Plan Review Details - Permit 16030335
Plan Review Stops For Permit 16030335
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-23 Cont ID  
Sent By jvalido Date 2016-03-23 Time 09:02 Rev Time 0.00
Received By lmarchan Date 2016-03-18 Time 14:41 Sent To  
Notes
2016-03-18 14:41:54RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-17 Cont ID  
Sent By lmarchan Date 2016-03-17 Time 09:32 Rev Time 0.00
Received By lmarchan Date 2016-03-16 Time 14:28 Sent To  
Notes
2016-03-16 14:29:13RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By jvalido Date 2016-03-09 Time 14:24 Rev Time 0.00
Received By jvalido Date 2016-03-08 Time 13:37 Sent To  
Notes
2016-03-09 17:09:083/16/2016 SMALL DENIED. J. JV.
2016-03-08 13:37:20MECH -$5000

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-25 Cont ID  
Sent By jvalido Date 2016-03-25 Time 14:13 Rev Time 0.00
Received By jvalido Date 2016-03-25 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-22 Cont ID  
Sent By jvalido Date 2016-03-22 Time 16:14 Rev Time 0.00
Received By jvalido Date 2016-03-22 Time 16:08 Sent To  
Notes
2016-03-22 16:26:00PLEASE CONTACT ME AT 786-295-9282 TO SCHEDULE A MEETING
 TO GO OVER YOUR PLANS. THANK YOU.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-16 Cont ID  
Sent By jvalido Date 2016-03-16 Time 16:50 Rev Time 0.00
Received By jvalido Date 2016-03-16 Time 16:32 Sent To  
Notes
2016-03-16 16:49:11107.2.1 - PROVIDE CLEAR AND READABLE PLANS. I AM UNABLE
 TO DECIPHER ROOMS. LABEL BEDROOMS. DRAW IN WALLS. USE
 WHITE PAPER NOT GRAPH PAPER. PROVIDE A CLEAR AND
 READABLE EQUIPMENT SCHEDULE. PROVIDE QUALIFIER NAME,
 COMPANY NAME COMPANY ADDRESS, CONTRACTOR LICENSE AND
 SIGNATURE OF QUALIFIER. PROVIDE CONDENSER EQUIPMENT TIE
 DOWN DETAIL. PROVIDE ALL REQUEST FROM FIRST REVIEW.
 INCLUDE ENTIRE SCOPE OF WORK IN "SCOPE OF REVISION"
 SHOULD BE EXACT REPLACEMENT OF DUCTWORK, CHANGEOUT OF
 AHU AND CONDENSER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By jvalido Date 2016-03-09 Time 17:03 Rev Time 0.00
Received By jvalido Date 2016-03-09 Time 17:02 Sent To  
Notes
2016-03-09 17:01:57107.2.1 - PROVIDE SUPPLY BOX DIMENSIONS, DUCT SIZES AND
 CFM FOR EACH SUPPLY BRANCH. EQUIPMENT SCHEDULE
 REQUIRED. CHECK AND CONFIRM BATHROOM EXHAUST
 REQUIREMENTS 107.3.5 #10 PROVIDE LOCATION OF CONDENSER.
 109.3 CHECK SCOPE OF WORK AND PROVIDE AN ACCURATE
 PERMIT VALUATION.