Plan Review Details - Permit 16030222
| Plan Review Stops For Permit 16030222 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-11-29 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-11-29 |
Time |
13:02 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-10-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2016-10-31 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2016-10-31 07:53:02 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16030222 | | | ADD: 5400 EAST AVENUE | | | CONT: STUART & SHELBY DEVELOPMENT | | | TEL: 561-637-7902 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | | | | | | | 4TH REVIEW | | | DATE: MON. OCT. 31/ 2016 | | | ACTION: DENIED | | | | | | NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT | | | TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | | | | 1-3) COMPLIED. | | | | | | 4A) 4TH REQUEST!!!!!! THE CITY IS IN RECEIPT OF THE | | | FLOOD ZONE CERTIFICATE FOR 5400 EAST AVE. SURVEYORS | | | NAME: JAMES G. PEDEN, JR. DATED 6/12/2015. PLEASE NOTE | | | THIS CERTIFICATE IS NOT SIGNED NOR SEALED BY THE | | | SURVEYOR. SURVEYORS: F. S. 472.025 SEALS. THE FINISH | | | FLOOR IS GIVEN AT ELEVATION 17.1 FT. NGVD. PLEASE ALSO | | | NOTE THE SUBMITTED | | | ELEVATION CERTIFICATE IS ALSO MARKED FINISH | | | CONSTRUCTION SEE LINE C1 OF CERTIFICATE. THIS 1ST | | | ELEVATION CERTIFICATE SHOULD BE MARKED CONSTRUCTION | | | DRAWINGS. THE CERTIFICATE SHOULD READ CONSTRUCTION | | | DRAWINGS. | | | | | | | | | | | | 4B-E) COMPLIED. | | | | | | 1ST ROUND COMMENT. 4) PLEASE NOTE THIS PROPERTY IS | | | LOCATED WITHIN AN AH FLOOD ZONE. FBC BUILDING 1612 AND | | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | | ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5-8) COMPLIED. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-09-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-09-07 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-09-07 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2016-09-07 14:01:29 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16030222 | | | ADD: 5400 EAST AVENUE | | | CONT: STUART & SHELBY DEVELOPMENT | | | TEL: 561-637-7902 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: WED. SEPT. 07/ 2016 | | | ACTION: DENIED | | | | | | 1-3) COMPLIED. | | | | | | 4A) 3RD REVIEW. FLOOD ZONE COMMENT. THE CITY IS IN | | | RECEIPT OF THE FLOOD ZONE CERTIFICATE FOR 5400 EAST | | | AVE. SURVEYORS NAME: JAMES G. PEDEN, JR. DATED | | | 6/12/2015. PLEASE NOTE THIS CERTIFICATE IS NOT SIGNED | | | NOR SEALED BY THE SURVEYOR. SURVEYORS: F. S. 472.025 | | | SEALS. THE FINISH FLOOR IS GIVEN AT ELEVATION 17.1 FT. | | | NGVD. | | | | | | 4B) 3RD REVIEW. SCOPE OF PROJECT WAS REDUCED FROM | | | $1,075,000.00 DOLLARS TO $998,616.00 IN VALUE. PLEASE | | | SUBMIT ON THE CONTRACTORS LETTERHEAD AN ITEMIZED LIST | | | AND DOLLAR AMOUNT WHERE THE SCOPE OF WORK WAS REDUCED | | | TO UNDER THE 50% OF THE MARKET VALUE. | | | | | | 2ND REVIEW COMMENT. THE CITY HAS ALSO REVIEWED THE | | | BUILDING EVALUATION REPORT PREPARED BY BOYLE & DRAKE | | | INC. LISTING THE MARKET VALUE OF THE STRUCTURE AT | | | $2,435,000.00 DOLLARS. 50% OF THE MARKET VALUE IS | | | $1,217,500.00 DOLLARS. | | | | | | 4C) THE CITY?S MUNI CODE UNDER THE DEFINITION OF | | | SUBSTANTIAL IMPROVEMENT IS FOUND UNDER ARTICLE XIX | | | DEFINITIONS, SECTION 94-611. | | | SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF | | | REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO | | | A STRUCTURE, TAKING PLACE DURING THE LIFE OF A | | | STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR | | | EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE | | | STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE | | | THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START | | | OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF | | | DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE | | | OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, | | | "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN | | | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR | | | OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, | | | WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL | | | DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL | | | IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT | | | OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, | | | SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO | | | ENSURE SAFE LIVING CONDITIONS. | | | | | | 4D) SINCE SUBSTANTIAL IMPROVEMENT HAS BEEN MET WITH THE | | | RENOVATION PERMIT (01040625/ VALUE OF | | | $150,000.00)TO THIS BUILDING. $1,075,000 (APPLIED | | | PERMIT VALUE) + $150,000.00 = $ 1,225,000.00 WHICH IS | | | GREATER THAN $1,217,500.00 OR 50% OF THE STRUCTURE | | | SUBSTANTIAL IMPROVEMENT HAS BEEN MET. | | | | | | 4E) SINCE IS A COMMERCIAL BUILDING ( NONRESIDENTIAL) | | | FLOOD PROOFING IS A OPTION TO MEET CODE COMPLIANCE. | | | WEST PALM BEACH MUNI CODE: | | | SEC. 94-546 (B) AREAS OF SPECIAL FLOOD HAZARD WITH BASE | | | FLOOD ELEVATION PROVIDED. (2) NONRESIDENTIAL | | | CONSTRUCTION. | | | ALL NEW CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY | | | COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL | | | STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING | | | BASEMENT, ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE | | | BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT | | | UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO | | | THAT BELOW SIX INCHES ABOVE THE FLOOD BASE LEVEL THE | | | STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY | | | IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL | | | COMPONENTS HAVING THE CAPABILITY OF RESISTING | | | HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF | | | BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR | | | ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS | | | SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE | | | PROVIDED TO THE CITY ENGINEER. | | | | | | 1ST ROUND COMMENT. 4) PLEASE NOTE THIS PROPERTY IS | | | LOCATED WITHIN AN AH FLOOD ZONE. FBC BUILDING 1612 AND | | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | | ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5-8) COMPLIED. | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-06-16 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-06-16 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2016-06-16 13:31:39 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16030222 | | | ADD: 5400 EAST AVENUE | | | CONT: STUART & SHELBY DEVELOPMENT | | | TEL: 561-637-7902 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: THURS. JUNE 16/ 2016 | | | ACTION: DENIED | | | | | | 1)SHEET A9 INDICATES THE WINDOW AND EXTERIOR DOOR | | | POSITIVE & NEGATIVE PRESSURES. PLEASE PROVIDE WHERE THE | | | WIND DESIGN CRITERIA CAN BE LOCATED IN THE PLANS. | | | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | | | | | | | 2A) SEMI- REQUIRED, PLEASE CIRCLE WHICH APPLICATION | | | METHOD WILL BE USED TO INSTALL THIS TYPE SHUTTER. | | | SHEET A7 SHOWS A WHITE BAHAMA STYLE SHUTTER, PLEASE | | | PROVIDE IF THIS RIGID AWNING WILL STAY AS POSITIONED OR | | | REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING IS | | | UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN THE | | | CLOSED POSITION SHALL ALSO COMPLY WITH CHAPTER 16 AND | | | SHALL BE IMPACT RESISTANT IN ACCORDANCE WITH SECTION | | | 1609.1.2 FBC-B. | | | | | | 2B) NEW COMMENT. SUBMITTED FLORIDA PRODUCT APPROVAL | | | TRULITE 351 SERIES ALUM OUTSWING DRY GLAZED DOORS FL# | | | 17086 DOES NOT HAVE THE FLORIDA COVERSHEET SHOWING IT | | | IS STILL AN APPROVED REPORT. THIS REPORT NOT LISTED ON | | | THE FLORIDA APPROVAL WEBSITE. COMPLIANCE WITH 2014 | | | FBC-B 1609.4.4.1. | | | | | | 3) COMPLIED. 2008 MIST DRYSTACK LEDGESTONE OWENS | | | CORNING. | | | | | | 4A) FLOOD ZONE COMMENT. THE CITY IS IN RECEIPT OF THE | | | FLOOD ZONE CERTIFICATE FOR 5400 EAST AVE. SURVEYORS | | | NAME: JAMES G. PEDEN, JR. DATED 6/12/2015. PLEASE NOTE | | | THIS CERTIFICATE IS NOT SIGNED NOR SEALED BY THE | | | SURVEYOR. SURVEYORS: F. S. 472.025 SEALS. THE FINISH | | | FLOOR IS GIVEN AT ELEVATION 17.1 FT. NGVD. | | | | | | 4B) THE CITY HAS ALSO REVIEWED THE BUILDING EVALUATION | | | REPORT PREPARED BY BOYLE & DRAKE INC. LISTING THE | | | MARKET VALUE OF THE STRUCTURE AT $2,435,000.00 DOLLARS. | | | 50% OF THE MARKET VALUE IS $1,217,500.00 DOLLARS. | | | | | | 4C) THE CITY?S MUNI CODE UNDER THE DEFINITION OF | | | SUBSTANTIAL IMPROVEMENT IS FOUND UNDER ARTICLE XIX | | | DEFINITIONS, SECTION 94-611. | | | SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF | | | REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO | | | A STRUCTURE, TAKING PLACE DURING THE LIFE OF A | | | STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR | | | EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE | | | STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE | | | THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START | | | OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF | | | DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE | | | OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, | | | "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN | | | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR | | | OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, | | | WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL | | | DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL | | | IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT | | | OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, | | | SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO | | | ENSURE SAFE LIVING CONDITIONS. | | | | | | 4D) SINCE SUBSTANTIAL IMPROVEMENT HAS BEEN MET WITH THE | | | RENOVATION PERMIT (01040625/ VALUE OF | | | $150,000.00)TO THIS BUILDING. $1,075,000 (APPLIED | | | PERMIT VALUE) + $150,000.00 = $ 1,225,000.00 WHICH IS | | | GREATER THAN $1,217,500.00 OR 50% OF THE STRUCTURE | | | SUBSTANTIAL IMPROVEMENT HAS BEEN MET. | | | | | | 4E) SINCE IS A COMMERCIAL BUILDING ( NONRESIDENTIAL) | | | FLOOD PROOFING IS A OPTION TO MEET CODE COMPLIANCE. | | | WEST PALM BEACH MUNI CODE: | | | SEC. 94-546 (B) AREAS OF SPECIAL FLOOD HAZARD WITH BASE | | | FLOOD ELEVATION PROVIDED. (2) NONRESIDENTIAL | | | CONSTRUCTION. | | | ALL NEW CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY | | | COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL | | | STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING | | | BASEMENT, ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE | | | BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT | | | UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO | | | THAT BELOW SIX INCHES ABOVE THE FLOOD BASE LEVEL THE | | | STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY | | | IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL | | | COMPONENTS HAVING THE CAPABILITY OF RESISTING | | | HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF | | | BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR | | | ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS | | | SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE | | | PROVIDED TO THE CITY ENGINEER. | | | | | | 1ST ROUND COMMENT. 4) PLEASE NOTE THIS PROPERTY IS | | | LOCATED WITHIN AN AH FLOOD ZONE. FBC BUILDING 1612 AND | | | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. | | | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD | | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | | ADDITIONAL 6 INCHES OF ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5)SEMI-COMPLIED. THE SUBMITTED WIND ENGINEERING FOR THE | | | RTU'S AND CURBS IS INCOMPLETE. | | | A) THE SUBMITTAL IS ONLY FOR THE LENNOX UNIT RTU-9. THE | | | CARRIER UNIT RTU-7 WAS NOT INCLUDED. | | | B) THE LENNOX SUBMITTAL DOES NOT INCLUDE THE CURB AND | | | CURB ATTACHMENT TO THE STRUTURE. | | | C) THE SUBMITTAL WAS A COPY AND DID NOT HAVE AN | | | ORIGINAL SIGNATURE AND SEAL. FL ADMIN CODE 61G15-23.002 | | | ENGINEERS. | | | | | | COMMENT 1ST ROUND REVIEW, SHEET M1.1 SHOWS A NEW ROOF | | | TOP RTU # 9 PLEASE PROVIDE ENGINEERING FOR THE FRAMING | | | AROUND THE NEW ROOF TOP HOLE FOR THIS UNIT. ALSO | | | PROVIDE THE MANUFACTURERS INSTALLATION INSTRUCTIONS, IF | | | A PRODUCT APPROVAL PLEASE PROVIDE AS WELL AS THE TIE | | | DOWN OF THE RTU TO THE CURB. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ ROOF TOP | | | FANS | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | | DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM | | | THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014 | | | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS? | | | | | | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 6) COMPLIED. 107.3.4.1 THOSE PRODUCTS WHICH ARE | | | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 7) COMPLIED. NOT REQUIRED. FBC-B 1509.6 MECHANICAL | | | EQUIPMENT SCREENS. | | | | | | 8) COMPLIED. 2014 FBC-ACCESSIBILITY CODE904.5.2 TRAY | | | SLIDES. | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-03-21 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-03-18 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2016-03-21 06:40:40 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16030222 | | | ADD: 5400 EAST AVENUE | | | CONT: STUART & SHELBY DEVELOPMENT | | | TEL: 561-637-7902 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. MARCH 18/ 2016 | | | ACTION: DENIED | | | | | | 1) SHEET A9 INDICATES THE WINDOW AND EXTERIOR DOOR | | | POSITIVE & NEGATIVE PRESSURES. PLEASE PROVIDE WHERE THE | | | WIND DESIGN CRITERIA CAN BE LOCATED IN THE PLANS. | | | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 | | | | | | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. | | | | | | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4 & ASCE 7-10 | | | | | | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.7.2. | | | ASCE 7-10. | | | | | | 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE & | | | NEGATIVE TABLE 1609.2(2). | | | | | | 2) SHEET A7 SHOWS A WHITE BAHAMA STYLE SHUTTER, PLEASE | | | PROVIDE IF THIS RIGID AWNING WILL STAY AS POSITIONED OR | | | REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING IS | | | UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN THE | | | CLOSED POSITION SHALL ALSO COMPLY WITH CHAPTER 16 AND | | | SHALL BE IMPACT RESISTANT IN ACCORDANCE WITH SECTION | | | 1609.1.2 FBC-B. | | | | | | 3) SHEET A7 & 8 BOTH SHOW DETAILS OF CULTURED STONE | | | VENEER 2008 MIST DRYSTACK LEDGESTONE OWENS CORNING. | | | PLEASE SUBMIT THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS. THE PLANS DO NOT INDICATE IF THE STONE IS | | | ATTACHED OR ADHERED. PLEASE PROVIDE COMPLIANCE WITH ONE | | | OF THESE CODE SECTIONS: | | | 2014 FBC-B 1405.6. ANCHORED MASONRY VENEERS | | | 1405.7 STONE VENEERS | | | 1405.10 ADHERED MASONRY VENEERS | | | 1405.10.2 EXTERIOR ADHERED MASONRY VENEERS/ PORCELAIN | | | TILE. | | | | | | 4) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN AN AH | | | FLOOD ZONE. FBC BUILDING 1612 AND CITY OF WPB CODE OF | | | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN | | | "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY | | | REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF | | | ELEVATION. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE | | | REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES | | | REQUIRED: | | | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE | | | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR | | | HEIGHT. | | | (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE | | | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR | | | ATTENDANTS | | | A/C PADS OR OTHER SLABS FOR GENERATORS | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31/2015 | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. | | | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE | | | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 5) SHEET M1.1 SHOWS A NEW ROOF TOP RTU # 9 PLEASE | | | PROVIDE ENGINEERING FOR THE FRAMING AROUND THE NEW ROOF | | | TOP HOLE FOR THIS UNIT. ALSO PROVIDE THE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS, IF A PRODUCT APPROVAL PLEASE | | | PROVIDE AS WELL AS THE TIE DOWN OF THE RTU TO THE CURB. | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ ROOF TOP | | | FANS | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | | DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM | | | THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014 | | | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS? | | | | | | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 6) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA | | | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 7) IF ZONING REQUIRES A MECHANICAL EQUIPMENT SCREEN FOR | | | THE NEW ROOF TOP EQUIPMENT THEN SHOW COMPLIANCE WITH: | | | FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS. | | | MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF | | | THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN | | | ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE | | | BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER | | | THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS | | | SHALL NOT BE REQUIRED TO COMPLY WITH THE | | | FIRE-RESISTANCE RATING REQUIREMENTS. | | | | | | SHEET A4 SHOWS NEW TRAY SLIDES BY OTHERS, PLEASE SHOW | | | COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE: | | | | | | 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE | | | 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-06-13 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-06-13 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-06-13 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-03-14 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-14 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2016-03-14 08:43:12 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. ADD A NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING | | | LABELS REQUIRED. A NOTE WILL SUFFICE. | | | 2. ON SHEET E1.1 UPDATE ELECTRICAL NOTES TO INDICATE | | | NEC 2011 NOT 2005 CODE EDITION. | | | 3. PROVIDE A NOTE TO INDICATE SEPARATE PERMITS REQUIRED | | | FOR ANY LOW VOLTAGE SYSTEMS | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-06-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-06-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-06-02 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-03-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-03-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-03-09 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2016-03-11 11:56:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. SHEET A 5 - THE EXIT SEPARATION DISTANCE DOES NOT | | | APPEAR TO COMPLY WTH NFPA 101, CHAPTER 7, MEANS OF | | | EGRESS, PER NFPA 101, CHAPTER 7, 7.5.1.3.2, WHERE TWO | | | EXITS, EXIT ACCESSES, OR EXIT DISCHARGES ARE REQUIRED, | | | THEY SHALL BE LOCATED AT A DISTANCE FROM ONE ANOTHER | | | NOT LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM | | | OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO | | | BE SERVED, MEASURED IN A STRAIGHT LINE BETWEEN THE | | | NEAREST EDGE OF THE EXITS, EXIT ACCESSES, OR EXIT | | | DISCHARGES. | | | | | | PLEASE PROVIDE COMPLIANCE WITH THIS REQUIRMENT. | | | | | | 2. SHEET A 4, A 9, A 14 - ALL DOOR HARWARE AND LOCKS IN | | | THE EXIT PATH OF TRAVEL SHALL COMPLY WITH NFPA 101, | | | CHAPTER 7 MEANS OF EGRESS, | | | | | | D61 - NO EXIT DOOR HARDWARE INDICATED | | | | | | D10 - NO EXIT DOOR HARDWARE INDICATED | | | | | | D 38 - NO EXIT DOOR HARDWARE INDICATED | | | | | | D 9 - NO EXIT DOOR HARDWARE INDICATED, NO FIRE RATING | | | INDICATED. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2017-07-06 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-06 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-06 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2017-04-25 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2017-01-06 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2017-01-04 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2017-04-25 10:34:21 | COMPLETED STEP LEFT INCOMPLETE ON 1/6/17 | | 2017-01-05 11:30:04 | RESUB ROUTED TO LLOUIE VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-12-01 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-11-21 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2016-11-22 13:26:11 | RESUB ROUTED TO JWITMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-10-31 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-10-26 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2016-10-27 14:59:18 | RESUB ROUTED TO JWITMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-09-07 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-09-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-08-19 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-06-16 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-27 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-03-23 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-03-04 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2016-03-14 08:43:31 | 3/14 TO C02 | | 2016-03-04 12:54:58 | C02 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2016-03-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-03-18 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-03-18 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2016-08-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-31 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-31 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2016-08-31 10:02:43 | MECHANICAL PROVISO | | | 8/31/16 | | | | | | 1) SITE SPECIFIC SIGNED AND SEALED WIND LOAD | | | ENGINEERING IS REQUIRED FOR INSTALLATION OF THE NEW | | | RTU'S AND CURBS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-06-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-06-03 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-06-02 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2016-06-03 10:32:48 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030222 | | | 6/3/16 | | | | | | 1) PROVIDE THE MODEL NUMBER AND EQUIPMENT SCHEDULE FOR | | | THE NEW ERV IN THE DINING ROOM. | | | | | | 2) SHEETS M1.1 & M3.1: THE SUPPLY CFMS FOR RTU'S 4 & 7 | | | DO NOT MATCH. | | | | | | 3) M1.1 & M2.1: THE EXHAUST RATE FOR THE FANS IN THE | | | MEN'S RRM 12 & WOMEN'S RRM 13 MUST BE 70 CFM'S EACH PER | | | TABLE 403.3. THESE DO NOT APPEAR TO BE PRIVATE TOILET | | | ROOMS. | | | | | | 4) THE DESIGN PROFESSIONAL MUST COMPLETE HIS PORTION OF | | | THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE 9 OF THE | | | ENERGY GAUGE IECC COMPLIANCE SUBMITTAL. | | | | | | 5) THE SUBMITTED WIND LOAD ENGINEERING FOR THE RTU'S | | | AND CURBS IS IN COMPLETE: A) THE SUBMITTAL IS ONLY FOR | | | THE LENNOX UNIT- RTU-9, THE CARRIER UNIT- RTU-7 WAS NOT | | | INCLUDED. B) THE LENNOX SUBMITTAL DOES NOT INCLUDE THE | | | CURB AND CURB ATTACHMENT TO THE STRUCTURE. C) THE | | | SUBMITTAL WAS A COPY AND DID NOT HAVE AN ORIGINAL | | | SIGNATURE AND SEAL FROM THE PE AS REQUIRED BY FLORIDA | | | STATUTE AND FAC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-03-17 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-03-17 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2016-03-17 08:46:25 | 1ST REVIEW: | | | CODES: FBC 2014 MECHANICAL, EXISTING BUILDING, ENERGY | | | CONSERVATION | | | PERMIT #16030222 | | | 3/17/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND | | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS | | | AND SPACES IN ACCORDANCE WITH TABLE 403.3 MECHANICAL. | | | PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE | | | REQUIRED AND PROVIDED CFM'S OF O/A. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR | | | RTU-9 IN ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) THE PROPOSED PROJECT IS CLASSIFIED AS A "RENOVATION" | | | IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY | | | CONSERVATION, AND THEREFORE REQUIRES DOCUMENTATION OF | | | ENERGY EFFICIENCY COMPLIANCE- SEE SECTIONS C101.4.3, | | | C101.5.1, AND C401.2. PLEASE SHOW COMPLIANCE USING | | | EITHER THE PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE | | | PATHS. | | | | | | 4) PROVIDE MOTORIZED DAMPERS FOR MTHE O/A TO EACH RTU | | | THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS AND | | | SPACES ARE NOT IN USE. | | | | | | 5) REFER TO SECTION C403.2.5.1 AND PROVIDE DEMAND | | | CONTROLLED VENTILATION IN ROOMS AND SPACES WHERE | | | APPLICABLE. | | | | | | 6) PROVIDE A DUCT SMOKE DETECTOR SYMBOL AT THE RETURN | | | AIR PLENUM, OF RTU-9 AND ALL OTHER SYSTEMS REQUIRING | | | DETECTORS- SECTION 606.2.1. PLEASE INDICATE A SEQUENCE | | | OF OPERATION FOR THE DETECTORS- CLARIFY IF ALL SYSTEMS | | | WILL BE LINKED TOGETHER TO SHUT DOWN UPON | | | ACTIVATIVATION OF ANY ONE DETECTOR. | | | | | | 7) PROVIDE WIND LOAD ENGINEERING FOR TIE-DOWN OF THE | | | NEW RTU-9 IN ACCORDANCE WITH SECTION 301.15 FBC-14 | | | MECHANICAL. PROVIDE THE WIND LOAD DESIGN CRITERIA ON | | | THE PLAN AND SECTION CUTS OF THE UNIT AND CURB SHOWING | | | THE STRUCTURAL DETAILS- PLEASE NOTE THAT THE DETAIL ON | | | M2.1 IS INCOMPLETE. | | | | | | 8) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE NEW | | | RTU-9 AND CLEARANCE DISTANCE MEASUREMENTS FROM THE AIR | | | INTAKE TO MECHANICAL AND GRAVITY EXHAUST OUTLETS, AND | | | FROM THE RTU TO THE ROOF EDGES. | | | | | | 9) PROVIDE A CONDENSATE DISPOSAL FOR THE RTU-9 | | | INDICATING PIPING DETAILS AND DISCHARGE LOCATION. | | | PLEASE NOTE THAT NO DETAILS ARE SHOWN ON THE PLUMBING | | | PAGES. | | | | | | 10) PROVIDE THE MAIN DUCT SIZES ON THE PLANS FOR RTU-4, | | | AND SEE SECTION 601.5: PLEASE NOTE THE 10" TRANSFER MAY | | | BE UNDERSIZED. | | | | | | 11) PLEASE CLARIFY IF THE TOILOET ROOM EXHAUST FANS AND | | | DUCTS ARE BEING REPLACED AND PROVIDE DETAILS AND | | | EQUIPMENT SCHEDULES IF APPLICABLE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-06-13 |
|
|
Cont ID |
|
| Sent By |
gearl |
Date |
2016-06-13 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
gearl |
Date |
2016-06-13 |
Time |
13:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-17 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-14 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2016-03-16 14:57:36 | 1) SHT. A-2 - TOILET ROOM CALCULATIONS - THE TABLE | | | REFERENCED IS INCORRECT. THERE IS NO TABLE 400.1 IN THE | | | 2014 FLORIDA PLUMBING CODE. THE CORRECT TABLE IS 403.1. | | | PLEASE CORRECT. | | | 2) CLEARLY SHOW THE LOCATION OF THE REQUIRED SERVICE | | | SINKS FOR THE INSTITUTIONAL AND ASSEMBLY OCCUPANCIES AS | | | REQUIRED BY 2014 FPC TABLE 403.1. | | | 3) A MINIMUM OF ONE NEW WASHER AND ONE NEW DRYER IN THE | | | EXISTING LAUNDRY AREA SHALL COMPLY WITH THE 2014 FBC | | | ACCESS. SEC.611.1 - 611.4. | | | 4) SHT. A-11, DETAIL #2 - SHOW THE REQUIRED 30 INCH | | | WIDE MINIMUM BY 60 INCH LONG MINIMUM CLEAR FLOOR SPACE | | | ADJACENT TO THE OPEN FACE OF THE ACCESSIBLE SHOWER. | | | 5) GRAB BARS IN THE ACCESSIBLE ROLL-IN SHOWER WITH THE | | | SEAT SHALL BE LOCATE DIN ACCORDANCE WITH THE 2014 FAC | | | SEC.608.3.2. | | | 6) THE CONTROLS IN THE ACCESSIBLE ROLL-IN SHOWER WITH | | | THE SEAT SHALL COMPLY WITH THE FAC SEC.608.5.2. | | | 7) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN ACCORDANCE | | | WITH THE FAC SEC.608.6. | | | 8) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH | | | THE FAC SEC. 610.3, 610.3.1. | | | 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE PER FAC SEC.609.4. | | | 10) SHT. A-12 - DETAIL #1 - SHOW THE INSIDE CLEAR | | | DIMENSIONS (L X W) OF THE ACCESSIBLE TOILET ROOM.THE | | | MINIMUM WIDTH SHALL BE 85 INCHES. 2014 FAC SEC. 604.3, | | | 606. | | | 11) SHT.A-13 - DETAIL #5 - THE THRESHOLD AT THE | | | ACCESSIBLE SHOWER SHALL BE A 1/2 INCH MAXIMUM PER 2014 | | | FAC SEC.608.7. | | | 12) SHT. P1.1 - THE PRINTING ON THE PLAN FOR THE WATER | | | AND SANITARY SIZES & NOTES IS SO SMALL IT IS ILLEGIBLE. | | | SUBMIT A CLEAR AND LEGIBLE PLAN. FBC 107.2.1. | | | 13) SHT.P2.1 - DETAIL #10 SHOWS WATER HEATERS BUT IT IS | | | LABELED AS "BACKFLOW PREVENTER ASSEMBLY."PLEASE | | | CORRECT. | | | 14) SHT. P2.1 - THE WATER HEATERS ARE SHOWN AS GAS. | | | SUBMIT A COMPLETE GAS DRAWING COMPLYING WITH THE | | | FOLLOWING ITEMS: | | | | | | 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. | | | G2413. | | | | | | 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER (IF | | | APPLICABLE) OF THE CORRUGATED STAINLESS STEEL TUBING | | | FOR EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | | | 3.) TYPE OF GAS (LP OR NATURAL). | | | | | | 4.) BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014 | | | FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 | | | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. | | | | | | 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN | | | THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS | | | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. | | | | | | 6.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | | 2407. | | | | | | 7.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | | SEC. G2413.2. . | | | | | | 8.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE | | | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS | | | SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426. | | | | | | 9.) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. | | | | | | 10.) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | | TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF | | | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT | | | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL | | | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND | | | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF | | | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11.) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | | ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF | | | REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE | | | ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, | | | THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170 | | | MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. | | | | | | 15) THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE | | | AND BE LISTED ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA"S (USC) LIST OF APPROVED DEVICES. | | | 16) A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW | | | PREVENTION DEVICE.A SEPARATE PERMIT APPLICATION SHALL | | | BE SUBMITTED WITH TWO COPIES OF THE SPECIFICATIONS FOR | | | THE DEVICE. | | | 17) A CLEANOUT IS REQUIRED IN EACH WASTE OR SOIL STACK | | | ( EXCEPT THE LAVATORY STACKS ) PER FPC SEC. 708.3.4. | | | 18) SHT. P3.1 - THE WATER CLOSETS IN THE MEN'S BATH #4 | | | & #5 ARE NOT VENTED. AS DRAWN, THEY ARE BEING WET | | | VENTED AND CREATING A CODE VIOLATION OF SEC. 912.1 OF | | | THE FPC FOR THE NUMBER AND TYPE OF FIXTURES ON THE WET | | | VENT. INDIVIDUALLY VENTING THE TOILETS WILL SOLVE THIS | | | PROBLEM. | | | 19) SHT.P3.1 - BATH #3 - A VENT IS REQUIRED BETWEEN THE | | | WATER CLOSET AND THE SHOWER. 2014 FPC SEC.901.2 & | | | 901.2.1. | | | 20) SHT. P3.1 - THE 3 INCH VENT IN RESTROOM #9 IS SHOWN | | | AS A FLAT, DRY VENT AND IS NOT PERMITTED. THE VENT | | | SHALL CONNECT TO A HORIZONTAL DRAIN ABOVE THE | | | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3. | | | 21) SHT. P3.1 - SIZE ALL VENTS ON THE SANITARY RISER. | | | 22) THE WASHING MACHINE SHALL BE INSTALLED ON A 3" | | | STACK PER THE 2014 FPC SEC.406.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2017-07-06 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-07-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-07-06 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-07-06 13:32:17 | APPROVE PER AVANN, P&Z ADMINISTRATOR. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2017-01-06 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-01-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-01-06 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-01-06 13:33:25 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) REPEAT COMMENT FROM 6/6/16, 8/30/16 AND 12/1/16: | | | PER PLANNING AND ZONING'S MEETING WITH A REPRESENTATIVE | | | FROM THE FACILITY BACK ON APRIL 8, 2016, THE | | | REPRESENTATIVE WAS INFORMED THAT A UNITY OF TITLE IS | | | REQUIRED TO JOIN ALL THE PARCELS WITHIN THE COMPLEX. IT | | | SEEMS THAT THIS HAS NOT BEEN COMPLETED. PLEASE CONTACT | | | THE ENGINEERING SERVICES DEPARTMENT FOR INFORMATION ON | | | HOW TO PROCEED WITH AN APPLICATION FOR A UNITY OF | | | TITLE. PROVIDE EVIDENCE OF THE RECORDED UNITY OF TITLE | | | ONCE IT HAS BEEN COMPLETED BY THE ENGINEERING SERVICES | | | DEPARTMENT. THE ENGINEERING SERVICES DEPARTMENT CAN BE | | | REACHED AT (561) 494-1040 OR YOU CAN DOWNLOAD THE | | | APPLICATION AT: | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. | | | | | 2017-01-05 13:54:05 | ROUTED TO LINDA LOUIE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2016-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-12-01 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-12-01 15:55:05 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) REPEAT COMMENT FROM 3/22/16, 6/6/16 AND 8/30/16: | | | UPDATED SURVEY IS MISSING FROM THE PERMIT APPLICATION. | | | | | | 2.) REPEAT COMMENT FROM 6/6/16 AND 8/30/16: PER | | | PLANNING AND ZONING'S MEETING WITH A REPRESENTATIVE | | | FROM THE FACILITY BACK ON APRIL 8, 2016, THE | | | REPRESENTATIVE WAS INFORMED THAT A UNITY OF TITLE IS | | | REQUIRED TO JOIN ALL THE PARCELS WITHIN THE COMPLEX. IT | | | SEEMS THAT THIS HAS NOT BEEN COMPLETED. PLEASE CONTACT | | | THE ENGINEERING SERVICES DEPARTMENT FOR INFORMATION ON | | | HOW TO PROCEED WITH AN APPLICATION FOR A UNITY OF | | | TITLE. PROVIDE EVIDENCE OF THE RECORDED UNITY OF TITLE | | | ONCE IT HAS BEEN COMPLETED BY THE ENGINEERING SERVICES | | | DEPARTMENT. THE ENGINEERING SERVICES DEPARTMENT CAN BE | | | REACHED AT (561) 494-1040 OR YOU CAN DOWNLOAD THE | | | APPLICATION AT: | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. | | | | | | NOTES: | | | | | | SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED FOR | | | SIGNAGE. | | | | | 2016-11-30 13:45:43 | ROUTED TO LINDA LOUIE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2016-08-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2016-08-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-08-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-08-30 09:55:45 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) REPEAT COMMENT FROM 3/22/16 AND 6/6/16: UPDATED | | | SURVEY IS MISSING FROM THE PERMIT APPLICATION. [PER THE | | | RESPONSE LETTER TO STAFF'S COMMENTS, PREPARED BY PAUL | | | RICHARD BRAUTIGAN ON 5/24/16 AND 7/6/16, THE SURVEY | | | WILL BE PROVIDED BY THE OWNER/CONTRACTOR; HOWEVER, THE | | | SURVEY STILL SEEMS TO BE MISSING FROM THE BUILDING | | | PERMIT PACKET. | | | | | | 2.) REPEAT COMMENT FROM 6/6/16: PER PLANNING AND | | | ZONING'S MEETING WITH A REPRESENTATIVE FROM THE | | | FACILITY BACK ON APRIL 8, 2016, THE REPRESENTATIVE WAS | | | INFORMED THAT A UNITY OF TITLE IS REQUIRED TO JOIN ALL | | | THE PARCELS WITHIN THE COMPLEX. IT SEEMS THAT THIS HAS | | | NOT BEEN COMPLETED. PLEASE CONTACT THE ENGINEERING | | | SERVICES DEPARTMENT FOR INFORMATION ON HOW TO PROCEED | | | WITH AN APPLICATION FOR A UNITY OF TITLE. PROVIDE | | | EVIDENCE OF THE RECORDED UNITY OF TITLE ONCE IT HAS | | | BEEN COMPLETED BY THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING SERVICES DEPARTMENT CAN BE REACHED AT | | | (561) 494-1040 OR YOU CAN DOWNLOAD THE APPLICATION AT: | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATI ONS | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-06-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-06-03 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2016-06-06 11:21:46 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) REPEAT COMMENT FROM 3/22/16: UPDATED SURVEY IS | | | MISSING FROM THE PERMIT APPLICATION. [PER THE RESPONSE | | | LETTER TO STAFF'S COMMENTS, PREPARED BY PAUL RICHARD | | | BRAUTIGAN ON 5/24/16, THE SURVEY WAS "PROVIDED BY | | | OWNER/CONTRACTOR, AS REQUESTED," HOWEVER, THE SURVEY | | | CANNOT BE FOUND WITH THE PERMIT RESUBMITTAL.] | | | | | | 2.) INFORMATION ON THE NUMBER OF BEDS MUST BE CLEARLY | | | PROVIDED IN THE SITE PLAN FOR THE ENTIRE FACILITY. THE | | | NUMBER OF BEDS INDICATED IN THE SITE PLAN DOES NOT SEEM | | | TO REFLECT THE NUMBER OF BEDS APPROVED BY STAFF. | | | | | | 3.) REVISE SITE PLAN TO SHOW THE ENTIRE COMPLEX; AREA | | | OF THE SCOPE OF WORK/CHANGES SHOULD BE HIGHLIGHTED. | | | | | | 4.) PER PLANNING AND ZONING'S MEETING WITH A | | | REPRESENTATIVE FROM THE FACILITY BACK ON APRIL 8, 2016, | | | THE REPRESENTATIVE WAS INFORMED THAT A UNITY OF TITLE | | | IS REQUIRED TO JOIN ALL THE PARCELS WITHIN THE COMPLEX. | | | IT SEEMS THAT THIS HAS NOT BEEN ACHIEVED. PLEASE | | | CONTACT THE ENGINEERING SERVICES DEPARTMENT FOR | | | INFORMATION ON HOW TO PROCEED WITH AN APPLICATION FOR A | | | UNITY OF TITLE. PROVIDE EVIDENCE OF THE RECORDED UNITY | | | OF TITLE ONCE IT HAS BEEN COMPLETED BY THE ENGINEERING | | | SERVICES DEPARTMENT. THE ENGINEERING SERVICES | | | DEPARTMENT CAN BE REACHED AT (561) 494-1040 OR YOU CAN | | | DOWNLOAD THE APPLICATION AT: HTTP://WWW.WPB.ORG/DEPARTM | | | ENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATI | | | ONS | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-22 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2016-03-22 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2016-03-22 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2016-03-22 17:12:59 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON | | | THE PLANS WHERE APPLICABLE: | | | | | | 1.) THE PLANS INDICATE THERE WILL BE BEDS PROVIDED AT | | | 5400 EAST AVENUE. NO BEDS ARE PERMITTED IN THIS | | | BUILDING PER ZONING. | | | | | | 2.) ADDITIONAL INFORMATION HAS BEEN REQUESTED IN THE | | | PAST FOR THE TOTAL NUMBER OF BEDS IN ALL BUILDINGS AND | | | THE NUMBER OF BEDS ALLOCATED WITHIN EACH BUILDING. THIS | | | INFORMATION HAS YET TO BE PROVIDED TO PLANNING STAFF. | | | | | | 3.) UPDATED SURVEY OF THE PROPERTY IS MISSING FROM THE | | | PERMIT APPLICATION. | | | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | | IF THERE ARE QUESTIONS. | | | |
|
|
|