SHOULD BE
 APPLIED CONSISTENTLY IN THE INSTALLATION OF A WATER
 CLOSET AND RELATED ELEMENTS.
  
  
  
 604.9.1 LOCATION.
 THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM
 AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR
 RIGHT-HAND APPROACH TO THE WATER CLOSET.
  
  
 ADVISORY SPECIFICATIONS FOR WATER CLOSETS SERVING
 CHILDREN AGES 3 THROUGH 12
  
 WATER CLOSET CENTERLINE 12 INCHES
 (305 MM) 12 TO 15 INCHES
 (
 TOILET SEAT HEIGHT 11 TO 12 INCHES
  
 GRAB BAR HEIGHT 18 TO 20 INCHES
  
 DISPENSER HEIGHT 14 INCHES
 (355 MM)
  
 9. SHT. S.2 DETAILS FOR DISABLE BATHS THE HEIGHT OF THE
 TOILET IS SHOWN AS 20IN ON ONE AND 18IN ON THE OTHER
 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 11. S.2 THE TOILET LOCATION DOES NOT MATCH THE REST OF
 THE PLAN PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 12. THE NOTE ON SHT. P.2 FOR THE GREASE INTERCEPTOR IS
 INCORRECT A GREASE INTERCEPTOR IS REQUIRED IF YOU ARE
 SERVING FOOD WITH A GREASE. YOU WILL STILL BE WASHING
 UTENSILS AND SERVING TRAYS. PER FBC PL 1003.3.1 GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES
 REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRETENSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRETENSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR
  
  
 NEW COMMENTS:
  
 1. THE WATER CLOSET IN THE UNISEX BATHROOM AND THE BOYS
 BATHROOM ARE NOTED VENTED PROPERLY. PER FBC PL 910.1
 /912.1/915.1
  
 2. THE HOT WATER SYSTEM SHALL COMPLY WITH FBC PL 607.2
 HOT OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
 THE WAY YOU HAVE THE SYSTEM DESIGNED IT EXCEEDS THE 50
 FT IT CAN BE REDESIGNED SO THAT IT DOES NOT EXCEED
 50FT.
  
  
 PROVISO
 1. PROVIDE APPROVED CODE COMPLIANT ISOMETRIC DRAWING
 FOR FIRST ROUGH INSPECTION. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 2. PROVIDE AN APPROVED SIGNED AND SEALED LETTER FROM
 DESIGNER OF RECORD FOR EXEMPTION OF GREASE INTERCEPTOR.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-07-28 Cont ID  
Sent By gjohnson Date 2016-07-28 Time 15:09 Rev Time 0.00
Received By gjohnson Date 2016-07-28 Time 15:09 Sent To  
Notes
2016-07-28 15:20:513RD REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. THE OVERALL WIDTH OF ACCESSIBLE TOILET ROOMS SHOULD
 BE MIN OF 85IN MIN TO ACCOMMODATE THE 60 IN CLEARANCE
 OF THE TOILET AND THE SPACE NEEDED FOR THE LAV. WPB
 AMEND. TO FBC 107.2.1
  
 2. PLEASE SHOW CLEARANCE AROUND TOILETS TO COMPLY WITH.
 FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3. PLEASE SHOW CLEAR FLOOR SPACE FOR LAVS. TO COMPLY
 WITH. FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED 305.3 SIZE.
 THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30 INCHES (760
 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM.
  
 4. ALL GRAB BARS SHALL BE MEASURED FROM THE FLOOR TO
 THE TOP OF THE GRIPING SURFACE. PER FBC ACC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 5. TOILET PAPER DISPENSER SHALL COMPLY WITHFBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 6. THE BOTTOM OF THE MIRROR IS SHOWN AS 42IN OF
 FINISHED FLOOR IT SHALL BE 40IN MAX OF THE FLOOR. PER
 FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTER SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7. PLEASE SHOW GRAB BAR COMPLIANCE WITH FBC ACC 604.5.1
 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 8. THE CHILDREN'S TOILET COMPARTMENTS SHALL COMPLY WITH
 FBC ACC 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
  
 ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE.
 THE REQUIREMENTS IN 604.9 ARE TO BE FOLLOWED WHERE THE
 EXCEPTION FOR CHILDREN?S WATER CLOSETS IN 604.1 IS
 USED. THE FOLLOWING TABLE PROVIDES ADDITIONAL GUIDANCE
 IN APPLYING THE SPECIFICATIONS FOR WATER CLOSETS FOR
 CHILDREN ACCORDING TO THE AGE GROUP SERVED AND REFLECTS
 THE DIFFERENCES IN THE SIZE, STATURE, AND REACH RANGES
 OF CHILDREN AGES 3 THROUGH 12. THE SPECIFICATIONS
 CHOSEN SHOULD CORRESPOND TO THE AGE OF THE PRIMARY USER
 GROUP. THE SPECIFICATIONS OF ONE AGE GROUP SHOULD BE
 APPLIED CONSISTENTLY IN THE INSTALLATION OF A WATER
 CLOSET AND RELATED ELEMENTS.
  
  
  
 604.9.1 LOCATION.
 THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM
 AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR
 RIGHT-HAND APPROACH TO THE WATER CLOSET.
  
  
 ADVISORY SPECIFICATIONS FOR WATER CLOSETS SERVING
 CHILDREN AGES 3 THROUGH 12
  
 WATER CLOSET CENTERLINE 12 INCHES
 (305 MM) 12 TO 15 INCHES
 (
 TOILET SEAT HEIGHT 11 TO 12 INCHES
  
 GRAB BAR HEIGHT 18 TO 20 INCHES
  
 DISPENSER HEIGHT 14 INCHES
 (355 MM)
  
 9. SHT. S.2 DETAILS FOR DISABLE BATHS THE HEIGHT OF THE
 TOILET IS SHOWN AS 20IN ON ONE AND 18IN ON THE OTHER
 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 10. THE REQUIREMENTS OF THE FBC FOR GROUP E DAY CARE IS
 305.2 GROUP E, DAY CARE FACILITIES.
 THIS GROUP INCLUDES BUILDINGS AND STRUCTURES OR
 PORTIONS THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN
 OLDER THAN 21/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL,
 SUPERVISION OR PERSONAL CARE SERVICES FOR FEWER THAN 24
 HOURS PER DAY.
 THE PLANS SHOW KIDS OF 2 YEARS OLD WHICH WOULD MAKE IT
 I4 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 11. SHT. S.2 THE TOILET LOCATION DOES NOT MATCH THE
 REST OF THE PLAN PLEASE CLARIFY. PER WPB AMEND. TO FBC
 107.2.1
  
 12. THE NOTE ON SHT. P.2 FOR THE GREASE INTERCEPTOR IS
 INCORRECT A GREASE INTERCEPTOR IS REQUIRED IF YOU ARE
 SERVING FOOD WITH A GREASE. YOU WILL STILL BE WASHING
 UTENSILS AND SERVING TRAYS. PER FBC PL 1003.3.1 GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES
 REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRETENSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRETENSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR
  
 13. SHT. S.1 SHOWS A PORTABLE SINK IN ONE OF THE
 CLASSROOM PROVIDE MANUFACTURE SPECS IT SHALL COMPLY
 WITH FBC PL 418.3 MOVABLE SINK SYSTEMS.
 MOVABLE SINK SYSTEMS SHALL COMPLY WITH ASME A112.19.12.
  
 14. SHT. P.3 #3 UNDER GENERAL PLUMBING NOTES ALL FLOOR
 DRAINS SHALL HAVE TRAP PRIMERS. SHOW ON RISER DIAGRAM.
 FBC PL 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 15.SHT. P.3 SANITARY RISER THE NEW BATHROOM GROUP AND
 KITCHEN AND ANY OTHE PLUMBING SHALL TIE IN DOWN STREAM
 OF EXISTING BATHROOM GROUP. PER FBC PL 912.1
  
 16. SHT. P.3 RISER DIAGRAM THE UNISEX BATHROOM SHALL BE
 VENTED TOGETHER THEN CONNECT TO BUILDING DRAIN. PER FBC
 PL 912.1
  
 17. SHT.P.3 THE FLOOR SINK SHALL HAVE A TRAP AND IT
 SHALL BE LOCATED OUTSIDE THE WALL . FBC PL 1002.1
  
 18. THE DRAIN LINE FROM 3 COMP SINK SHOULD NOT BE
 VENTED THE FLOOR SINK DOES NOT NEED A TRAP IT IS TIED
 INTO A COMBINATION WASTE VENT LINE. FBC PL 915
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-07 Cont ID  
Sent By gjohnson Date 2016-07-07 Time 11:10 Rev Time 0.00
Received By gjohnson Date 2016-06-28 Time 17:54 Sent To  
Notes
2016-06-30 15:29:431ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. THE 3 COMPARTMENT SINK SHALL CONNECT INDIRECTLY TO
 SANITARY. PER FBC PL SEC. 802.1.1 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 2. THE 3 COMPARTMENT SINK IS REQUIRED TO DRAIN THROUGH
 A GREASE INTERCEPTOR. PER FBC PL SEC. 1003.3.1 GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES
 REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS.
  
 3. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 3. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PL TABLE
 403.1
  
 4. ON SANITARY RISER DIAGRAM P3, FD-1 ARE NOT VENTED.
 PER FBC PL SEC.912.2.1
  
 5. ON WATER RISER DIAGRAM HOT OR TEMPERED-WATER IS
 REQUIRED FOR P-8,
  
 6. THE WATER HEATER DETAIL SHOWS RELIEF LINE WHERE WILL
 THIS DRAIN DISCHARGE. PER WPB AMEND TO FBC 107.2.1
  
 7. PLUMBING FIXTURE SCHEDULE SHOWS 1IN. CW FOR WATER
 CLOSETS THE WATER RISER DIAGRAM SHOWS 1/2IN. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SEPARATE FACILITY'S ARE REQUIRED FOR STAFF. PER FBC
 PL SEC. 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 ACCESSIBILITY :
  
