Plan Review Details - Permit 16030500
| Plan Review Stops For Permit 16030500 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-03-23 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-03-23 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2016-03-23 11:13:47 | PROVISO | | | | | | - SPOKE TO PROJECT MANAGER AND HE STATED HE WILL | | | INSTALL A DISCONNECT AHEAD OF THE MLO PANELBOARD TO | | | PROTECT SECONDARY CONDUCTORS FOR 150 KVA STEP DOWN | | | TRANSFORMER FOR THE TEMPORARY OF THE BRISTOL. NEC | | | 450.3B , NEC 240.21C, NEC 408.36 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-03-14 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-03-14 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2016-03-14 10:40:32 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, FEEDER SCHEDULES AND EQUIPMENT SPEC. | | | | | | - SINCE DIRECTIONAL BOARING WILL BE TAKING PLACE IN THE | | | RIGHT A WAY AN ENGINNERING PERMIT IS REQUIRED | | | | | | - PROVIDE A SITE PLAN TO INCLUDE ROUTING OF SERVICE | | | CONDUCTORS , TRANSFORMER LOCATIONS , AND ELECTRICAL | | | APPARATUS LOCATIONS IN RELATION TO EACH OTHER. | | | | | | - PROVIDE ADEQUATE PROTECTION TO ALL ELECTRICAL | | | EQUIPMENT MOUNTED ON RACKS WITH POINTY SHARP EDGEES | | | EXTENDING OUT WERE SUBJECT TO ACCIDENTAL CONTACT. | | | | | | - PLEASE COMPLY WITH THE FOLLOWING CODE SECTIONS NEC | | | 110.9 & 110.10 AIC RATING OF EQUIPMENT & PROTECTIVE | | | DEVICES, NEC 110.15 HIGH LEG MARKING, NEC 110.16 | | | ARC-FLASH HAZARD WARNING, NEC 110.24 | | | AVAILABLE FAULT CURRENT FIELD MARKINGS, NEC 110.27 | | | GUARDING OF LIVE PARTS, NEC 300.6 PROTECTION AGAINST | | | CORROSION , AND PROPERLY LABEL ALL DISCCONECTS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-03-23 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-03-23 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2016-03-23 13:57:05 | MG CONFIRMS A SEPARATE ROW PERMIT IS APPLIED FOR. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-03-14 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-03-14 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2016-03-14 11:28:16 | 3/14/16 | | | | | | PROVIDE EVIDENCE OF APPROVAL FOR USE OF OR CONSTRUCTION | | | WITH THE PUBLIC RIGHT-OF-WAY FROM THE CITY ENGINEERING | | | DEPARTMENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-03-23 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-03-21 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2016-03-21 12:00:18 | RESUB ROUTED TO MVALDES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-03-14 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-03-11 |
Time |
11:38 |
Sent To |
E |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |