Plan Review Details - Permit 16030424
Plan Review Stops For Permit 16030424
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-25 Cont ID  
Sent By   Date 2016-03-25 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-03-25 Time 05:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-17 Cont ID  
Sent By rlecky Date 2016-03-17 Time 13:17 Rev Time 0.00
Received By rlecky Date 2016-03-17 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-24 Cont ID  
Sent By wjolin Date 2016-03-24 Time 10:09 Rev Time 0.00
Received By wjolin Date 2016-03-24 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 09:59 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 15:07 Sent To  
Notes
2016-04-05 15:07:16RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 05:07 Rev Time 0.00
Received By tklarge Date 2016-03-10 Time 10:31 Sent To  
Notes
2016-03-10 10:08:39C31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-25 Cont ID  
Sent By jwitmer Date 2016-03-25 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-03-25 Time 05:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 09:59 Rev Time 0.00
Received By ccole Date 2016-04-11 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By ccole Date 2016-03-21 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 10:57 Sent To  
Notes
2016-03-21 11:25:081ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030424
 3/21/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AHU'S #4 & 7- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE
 REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE
 LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR
 ACTIVATES.
 3) M1: THE 10" FLEX DUCTS SUPPLYING 350 AND 340 CFMS
 FOR AHU-3 & 5 NEED TO INCREASE TO 12".
 4) M1: THE EXHAUST FROM EF-3 SHALL DISCHARGE TO THE
 OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14
 MECHANICAL.
 5) M1: NOTE #4: INDICATES THE NEW CU'S TO BE MOUNTED ON
 EXISTING ROOF STANDS- PLEASE PROVIDE ENGINEERED DETAILS
 FOR TIE DOWN OF THE UNITS- SECTION 301.15 FBC-14
 MECHANICAL.
 6) M2: PLEASE PROVIDE THE REQUIRED AND PROVIDED CFM'S
 IN THE O/A CALCULATION TABLE.
 7) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR
 SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND
 MOTORIZED DAMPERS WILL BE PROVIDED.
 8) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION
 DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-09 Cont ID  
Sent By tklarge Date 2016-04-09 Time 04:06 Rev Time 0.00
Received By tklarge Date 2016-04-09 Time 03:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-26 Cont ID  
Sent By tklarge Date 2016-03-26 Time 05:07 Rev Time 0.00
Received By tklarge Date 2016-03-26 Time 04:42 Sent To  
Notes
2016-03-26 05:07:001) PROVIDE SANITARY & WATER RISER DIAGRAMS FOR ALL
 CHANGES TO THE PLUMBING SYSTEM.NOTE #5 ON SHT. M1 NOTES
 THAT THE NEW SINK IS CONNECTING TO EXISTING SANITARY &
 WATER LINES BUT AN EXISTING SINK IS NOT SHOWN ON
 SHT.2.1. CLARIFY.FBC 107.3.5.1.3.
 2) THE WATER SUPPLY TO THE COFFEE MACHINES SHALL BE
 PROTECTED AGAINST BACKFLOW PER 2014 FBC-PLUMBING
 SEC.608.16.10.
 3) SUBMIT PIPING DETAILS FOR THE WATER HEATER AND PAN
 DRAIN.WHAT TYPE OF FIXTURE IS THE PAN DRAIN DRAINING
 TO? FBC 107.3.5.1.3.
 4) HOT WATER SHALL BE SUPPLIED TO THE BREAKROOM SINK
 PER 2014 FBC-PLUMBING SEC.607.1.
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-15 Cont ID  
Sent By ajones Date 2016-03-15 Time 11:39 Rev Time 0.00
Received By ajones Date 2016-03-15 Time 11:39 Sent To  
Notes
***NONE***