Plan Review Details - Permit 16030148
Plan Review Stops For Permit 16030148
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By cthroop Date 2016-03-18 Time 10:29 Rev Time 0.00
Received By cthroop Date 2016-03-18 Time 10:29 Sent To  
Notes
2016-03-18 10:33:571ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 INSUFFICIENT INFORMATION ON SUBMITTED PLANS. NO REVIEW
 PERFORMED AT THIS TIME . PLEASE RE-SUBMIT.
 PROVIDE DETAILED SCOPE OF WORK.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By vperez Date 2016-03-07 Time 14:06 Rev Time 0.00
Received By vperez Date 2016-03-07 Time 13:30 Sent To  
Notes
2016-03-07 14:06:39INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE SUBMIT PER FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA; SHOW THE ENTIRE SCOPE OF ELECTRICAL WORK THAT
 WILL BE ALTERED UNDER THIS PERMIT. NONE ARE SHOWN AT
 THIS TIME.
 2.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS OWNER BUILDER PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-18 Cont ID  
Sent By cthroop Date 2016-03-18 Time 10:29 Rev Time 0.00
Received By cthroop Date 2016-03-03 Time 12:45 Sent To  
Notes
2016-03-07 14:07:443/7 TO CAROLINE
2016-03-03 12:45:52PLUMB -$5000

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By tklarge Date 2016-03-07 Time 04:59 Rev Time 0.00
Received By tklarge Date 2016-03-07 Time 04:39 Sent To  
Notes
2016-03-07 04:51:461) THE SUBMITTED PLANS ARE MOSTLY DONE IN PENCIL AND
 ARE UNACCEPTABLE AS PENCIL CAN BE ERASED. SUBMIT TWO
 SETS OF PLANS IN AN UNERASABLE FORMAT. FBC 107.2.1.
 2) THE SUBMITTED PLANS DO NOT CLEARLY REFLECT THE
 ENTIRE SCOPE OF WORK TO BE DONE AND ARE LACKING THE
 MINIMUM REQUIRED INFORMATION.. REFER TO 2014 FBC SEC.
 107.3.5 - MINIMUM CRITERIA FOR PLAN REVIEW.
 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  