Plan Review Details - Permit 16030364
Plan Review Stops For Permit 16030364
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-09 Cont ID  
Sent By shill Date 2016-04-09 Time 09:01 Rev Time 0.00
Received By shill Date 2016-04-09 Time 09:01 Sent To  
Notes
2016-04-09 09:02:35PROVISO - PRIOR TO INSTALLATION OF PEDESTRIAN WALKWAY
 PROTECTION ON ADJACENT (HOTEL) PROPERTY, A LETTER
 GRANTING PERMISSION IS REQUIRED TO BE PROVIDED BY THE
 ADJACENT PROPERTY OWNER (HOTEL),
  
 OR
  
 CONTRACTOR TO SUBMIT A LETTER STATING THAT THEY HAVE
 BEEN VERBALLY GRANTED PERMISSION TO INSTALL THE
 PEDESTRIAN PROTECTION ON THE ADJACENT HOTEL PARCEL, AND
 THE LETTER FROM THE ADJACENT PROPERTY OWNER MAY BE SENT
 DIRECTLY FROM THE HOTEL
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-05 Cont ID  
Sent By shill Date 2016-04-05 Time 14:09 Rev Time 0.00
Received By shill Date 2016-04-05 Time 12:36 Sent To  
Notes
2016-04-05 14:11:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF PROPOSED
 SCAFFOLDING.
  
 2. THE DOCUMENTS FROM THE FIRST SUBMITTAL WERE REMOVED.
 IN THE FUTURE, PLEASE LEAVE ALL DOCUMENTS AS, IF
 SOMETHING IS LACKING, I CAN SOMETIMES COMPLETE THE
 SUBMITTAL USING OLD DOCUMENTS. ALSO, WE NEED THESE FOR
 REFERENCE. ALL DOCUMENTS ARE TO BE RETAINED IN THE
 SUBMITTAL AND ARE NOT TO BE DISCARDED UNTIL ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By shill Date 2016-03-09 Time 10:29 Rev Time 0.00
Received By shill Date 2016-03-09 Time 10:29 Sent To FIRE
Notes
2016-03-09 10:54:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PEDESTRIAN PROTECTION WILL ENCROACH THE PROPERTY LINE.
 PROVIDE A LETTER GRANTING PERMISSION FROM THE ADJACENT
 PROPERTY OWNER.
  
 2. THE PLANS PROVIDED LACK A TITLE BLOCK FOR THE
 ENGINEER, FS 471, FAC61G15-23.002. THE PLANS ALSO DO
 NOT CORRECTLY IDENTIFY THE PROJECT (FORT LAUDERDALE IS
 SHOWN AS THE LOCATION).
  
 3. THE PLAN SUBMITTED REQUIRES THAT THE STRUCTURAL
 ENGINEER CONFIRM THAT THE STRUCTURE THAT THE SCAFFOD
 SYSTEM IS RESTING ON IS CAPABLE OF SUPPORTING THE
 SUPERIMPOSED LEG LOAD OF 6300 LBS. A SHOP DRAWING
 REVIEW STAMP OR REVIEW LETTER IS REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-06 Cont ID  
Sent By vperez Date 2016-04-06 Time 09:03 Rev Time 0.00
Received By vperez Date 2016-04-06 Time 09:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By pleduc Date 2016-03-29 Time 15:23 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By shill Date 2016-03-09 Time   Rev Time 0.00
Received By pleduc Date 2016-03-11 Time 13:34 Sent To PC
Notes
2016-03-11 13:41:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THE SUBMITTED PLAN INDICATE THE COVERING
 OVER/THROUGH AN EXIT PATH OF TRAVEL. THERE IS NO
 INDICATION OF EXIT PATH ILLUMINATION PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
  
 7.8.1 GENERAL.
  
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS BE AVAILABLE FOR USE, UNLESS OTHERWISE
 PROVIDED IN 7.8.1.2.2.
  
 PLEASE PROVIDE THE CONTINUATION OF THE EXISTING AND
 REQUIRED LIGHTING OF PATH OF TRAVEL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-06 Cont ID  
Sent By vperez Date 2016-04-06 Time 09:03 Rev Time 0.00
Received By vperez Date 2016-04-06 Time 09:03 Sent To  
Notes
2016-04-05 14:13:284/5 TO ELEC BOX
  
2016-03-28 14:28:19RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By pleduc Date 2016-03-11 Time   Rev Time 0.00
Received By pleduc Date 2016-03-08 Time 09:09 Sent To  
Notes
2016-03-09 10:30:133/9 TO FIRE BOX
  
  
2016-03-09 09:09:44SUBMITTAL ROUTED TO SHILL

Review Stop Z ZONING
Rev No 1 Status N Date 2016-04-01 Cont ID  
Sent By shill Date 2016-04-01 Time 08:28 Rev Time 0.00
Received By shill Date 2016-04-01 Time 08:28 Sent To  
Notes
2016-04-01 08:29:12EMAILED ESCHNEIDER ON 4/1/16 - ZONING NOT REQUIRED? ES
 TO ADD ANOTHER ZONING STOP IF HE NEEDS TO SEE THIS