Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By tklarge Date 2016-03-14 Time 11:48 Rev Time 0.00
Received By tklarge Date 2016-03-14 Time 11:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By tklarge Date 2016-03-10 Time 07:24 Rev Time 0.00
Received By tklarge Date 2016-03-10 Time 06:27 Sent To  
Notes
2016-03-10 07:09:351) THE PLAN SHOWS A 3/4" GALVANIZED LINE SUPPLYING THE
 TANKLESS WATER HEATER. THE MAXIMUM BTU LOAD ON A 3/4"
 LINE PER TABLE 402.4 (2) OF 2014 FGC AT 90 FT. ON A .5
 PSI SYSTEM IS 110 BTU'S.
 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL THE
 GAS APPLIANCES.PE PIPE CAN ONLY BE USED OUTSIDW
 UNDERGROUND. FGC SEC.404.17.1, FBC SEC. 107.2.1.
 3) SUBMIT MANUF. SPEC SHEETS FOR THE NEW GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER
 2014 FGC SEC. 301.3.
 4) THE GAS DRAWING SHOWS THE PE PIPE LOCATED IN A
 SLEEVE.PE PIPE CAN ONLY BE USED OUTSIDW UNDERGROUND.
 FGC SEC.404.17.1. CLARIFY.SUBMIT THE SIZE OF THE SLEEVE
 AND SHOW COMPLIANCE WITH 2014 FGC SEC.404.8.1 IF THIS
 INSTALLATION IS PERMITTED BY CODE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2016-03-14 Cont ID  
Sent By tklarge Date 2016-03-14 Time 11:48 Rev Time 0.00
Received By tklarge Date 2016-03-14 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By tklarge Date 2016-03-10 Time 07:24 Rev Time 0.00
Received By tklarge Date 2016-03-09 Time 14:06 Sent To  
Notes
2016-03-09 14:06:23PLUMB -$5000


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved