Plan Review Details - Permit 16030279
Plan Review Stops For Permit 16030279
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-12 Cont ID  
Sent By cthroop Date 2016-07-12 Time 11:43 Rev Time 0.00
Received By cthroop Date 2016-07-12 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By cthroop Date 2016-03-14 Time 09:59 Rev Time 0.00
Received By cthroop Date 2016-03-14 Time 09:59 Sent To  
Notes
2016-03-14 10:07:551ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE DETAIL FOR POLE BURIAL RTEQUIREMENTS.
 2. PROVIDE WIND LOAD CALC'S. FOR EACH TYPE OF POLE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-14 Cont ID  
Sent By mvaldes Date 2016-03-14 Time 09:27 Rev Time 0.00
Received By mvaldes Date 2016-03-14 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-12 Cont ID  
Sent By cthroop Date 2016-07-12 Time 11:43 Rev Time 0.00
Received By cthroop Date 2016-07-08 Time 13:13 Sent To  
Notes
2016-07-08 13:13:39RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-14 Cont ID  
Sent By cthroop Date 2016-03-14 Time 09:59 Rev Time 0.00
Received By cthroop Date 2016-03-07 Time 10:27 Sent To  
Notes
2016-03-09 16:31:50TO ELECTRIC
2016-03-08 10:27:25ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-09 Cont ID  
Sent By aaponte Date 2016-03-09 Time 16:29 Rev Time 0.00
Received By aaponte Date 2016-03-09 Time 16:29 Sent To  
Notes
***NONE***