| 2016-03-11 07:34:02 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16030102 |
| | W. P. B. PERMIT: 15090236 |
| | ADD:2101 PALM BEACH LAKES (744343190020900) |
| | CONT: LM DEVELOPMENT GROUP |
| | TEL: ( 954)476-0800 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 11/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR HAS INCREASED THE SCOPE OF WORK FROM |
| | JUST A SHELL BUILDING WITH THE ADDITIONAL WORK INCLUDED |
| | MECHANICAL, PLUMBING AND ELECTRICAL. |
| | THE VALUE OF THE INCREASE IN THE SCOPE OF WORK IS |
| | DECLARED AS $10,000.00 DOLLORS. SHEET M1 SHOWS 5 ROOF |
| | TOP A/C UNITS ALONE, NOT COUNTING THE ADDITIONAL |
| | ELECTRICAL AND PLUMBING WORK AS WELL AS THE BUILDING |
| | CONTRACTORS WORK. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE M1 SHEET SHOWS 5 NEW ROOF TOP A/C UNITS A |
| | REVISION TO THE ORIGINAL PERMIT. ON THE SHELL BUILDING |
| | SHEET S-4 SHOWED THE TYPICAL ROOF OPENING FRAMING |
| | DETAIL, BUT THERE ARE NO CURB DETAILS OF HOW THE CURB |
| | WILL BE ANCHORED, NOR IS THERE DETAILS OF HOW THE A/C |
| | UNIT WAS TO BE ANCHORED TO THE CURB. |
| | PLEASE PROVIDE DETAILS SHOWING CODE COMPLIANCE WITH: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP |
| | CURBS. |
| | |
| | 2A) 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| | PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2B) IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A |
| | DELEGATE ENGINEER OR MECHANICAL ENGINEER THE ENGINEER |
| | OF RECORD WILL NEED TO REVIEW THE ENGINEERED DETAILS |
| | FOR CONFORMANCE WITH THEIR OVERALL DEDIGN FOR THE |
| | BUILDING. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A |
| | DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN |
| | H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED |
| | CALCULATIONS ARE COPIES NOT SIGNED AND SEALED |
| | ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES |
| | SUBMITTED NOT (3) ORIGINALS. |
| | |
| | 3) THIS BUILDING WAS DESIGNED AS A SHELL BUILDING |
| | EXEMPT FROM THE ENERGY CODE. WITH THE A/C ROOF TOP |
| | UNITS BEING ADDED TO THE SCOPE OF WORK, ELECTRICAL AND |
| | PLUMBING FOR THE HOOK UP OF THESE UNITS THE BUILDING NO |
| | LONGER QAULIFIES AS A SHELL BUILDING AND WILL NEED TO |
| | MEET THE REQUIREMENTS FOUND UNDER THE 2014 FBC-ENERGY |
| | CODE; |
| | 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR |
| | C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL |
| | TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE |
| | DESIGN BUILDING. |
| | |
| | NOTE ASHRAE 90 CALCS WERE SUBMITTEDBUTTHE MANDATORY |
| | REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO |
| | BECHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT |
| | BLANK!!!!!! |
| | |
| | 3B) NO LOAD CALS SUBMITTED.!!!!!!!! C403.2.1 |
| | CALCULATION OF HEATING AND COOLING LOADS. SUBMIT 3 SETS |
| | OF CALCS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |