Plan Review Details - Permit 16030229
Plan Review Stops For Permit 16030229
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By jwitmer Date 2016-05-09 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2016-05-09 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 12:15 Sent To  
Notes
2016-03-24 13:44:32BUILDING PLAN REVIEW
 W.P.B. REVISION: 16030229
 W. P. B. PERMIT: 15070534
 ADD: 4117 BROADWAY
 CONT: DREAMWORKS CONST. & REMOD.
 TEL: (813)249-5541
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MARCH 24/ 2016
 ACTION: DENIED.
  
 NOTE THIS WAS A PROVISO UNDER THE PRIME PERMIT
 15070534. THE COVERSHEET LIST VARIOUS PRODUCT
 APPROVALS. PLEASE SUBMIT THE ACTUAL PRODUCT APPROVALS
 FOR REVIEW FOR CODE COMPLIANCE. NO PRODUCTS SUBMITTED
 ON THE 2ND REVIEW CYCLE.
 BUILT UP ROOFING GAF FL # 477-R07
 UNDERLAYMENT GAF FL # 10626-R12
 FASTENERS OMG FL # 699-R07
 INSULATION GAF FL # 16311-R4
  
 1) THE SUBMITTED PRODUCT APPROVAL IS A DIFFERENT
 APPROVAL FROM THE PRODUCT APPROVALS LISTED UNDER THE
 PRIME PERMIT. THE CONTRACTOR HAS HAD THE ENGINEER OF
 RECORD APPLY THEIR SHOP DRAWING STAMP OF APPROVAL BUT
 WITHIN THE DOCUMENT THERE ARE MANY SUB-SYSTEMS FOR
 INSULATED WOOD DECKS AS WELL AS NON-INSULATED WOOD
 DECKS WITH VARYING PRESSURES. NO SUB-SYSTEM HAS BEEN
 IDENTIFIED. PLEASE IDENTIFY WHICH SUB-SYSTEM IS TO BE
 APPLIED, THEN CIRCLE THE C EXPOSURE, ENCLOSED
 STRUCTURE, 15 FEET MEAN ROOF HEIGHT AND THE 170 MPH
 COLUMN.
 THIS WILL GIVE YOU THE REQUIRED FASTENING PATTERN FOR
 ROOF ZONES 2 & 3.
  
 2) WE HAVE TALKED ON THE TELEPHONE ABOUT THIS JOB.
 FOLLOW THE INSTRUCTIONS THE INSPECTOR HAS GIVEN YOU, ON
 THE PERMIT CARD.
 2A) PROVIDE INPROGRESS PICTURES OR AN ENGINEER'S
 INSPECTION REPORT. INPROGRESS INSPECTION MISSED.
  
 2B) PROVIDE APPROVED PRODUCT APPROVALS.
  
 3) THEN RECALL IN THE FINAL ROOFING INSPECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By jwitmer Date 2016-03-08 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-03-08 Time 06:02 Sent To  
Notes
2016-03-08 06:33:13BUILDING PLAN REVIEW
 W.P.B. REVISION: 16030229
 W. P. B. PERMIT: 15070534
 ADD: 4117 BROADWAY
 CONT: DREAMWORKS CONST. & REMOD.
 TEL: (813)249-5541
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 08/ 2016
 ACTION: DENIED.
  
 NOTE THIS WAS A PROVISO UNDER THE PRIME PERMIT
 15070534.
 1) THE DESIGNER OF RECORD HAS LISTED THE PRODUCT
 APPROVALS TO BE USED FOR THE INSTALATION OF THE ROOFING
 SYSTEM.SEE LIST BELOW. THE ROOFING CONTRACTOR MENDIETA
 ROOFING CORP HAS SUBMITTED PRODUCT THAT ARE DIFFERENT
 FROM THE PRODUCTS THE ENGINEER OF RECORD HAS REQUESTED
 ON THE COVERSHEET OF THE PLANS. THE ENERGY CALCULATIONS
 SUBMITTED FOR THIS JOB INDICATES THE USE OF ISO/METAL
 DECK AND A R-VALUE OF 6.7. PLEASE SHOW COMPLIANCE WITH
 THE ENERGY CODE AS WELL.
  
 REGISTERED DESIGN PROFESSIONAL: MAZEN MARIE -P. E.
 60166
  
 107.3.4.2 DEFERRED SUBMITTALS. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 THE COVERSHEET LIST VARIOUS PRODUCT APPROVALS. PLEASE
 SUBMIT THE ACTUAL PRODUCT APPROVALS FOR REVIEW FOR CODE
 COMPLIANCE. NO PRODUCTS SUBMITTED ON THE 2ND REVIEW
 CYCLE.
 BUILT UP ROOFING GAF FL # 477-R07
 UNDERLAYMENT GAF FL # 10626-R12
 FASTENERS OMG FL # 699-R07
 INSULATION GAF FL # 16311-R4
  
  
  
 2) NOT PART OF THIS SUBMITTAL. SHEET A-3 PRE-ENGINEERED
 AWNING DESIGNED BY A DELEGATE SPECIALTY ENGINEER. SHOP
 DRAWINGS ARE TO BE SUBMITTED TO THE DESIGNER OF RECORD
 AND APPROVED, WITH SHOP DRAWING STAMP OF REVIEWED
 BEFORE SUBMITTING TO THE BUILDING DEPARTMENT. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-09 Cont ID  
Sent By   Date 2016-05-09 Time   Rev Time 0.00
Received By lmarchan Date 2016-04-28 Time 16:24 Sent To  
Notes
2016-04-28 16:24:45RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2016-03-23 Time 09:15 Sent To  
Notes
2016-03-24 09:16:00RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-08 Cont ID  
Sent By jwitmer Date 2016-03-08 Time 06:33 Rev Time 0.00
Received By jwitmer Date 2016-03-04 Time 14:10 Sent To  
Notes
2016-03-04 14:10:53REVISION ROUTED TO JWITMER