| 2016-03-08 13:34:47 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030163 |
| | ADD: 206 DYER RD. |
| | CONT: STORM ROOFING |
| | TEL: 561-689-0268 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 08/2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SHOW COMPLIANCE WITH: |
| | 2014 FBC-EXISTING BUILDING CODE 708.8 WHEN A ROOF |
| | COVERING ON AN EXISTING SITE-BUILT SINGLE FAMILY |
| | RESIDENTIAL STRUCTURE IS REMOVED AND REPLACED ON A |
| | BUILDING THAT IS LOCATED IN THE WIND-BORNE DEBRIS |
| | REGION AS DEFINED IN THE FLORIDA BUILDING CODE, |
| | BUILDING AND THAT HAS AN INSURED VALUE OF $300,000 OR |
| | MORE OR, IF THE BUILDING IS UNINSURED OR FOR WHICH |
| | DOCUMENTATION OF INSURED VALUE IS NOT PRESENTED, HAS A |
| | JUST VALUATION FOR THE STRUCTURE FOR PURPOSES OF AD |
| | VALOREM TAXATION OF $300,000 OR MORE: |
| | |
| | (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| | REQUIRED BY SECTION 708.8.1. |
| | |
| | (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| | SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN |
| | THE COST OF REROOFING. |
| | |
| | EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| | PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| | REQUIRED TO COMPLY WITH THIS SECTION. |
| | |
| | 708.8.1 ROOF-TO-WALL CONNECTIONS FOR SITE-BUILT SINGLE |
| | FAMILY RESIDENTIAL STRUCTURES. |
| | WHERE REQUIRED BY SECTION 708.8, THE INTERSECTION OF |
| | ROOF FRAMING WITH THE WALL BELOW SHALL PROVIDE |
| | SUFFICIENT RESISTANCE TO MEET THE UPLIFT LOADS |
| | SPECIFIED IN TABLE 708.8.1, EITHER BECAUSE OF EXISTING |
| | CONDITIONS OR THROUGH RETROFIT MEASURES. AS AN |
| | ALTERNATIVE TO AN ENGINEERED DESIGN, THE PRESCRIPTIVE |
| | RETROFIT SOLUTIONS PROVIDED IN SECTIONS 708.8.1.1 |
| | THROUGH 708.8.1.7 SHALL BE ACCEPTED AS MEETING THE |
| | MANDATED ROOF-TO-WALL RETROFIT REQUIREMENTS. |
| | EXCEPTIONS: |
| | |
| | 1. WHERE IT CAN BE DEMONSTRATED (BY CODE ADOPTION DATE |
| | DOCUMENTATION AND PERMIT ISSUANCE DATE) THAT |
| | ROOF-TO-WALL CONNECTIONS AND/OR ROOF-TO FOUNDATION |
| | CONTINUOUS LOAD PATH REQUIREMENTS WERE REQUIRED AT THE |
| | TIME OF ORIGINAL CONSTRUCTION. |
| | |
| | 2. ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED |
| | UNLESS EVALUATION AND INSTALLATION OF CONNECTIONS AT |
| | GABLE ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15 |
| | PERCENT OF THE COST OF ROOF REPLACEMENT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |