Plan Review Details - Permit 16030249
Plan Review Stops For Permit 16030249
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-07-01 Cont ID  
Sent By cthroop Date 2017-07-01 Time 10:24 Rev Time 0.00
Received By cthroop Date 2017-06-29 Time 17:14 Sent To  
Notes
2017-07-01 10:51:34BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADVISORY: SUB PERMITS FOR 14100911 HAVE EXPIRED. PLEASE
 RE-SUBMIT PLUMBING AND ELECTRIC SUB PERMITS WITH
 CURRENT SCOPE OF WORK AND CONTRACTOR INFO.
  
 1. CHANGE OF DESIGN PROFESSIONAL FROM JOHN GRIFFIN,
 P.E. TO JOHN M NOSSAL AIA.
 2. SUBMITTED PLANS SHOW WATER HEATER AS EXISTING,
 LOCATED OUTSIDE RESIDENCE IN AN ILLEGALLY CONSTRUCTED
 STORAGE STRUCTURE.
 3. SEARCH OF PUBLIC RECORDS (FILE NET) INDICATES NO
 PERMIT WAS ISSUED FOR THE RE-LOCATION OF THE WATER
 HEATER.
 3A. PERMIT # 14100911 WAS ISSUED TO REPLACE WATER
 HEATER (LIKE FOR LIKE). NO PLAN WAS SUBMITTED OR
 REQUIRED, NO CHANGE IN LOCATION.
 3B. PERMIT # 14120915 WAS ISSUED TO ADDRESS VARIOUS
 ITEMS OF UN-PERMITTED WORK. WATER HEATER WAS NOT PART
 OF THIS PERMIT.
 4. THIS RE-SUBMITTAL OF REVISION # 16030249 OF MASTER
 PERMIT # 14120915 IS TO INCLUDE PERMITTING AND
 INSPECTION OF ILLEGALLY CONSTRUCTED STORAGE SHED AND
 RELOCATION OF WATER HEATER. WORK DESCRIPTION WILL BE
 CHANGED TO REFLECT ENTIRE SOW.
 5. ROOFING PERMIT REQUIRED.
 6. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 7. PROVIDE DETAIL OF STRUCTURAL ATTACHMENT OF SHED DOOR
 OR PROVIDE PRODUCT APPROVAL FOR NEW DOOR. NOTE: FBC R
 301.2.1.2 PROVIDES EXEMPTION FOR OPENING PROTECTION FOR
 STORAGE SHEDS OF 720 SQ, FT. OR LESS.
 8. PROVIDE DETAIL OF STRUCTURAL SLAB. IF EXISTING,
 VERIFY FOOTING AND SLAB THICKNESS AND FOOTING
 RE-INFORCEMENT.
 9. PROVIDE SITE PLAN. DEMONSTRATE REQUIRED SETBACKS TO
 PROPERTY LINES.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING AND DOOR SUBMITTALS.
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 10:11 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 10:11 Sent To  
Notes
2016-10-21 11:03:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
  
 1. ADVISORY - THE FOLLOWING ITEMS WERE ADDRESSED ON THE
 1ST REVIEW AND HAVE NOT BEEN ADDRESSED BY DESIGNER OF
 RECORD. IF THESE ITEMS ARE NOT ADDRESSED ON THE NEXT
 REVIEW (4TH) THEY WILL TRIGGER MANDATORY 4X PERMIT FEE
 PER FS 553.80 (2) (B).
 2. STRUCTURAL DETAILS FOR PROPOSED ADDITION FOR WATER
 HEATER. PROVIDE DETAILS FOR FOUNDATION, WALLS, ROOF
 SYSTEM AND DOORS (PRODUCT APPROVALS). PROVIDE
 DEMENSIONS OF PROPOSED ADDITION AND ROUGH OPENINGS.
 3. PROVIDE SURVEY TO SHOW DISTANCE FROM PROPOSED WALLS
 OF ADDITION TO PROPERTY LINE. VERIFY WALLS OF ADDITION
 DO NOT ENCROACH UPON BUILDING SET BACKS.
 4. PROPOSED ADDITION ON PLAN SHEET 1 IS A DIFFERENT
 SIZE THAN THE PROPOSED ADDITION ON PLAN SHEET E-1.
 PLEASE CLARIFY.
 5. CODE REFERENCE ON PLAN SHEET 1 STATES "FBC 2010
 EXISTING BUILDING CODE". THE GOVERNING CODE FOR THIS
 SUBMITTAL IS THE 2014 FLORIDA BUILDING CODE W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION.
 PLEASE CHANGE GOVERNING CODE REFERENCE ON PLANS.
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-02 Cont ID  
Sent By shill Date 2016-08-02 Time 10:03 Rev Time 0.00
Received By cthroop Date 2016-08-02 Time 10:03 Sent To  
Notes
2016-08-02 10:05:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
 DATE: 8/2/16
  
 1. COMMENTS FROM 1ST REVIEW BY SAMANTHA HILL ON 3/22/16
 HAVE NOT BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By shill Date 2016-03-22 Time 07:52 Rev Time 0.00
Received By shill Date 2016-03-22 Time 07:52 Sent To  
Notes
2016-03-22 07:59:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AN "EXISTING" WATER HEATER IS SHOWN. THIS IS NOT
 CONSIDERED "EXISTING" UNLESS IT IS LEGALLY PERMITTED,
 INSPECTED, AND A FINAL INSPECTION OBTAINED. THIS SHOULD
 BE REFERRED TO AS "PROPOSED" OR "WORK INSTALLED WITHOUT
 PERMIT." THE PLAN, SIGNED AND SEALED BY THE ENGINEER,
 IS MISLEADING. THIS ENGINEER HAS ALREADY SUBMITTED A
 PLAN SHOWING "EXISTING" CONDITIONS. HOW COULD THEY BOTH
 BE "EXISTING" WHEN THEY ARE NOT THE SAME? A SET HAS
 BEEN RETAINED AND MAY BE FORWARDED TO FBPE. WHEN PLANS
 ARE SIGNED AND SEALED BY A DESIGN PROFESSIONAL, PLAN
 REVIEW TENDS TO RELY ON THESE PLANS AS ACCURATE. SEE
 FBC 107. PLANS ARE TO ACCURATELY SHOW THE NATURE AND
 SCOPE OF WORK.
  
 HAS THE ENGINEER VISITED THE JOB SITE, FS471? IT IS NOT
 CLEAR WHY THERE ARE DISCREPANCIES ON THE PLANS. PLEASE
 HAVE ENGINEER ADDRESS THIS ISSUE.
  
 2. STRUCTURAL DETAILS HAVE BEEN REQUESTED BY INSPECTORS
 AND PLAN REVIEWERS. ADDRESS AT THIS TIME, FBC 107.
  
 3. PROVIDE A SURVEY WHICH SHOWS THE DISTANCE OF THE
 PROPOSED NEW WALL (WATER HEATER ENCLOSURE WALL) TO THE
 PROPERTY LINE, FBC 2010 RESIDENTIAL 302. DUE TO FLORIDA
 STATUTUTORY SCOPE OF WORK UNDER THE LICENSES OF
 PROFESSIONAL LAND SURVEYORS, ARCHITECTS, AND ENGINEERS,
 ONLY A SURVEYOR CAN DETERMINE THE LOCATION OF THE
 PROPERTY LINE.
  
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO PERFORM A
 COMPLETE PLAN REVIEW.
  
 4. THE WORD "EXISTING" IS IN MANY LOCATIONS ON THE
 PLAN. ITEMS WHICH WERE PERMITTED, INSPECTED AND FINALED
 ARE "EXISTING." IF ALL ITEMS DO NOT MEET THIS
 DEFINITION FOR BUILDING DEPARTMENT PURPOSES, REVISE THE
 PLAN TO CLARIFY NATURE OF EACH ITEM - PROPOSED? BUILT
 OR INSTALLED WITHOUT PERMIT, TO BE LEGALIZED UNDER THE
 SCOPE OF THIS PERMIT?
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 12:15 Rev Time 0.00
Received By jleahy Date 2017-06-26 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-20 Cont ID  
Sent By vperez Date 2016-10-20 Time 11:53 Rev Time 0.00
Received By vperez Date 2016-10-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-19 Cont ID  
Sent By vperez Date 2016-07-19 Time 10:03 Rev Time 0.00
Received By vperez Date 2016-07-19 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By vperez Date 2016-03-09 Time 06:10 Rev Time 0.00
Received By vperez Date 2016-03-09 Time 06:10 Sent To Z
Notes
2016-03-09 06:16:58INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO GRANTED UPON INITIAL ISSUANCE OF PERMIT HAS
 NOT BEEN ADDRESSED ON PLANS.
 2. PROVIDE MANUF. DATA SHEET OF WATER HEATER BEING
 INSTALLED TO VERIFY LOADS. FBC 107.3.5
 3. SHOW A MEANS DISCONNECT WITHIN SIGHT OF EQUIPMENT.
 FBC RES E4105.5
 4. PLEASE CONTACT ME WITH ANY QUESTIONS OR CONCERNS
 REGARDING THIS PROJECT AT THE NUMBER LISTED BELOW.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-01 Cont ID  
Sent By cthroop Date 2017-07-01 Time 10:24 Rev Time 0.00
Received By cthroop Date 2017-06-13 Time 11:38 Sent To  
Notes
2017-06-14 11:38:28R14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 10:11 Rev Time 0.00
Received By cthroop Date 2016-10-14 Time 15:51 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-02 Cont ID  
Sent By cthroop Date 2016-08-02 Time 10:03 Rev Time 0.00
Received By cthroop Date 2016-07-14 Time 12:50 Sent To  
Notes
2016-07-14 12:51:12LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-22 Cont ID  
Sent By shill Date 2016-03-22 Time 08:23 Rev Time 0.00
Received By shill Date 2016-03-04 Time 11:15 Sent To  
Notes
2016-03-09 06:17:173/9 TO CAROLINE
2016-03-07 11:15:58TKLARGE DESK

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-07-12 Cont ID  
Sent By tklarge Date 2017-07-12 Time 11:56 Rev Time 0.00
Received By tklarge Date 2017-07-12 Time 11:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-06-26 Cont ID  
Sent By tklarge Date 2017-06-26 Time 07:50 Rev Time 0.00
Received By tklarge Date 2017-06-26 Time 06:21 Sent To  
Notes
2017-06-26 06:59:151) THERE IS A SET OF PLANS IN THE FOLDER THAT ARE FROM
 JOHN GRIFFIN, P.E.THAT ARE NOT VOIDED AND ALSO TWO SETS
 FROM JOHN NOSSAL. SUBMIT THE TWO SETS TO BE USED FOR
 THIS PERMIT. WPB AMEND. TO FBC SEC. 107.1.
 2) THE PLANS FROM JOHN NOSSAL HAVE NOTES ON THEM
 STATING THERE IS MINOR PLUMBING WORK TO BE DONE, BUT
 THERE IS NO INFORMATION AS TO THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE. DETAIL ON THE PLAN THE ENTIRE
 SCOPE OF PLUMBING WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) UNDER THE HEADING "PLUMBING SPECIFICATIONS" THERE IS
 A NOTE STATING THAT "ALL NEW PLUMBING SUPPLY LINES TO
 BE 3/4" COPPER TUBE." CLARIFY.
 4) CLARIFY THE NOTE "EXIST. WATER WAS REMOVED &
 REPLACED IN KIND" AS NOTED UNDER THE ELECTRICAL
 SPECIFICATIONS HEADING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
2017-06-21 08:30:55ON TIM LARGE'S DESK 6/21/117 GPJ

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-10-21 Cont ID  
Sent By tklarge Date 2016-10-21 Time 04:06 Rev Time 0.00
Received By tklarge Date 2016-10-21 Time 03:51 Sent To  
Notes
2016-10-21 03:51:141) ONLY A REVISED SHEET E-1 HAS BEEN SUBMITTED. SUBMIT
 A REVISED SHEET NO.1 THAT SHOWS COMPLIANCE WITH ALL THE
 PLAN REVIEW COMMENTS. WPB AMEND TO FBC SEC. 107.2.1.
 2) SHOW THE ORIGINAL LOCATION OF THE WATER HEATER.
 PREVIOUS PERMITS SHOW THE ORIGINAL LOCATION IN THE
 "SEWING ROOM" WHICH IS NOW ILLEGALLY BEING USED AS A
 BEDROOM. 3RD REQUEST.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER. FBC 107.2.1. IF THE LOCATION OF
 THE WATER HEATER IS CONSIDERED A WET LOCATION, THE
 WATER HEATER SHALL BE LABELED FOR SUCH USE. 3RD REQUEST
 4) THIS PERMIT SHALL INCLUDE THE ILLEGALLY CONSTRUCTED
 EXTERIOR ENCLOSURE THAT HOUSES THIS WATER HEATER. FBC
 105.1. SUBMIT DETAILS FOR THE ENCLOSURE.FBC 107.1.3RD
 REQUEST.
  
