| 2016-05-09 11:07:39 | 1) THE SUBMITTED PLANS STILL INCLUDE COPIES OF GAS |
| | SIZING TABLES FOR SCH. 40 METALLIC PIPE AND ALSO FOR |
| | CSST. THERE IS NO METALLIC PIPE OR CSST SHOWN ON THE |
| | PLANS. SUBMIT TWO COPIES OF A COMPLETE GAS LAYOUT |
| | SHOWING THE TYPES OF PIPE BEING INSTALLED AND WHERE. IF |
| | THE CSST IS NOT BEING INSTALLED, REMOVE THE SIZING |
| | TABLE FROM THE PACKAGE. FBC 107.2.1. |
| | 2) THE SUBMITTED PLANS HAVE SIZING TABLES FOR PE PIPE |
| | AND ALSO FOR PE TUBING. WHICH IS IT? SUBMIT COPIES OF |
| | THE CORRECT SIZING TABLES FOR THE CORRECT TYPE OF PIPE |
| | MATERIAL BEING INSTALLED. |
| | 3) FOUR DIFFERENT GAS SIZING TABLES FOR PE PIPE HAVE |
| | BEEN SUBMITTED FOR REVIEW AND THEY ARE ALL FOR AN INLET |
| | PRESSURE OF LESS THAN 2 PSI BUT THE PLANS SHOW AN INLET |
| | PRESSURE OF 2 PSI. CLARIFY. |
| | 4) SHOW THE TOTAL DEVELOPED LENGTH FROM EACH STEP DOWN |
| | REGULATOR TO THE APPLIANCE SERVED AND SHOW THE TYPE OF |
| | PIPE ON THE PLANS FROM THE STEP DOWN REGULATOR TO THE |
| | APPLIANCE. SUBMIT THE CORRECT SIZING TABLE FROM THE |
| | 2014 FUEL GAS CODE. FBC 107.2.1. |
| | 5) SOME OF THE SIZING TABLES SUBMITTED ARE STILL FROM |
| | AN OUTDATED EDITION OF THE FUEL GAS CODE.THE CODE IN |
| | EFFECT IS THE 2014 FLORIDA BUILDING CODE, FUEL GAS |
| | WHICH IS BASED ON THE 2012 ICC CODE, NOT THE |
| | 2009.SUBMIT COPIES OF THE CORRECT SIZING TABLES FROM |
| | THE CODE THAT IS CURRENTLY IN EFFECT. |
| | 6) REMOVE ALL DOCUMENTS THAT ARE NOT APPLICABLE TO THIS |
| | INSTALLATION. THIS SUBMITTAL IS TOO CONFUSING TO |
| | PERFORM A COMPREHENSIVE REVIEW. |
| | 7) THE WORK ORDER/INVOICE SHOWS 63 FEET OF PE PIPE TO |
| | BE INSTALLED AND ALSO 50 FEET. WHICH IS IT? CLARIFY. |
| | |