Plan Review Details - Permit 16030299
Plan Review Stops For Permit 16030299
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-23 Cont ID  
Sent By shill Date 2016-04-23 Time 16:00 Rev Time 0.00
Received By shill Date 2016-04-23 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-21 Cont ID  
Sent By shill Date 2016-03-21 Time 17:17 Rev Time 0.00
Received By shill Date 2016-03-21 Time 14:07 Sent To  
Notes
2016-03-21 17:17:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. TWO SLOPES ARE SHOWN. REVISE PLAN TO SHOW COMPLIANCE
 WITH FBC 2014 ACCESSIBILITY 405.
  
 2. FBC 107, PROVIDE A DETAIL FOR THE SUPPORT FOR THE
 VESSEL TUB.
  
 3. SEVERAL SALES DESKS ARE SHOWN, BUT NO DETAILS
 PROVIDED. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 2014
 ACCESSIBILITY 904.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By mvaldes Date 2016-04-11 Time 12:06 Rev Time 0.00
Received By mvaldes Date 2016-04-11 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By mvaldes Date 2016-03-14 Time 16:01 Rev Time 0.00
Received By mvaldes Date 2016-03-14 Time 16:01 Sent To  
Notes
2016-03-14 17:33:19JOB PERMIT NUMBER: 16030299
 JOB ADDRESS: 820 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MARCH 14 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 240.24 E OVERCURRENT DEVICES OTHER THAN
 SUPPLEMENTARY OCPD SHALL NOT BE LOCATED IN BATHROOMS
 PLEASE RELOCATE PANELS. KEEP NEC 110.26 WORKING SPACE
 CLEARANCE IN MIND FOR POSITIONING. PLEASE CLARIFY ?
 - NEC 210.8 B GFCI PROTECTION REQUIRED FOR RECEPTACLES
 INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF SINKS.
 - NEC 110.9 , 110.10 PROVIDE AIC CALCULATIONS FROM FPL
 TRANSFORMER TO MAIN DISCONNECT AND FROM DISCONNECT TO
 EACH INDIVIDUAL PANEL ?
 - NEC 110.16 , 110.24 PROVIDE ARC-FLASH HAZARD WARNING
 LABEL AND AVAILABLE FAULT CURRENT MARKINGS.
 - MUST COMPLY WITH FBC-E SECTION 405 MANDATORY LIGHTING
 CONTROLS A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By pleduc Date 2016-04-07 Time   Rev Time 0.00
Received By pleduc Date 2016-04-07 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-11 Cont ID  
Sent By pleduc Date 2016-03-11 Time   Rev Time 0.00
Received By pleduc Date 2016-03-11 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-27 Cont ID  
Sent By ccole Date 2016-04-27 Time 10:12 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 13:34 Sent To  
Notes
2016-04-26 13:34:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-23 Cont ID  
Sent By shill Date 2016-04-23 Time 16:01 Rev Time 0.00
Received By shill Date 2016-03-30 Time 13:25 Sent To  
Notes
2016-03-30 13:26:24C31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-21 Cont ID  
Sent By shill Date 2016-03-21 Time 17:52 Rev Time 0.00
Received By shill Date 2016-03-07 Time 13:03 Sent To  
Notes
2016-03-08 13:04:06C29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-21 Cont ID  
Sent By shill Date 2016-03-21 Time 17:52 Rev Time 0.00
Received By shill Date 2016-03-21 Time 17:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-27 Cont ID  
Sent By ccole Date 2016-04-27 Time 10:11 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-04 Cont ID  
Sent By ccole Date 2016-04-04 Time 11:29 Rev Time 0.00
Received By ccole Date 2016-04-04 Time 11:29 Sent To  
Notes
2016-04-04 12:00:422ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030299
 4/4/16
  
 1) SHEET M100: HVAC NOTE INDICATES "DS DETECTORS TO BE
 INSTALLED IN ALL RETURN DUCTS", HOWEVER THE PLANS SHOW
 DS SYMBOLS AT THE SUPPLY DUCTS OF THE SYSTEMS. PLEASE
 NOTE THAT THE CODE IS A MINIMUM COMPLIANCE PATH AND
 WHERE DS DETECTORS ARE REQUIRED PER SECTION 606.2.1,
 THEY SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS.
 2) PLEASE PROVIDE A HEAT REJECTION CALCULATION TO
 CLARIFY HOW AC -2A WAS SIZED. THE SCHEDULE INDICATES A
 3-TON SYSTEM FOR THE IT ROOM WHICH IS APPROXIMATELY 60
 SQ.FT.
 3) PROVIDE THE MIAMI-DADE NOA FOR THE ALUMA-STAND
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR.
 4) THE SUBMITTED SPECIFICATIONS FOR THE XVENT BOX DO
 NOT INDICATE THE PRODUCT HAS BEEN TESTED AND CETRTIFIED
 TO MEET THE AMCA 550 STANDARD FOR AIR PERFORMANCE,
 WATER PENETRATION, AND WIND-DRIVEN RAIN- SEE SECTIONS
 401.5 AND 501.3.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By ccole Date 2016-03-15 Time 07:58 Rev Time 0.00
Received By ccole Date 2016-03-15 Time 07:58 Sent To  
Notes
2016-03-15 08:07:151ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION
 PERMIT #16030299
 3/15/16
  
 1) REFER TO SECTION C403.2.7.6 FBC-14 ENERGY
 CONSERVATION: AIR-HANDLING UNITS SHALL NOT BE ALLOWED
 IN ATTICS OF COMMERCIAL BUILDINGS. SHEET A100 SHOWS
 AHU'S 1, 3, 4, 5, 6, 7 IN THE ATTIC SPACE- PLEASE
 CORRECT THE PLANS AND DETAILS.
 2) THE SUBMITTED ENERGY FORM C402-2014 DOES NOT SHOW
 COMPLIANCE DATA FOR THE NEW MINI-SPLIT AC SYSTEMS.
 3) THE AC CALCULATIONS INDICATE 8.63 TONS FOR AHU-1 AND
 4.26 TONS FOR AHU-3, HOWEVER THE EXISTING SYSTEMS SHOWN
 ON M300 INDICATE 6.5 TON FOR AHU-1, AND 2.5 TON FOR
 AHU-3. IT WOULD APPEAR THE TWO EXISTING SYSTEMS ARE
 UNDERSIZED.
 4) SHEET M100: ACCESS PANELS ARE REQUIRED FOR THE
 ABOVE-CEILING AIR HANDLERS. REFER TO SECTION 306.1 AND
 PROVIDE A DIMENSIONED DETAIL FOR CONSTRUCTION AND
 INSTALLATION OF THE PANELS.
 5) M100: A DUCT SMOKE DETECTOR SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF AHU-1- SECTION 606.2.1 FBC-14
 MECHANICAL. PLEASE INDICATE HOW ALL OF THE DS DETECTORS
 WILL BE SUPERVISED IN COMPLIANCE WITH 606.4.1.
 6) M100: SHOW THE LOCATIONS OF CU'S 1A, 2A, & # 3A, AND
 PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15.
 7) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES OF THE NEW OCCUPANCY- SEE TABLE 403.3 FBC-14
 MECHANICAL AND PROVIDE A SCHEDULE ON THE PLANS
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 8) PLEASE CORRECT THE NOTE BY THE OUTDOOR AIR INTAKE
 FOR AHU'S 2 & 3: A MOTORIZED OR GRAVITY DAMPER IS
 REQUIRED FOR THE INTAKE PER SECTIONS C402.4.5 AND
 C402.4.5.2 FBC-14 ENERGY CONSERVATION. PLEASE SEE
 SECTION 401.4 FBC-14 MECHANICAL AND SHOW REQUIRED
 CLEARANCES FOR ALL AIR INTAKES.
 9) INDICATE HOW THE EXHAUST AND AIR INTAKE OPENINGS
 WILL BE PROTECTED FROM WIND BORNE DEBRIS- SEE CHAPTER
 19 FBC BUILDING. PLEASE NOTE THAT ALL SUBMITTALS (
 MANUFACTURER'S SPECIFICATIONS, PRODUCT APPROVALS, NOA'S
 ETC.) SHALL BE REVIEWED AND APPPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By gjohnson Date 2016-04-13 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2016-04-13 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By gjohnson Date 2016-03-16 Time 13:00 Rev Time 0.00
Received By gjohnson Date 2016-03-15 Time 14:04 Sent To  
Notes
2016-03-16 13:28:331ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE LETTER FROM ARCHITECT REQUESTING RELIEF FOR
 HOT WATER REQUIRED ON THE TUB AND SHOWERS PER FBC PL
 SEC. 607.1
 2. BACK FLOW REQUIRED ON AUTOFILL FOR FOUNTAIN. PER FBC
 PL SEC. 608.13
 3. PROVIDE MANUFACTURE SPEC SHEETS FOR STEAM
 UNIT,BOOSTER PUMP AND WATER HEATERS. PER WPB AMEND. TO
 FBC SEC. 107.2.1
 4. SHOW LOCATION OF OF WATER HEATER PAN DRAIN SHT.P100.
 PER WPB AMEND.TO FBC SEC. 107.2.1
 5. SHT. P100 SHOWS STORAGE TANK WATER HEATER SHT. P300
 DETAILED ELELECTRIC WATER HEATER SHOWS TANKLESS PLEASE
 CLARIFY. PER WPB AMEND.TO FBC SEC. 107.2.