 1. ADULT TOILET AND BATHING ROOMS SHALL COMPLY WITH FBC
 ACC. SEC. 603-604
  
 603.2.1 TURNING SPACE.
 TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED
 WITHIN THE ROOM.
  
 603.2.2 OVERLAP.
 REQUIRED CLEAR FLOOR SPACES, CLEARANCE AT FIXTURES, AND
 TURNING SPACE SHALL BE PERMITTED TO OVERLAP.
  
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.5 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 609. GRAB
 BARS SHALL BE PROVIDED ON THE SIDE WALL CLOSEST TO THE
 WATER CLOSET AND ON THE REAR WALL.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 2. CHILDREN'S TOILET ROOMS SHALL COMPLY WITH 604.9
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
 3. SHOWER COMPARTMENT SHALL COMPLY WITH 608
  
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
  
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 608.4 SEATS.
 A FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN
 TRANSFER TYPE SHOWER COMPARTMENTS. A FOLDING SEAT SHALL
 BE PROVIDED IN ROLL-IN TYPE SHOWERS REQUIRED IN
 TRANSIENT LODGING GUEST ROOMS WITH MOBILITY FEATURES
 COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH 610.
  
  
 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 15:12 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 13:09 Sent To  
Notes
2016-03-24 15:12:151) THE HEIGHT OF THE THREE COMPARTMENT SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FOOR. FAC SEC. 212.1.
 2) SHOW THE DRINKING FOUNTAINS ON THE SANITARY AND
 WATER RISER DIAGRAMS.FBC 107.3.5.1.3.
 3) THE DRINKING FOUNTAINS SHALL COMPLY WITH FAC SEC.
 307.2 FOR PROTRUDING OBJECTS. SUBMIT AN ELEVATION
 DETAIL SHOWING THE LEADING EDGE OF BOTH UNITS ABOVE THE
 FINISH FLOOR.
 4) INDICATE THE PREVIOUS OCCUPANCY OF THIS SPACE.FBC
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2016-08-03 Time   Rev Time 0.00
Received By llouie Date 2016-08-02 Time 14:30 Sent To  
Notes
2016-08-03 12:49:10APPROVAL SUBJECT TO THE FOLLOWING CONDITIONS OUTLINED
 IN APPROVAL LETTER FOR PB CASE NO. 1112P, ISSUED ON
 7/28/16:
  
 1.) A SEPARATE REVIEW AND PERMIT APPLICATION FOR
 LANDSCAPING IS REQUIRED. THE LANDSCAPE PERMIT PLANS
 MUST COMPLY WITH THE CONDITION PER THE APPROVAL LETTER.
  
 2.) AN ENGINEERING PERMIT WILL BE REQUIRED FROM THE
 ENGINEERING SERVICES DEPARTMENT.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-08 Cont ID  
Sent By llouie Date 2016-07-08 Time 12:01 Rev Time 0.00
Received By llouie Date 2016-07-08 Time 12:01 Sent To  
Notes
2016-07-08 12:02:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A MINOR PLANNED DEVELOPMENT (PD) APPLICATION
 MODIFYING THE SITE PLAN FOR THE PROJECT (PB CASE NO.
 1112P) IS PENDING WITH THE PLANNING DIVISION. PLEASE
 NOTE THAT ZONING WILL NOT APPROVE THE PERMIT REVIEW
 UNTIL THE SITE PLAN AMENDMENT IS APPROVED THROUGH THE
 PD AMENDMENT PROCESS.
  
 2.) PROVIDE A SITE PLAN SHOWING THE PROPOSED EXTERIOR
 MODIFICATIONS IN RELATIONSHIP TO THE SURROUNDING AREA.
 [REPEAT COMMENT FROM 3/25/16]
  
 NOTE:
  
 * SEPARATE LANDSCAPE PERMIT AND REVIEW REQUIRED FOR NEW
 LANDSCAPING.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-25 Cont ID  
Sent By llouie Date 2016-03-25 Time 11:02 Rev Time 0.00
Received By llouie Date 2016-03-25 Time 11:02 Sent To  
Notes
2016-03-25 11:04:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 1.) PROVIDE A SITE PLAN SHOWING THE PROPOSED EXTERIOR
 MODIFICATIONS IN RELATIONSHIP TO THE SURROUNDING AREA.
  
 NOTES:
  
 * SEPARATE LANDSCAPE PERMIT AND REVIEW REQUIRED FOR NEW
 LANDSCAPING.
  
 * A MINOR PLANNED DEVELOPMENT (PD) APPLICATION
 MODIFYING THE SITE PLAN FOR THE PROJECT (PB CASE NO.
 1112P) IS CURRENTLY UNDER REVIEW AND IS SCHEDULED TO GO
 BEFORE THE PLANS AND PLATS REVIEW COMMITTEE (PPRC) ON
 4/13/16. PLEASE NOTE THAT ZONING WILL NOT APPROVE THE
 PERMIT UNTIL THE SITE PLAN IS APPROVED THROUGH THE PD
 AMENDMENT PROCESS.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.