 NOTE - THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE
 PLAN REVIEW FEE IN ACCORDANCE WITH FL.STATUTES 553.80
 (B).
  
 I SUGGEST THE ENGINEER OF RECORD CONTACT ME TO MAKE AN
 APPOINTMENT TO REVIEW THE COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By tklarge Date 2016-07-29 Time 11:41 Rev Time 0.00
Received By tklarge Date 2016-07-29 Time 11:36 Sent To  
Notes
2016-07-29 11:40:121) THE WATER HEATER IN THE EXTERIOR ENCLOSURE IS NOT AN
 EXISTING WATER HEATER. IT IS A NEW WATER HEATER IN A
 NEW LOCATION AND SHALL BE DEPICTED ON THE PLANS AS
 SUCH. IT HAS BEEN RELOCATED FROM IT'S ORIGINAL LOCATION
 WITH NEW WATER PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE ORIGINAL LOCATION OF THE WATER HEATER.
 PREVIOUS PERMITS SHOW THE ORIGINAL LOCATION IN THE
 "SEWING ROOM" WHICH IS NOW ILLEGALLY BEING USED AS A
 BEDROOM. 2ND REQUEST.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER. FBC 107.2.1. IF THE LOCATION OF
 THE WATER HEATER IS CONSIDERED A WET LOCATION, THE
 WATER HEATER SHALL BE LABELED FOR SUCH USE. 2ND REQUEST
 4) THIS PERMIT SHALL INCLUDE THE ILLEGALLY CONSTRUCTED
 EXTERIOR ENCLOSURE THAT HOUSES THIS WATER HEATER. FBC
 105.1. SUBMIT DETAILS FOR THE ENCLOSURE.FBC 107.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By tklarge Date 2016-03-08 Time 03:52 Rev Time 0.00
Received By tklarge Date 2016-03-08 Time 03:40 Sent To  
Notes
2016-03-08 03:45:031) SHOW THE ORIGINAL LOCATION OF THE WATER HEATER.
 PREVIOUS PERMITS SHOW THE ORIGINAL LOCATION IN THE
 "SEWING ROOM" WHICH IS NOW ILLEGALLY BEING USED AS A
 BEDROOM.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER. FBC 107.2.1. IF THE LOCATION OF
 THE WATER HEATER IS CONSIDERED A WET LOCATION, THE
 WATER HEATER SHALL BE LABELED FOR SUCH USE.
 3) THIS PERMIT SHALL INCLUDE THE ILLEGALLY CONSTRUCTED
 EXTERIOR ENCLOSURE THAT HOUSES THIS WATER HEATER. FBC
 105.1. SUBMIT DETAILS FOR THE ENCLOSURE.FBC 107.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2017-06-28 Cont ID  
Sent By njwira Date 2017-06-28 Time 16:29 Rev Time 0.00
Received By njwira Date 2017-06-28 Time 14:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-10-19 Cont ID  
Sent By cthroop Date 2016-10-21 Time 10:11 Rev Time 0.00
Received By njwira Date 2016-10-17 Time 09:57 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By ajones Date 2016-07-27 Time 15:10 Rev Time 0.00
Received By ajones Date 2016-07-27 Time 15:09 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By ajones Date 2016-03-11 Time 13:52 Rev Time 0.00
Received By ajones Date 2016-03-11 Time 13:52 Sent To B
Notes
2016-03-11 13:54:123/11/16- FAILED NEED TO SHOW LOCATION OF RELOCATED
 WATER HEATER ON PLAN
 ANGELLA VANN
 561-822-1441
 [email protected]