| 2016-04-21 07:54:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. APRIL 21/ 2016 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!! !!!!!!!!!!!!! CHAPTER 553.80(2)(B) |
| | FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL |
| | IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF |
| | PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED |
| | FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | PLEASE READ!!!!!!! WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED |
| | SHEETS & REPLACE ANY PAGES AS NECESSARY. OLD SHEETS |
| | LEFT IN PLANS. REVIEW FAILS. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 6 UNIT/ R2 / APARTMENT BUILDING |
| | |
| | 1) CORRECTED. 2ND REQUEST. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. . |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. |
| | |
| | 2) 2ND REQUEST. THE COVER-SHEET A-0.0 UNDER THE HEADING |
| | PROJECT DATA; |
| | |
| | 2A) 2ND REQUEST. UNDER THE WIND DESIGN THE PLANS ONLY |
| | LIST THE R2 OCCUPANCY NOT THE R3 SINGLE FAMILY UNIT. |
| | PLANS AND DESIGN CRITERIA NEED TO BE SPLIT INTO 2 |
| | PERMITS AND PACKAGES SO EACH BUILDING AND ASSOCIATED |
| | OCCUPANCY CAN BE REVIEWED UNDER THE APPROPRIATE CODE. |
| | 107,2,1,4, |
| | |
| | 2B) ) 2ND REQUEST. THE PROJECT DATA SHEET INDICATES |
| | THIS IS A LEVEL II ALTERATION. IT APPEARS MORE LIKE A |
| | LEVEL II LIMITED ALTERATION.2014 FBC-EXIST. BLDG. CODE |
| | 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK |
| | AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE |
| | BUILDING. THIS REVIEW WILL BE TREATED AS SUCH, PLEASE |
| | UPDATE PLANS. |
| | |
| | 2C) 2ND REQUEST. UNDER THE HEADING PROJECT DATA THERE |
| | ARE (2) CODES THAT ARE MISSING IN THE DESIGN CRITERIA, |
| | FOR THE COMMERCIAL 6 UNIT APARTMENT BUILDING THE 2014 |
| | FBC-BUILDING, AND FOR THE SINGLE FAMILY DWELLING UNIT |
| | THE 2014 FBC-RESIDENTIAL CODE, 2 SEPARATE AND DISTINCT |
| | CODES. THE RESIDENTIAL CODE DEALS STRICTLY WITH 1-2 |
| | FAMILY DWELLING UNITS!!!!!!!!!! SEE SCOPING AND TITLE |
| | REQUIREMENTS IN EACH CODE. 101.1 TITLE/ SCOPE 101.2.. |
| | |
| | 2D) COMPLIED. UNDER THE HEADING APARTMENT BUILDING |
| | SCOPE OF WORK THE PLANS INDICATE THIS IS A 6 STORY |
| | BUILDING. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2E)2ND REQUEST. THE PLANS DO NOT DECLARE IF THIS |
| | BUILDING IS FIRE SPRINKLERED OR NOT. IF FIRE |
| | SPRINKLERED WHAT TYPE OF FIRE SPRINKLER IS DESIGN? |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. |
| | |
| | 2F) COMPLIED |
| | |
| | 2G) COMPLIED.. |
| | |
| | 3) 2ND REQUEST. CODE SUMMARY. SHEET A-3.3 ALL INDICATE |
| | THE PLANS WERE DESIGNED TO THE 2014 FLORIDA BUILDING |
| | CODE. PLEASE NOTE THE 2014 FLORIDA BUILDING CODE IS FOR |
| | COMMERCIAL BUILDINGS (APARTMENT BUILDINGS / R2). THIS |
| | SHEET IS THE FLOOR PLAN FOR THE SINGLE FAMILY HOUSE |
| | (R3). THE CODE FOR THE SINGLE FAMILY HOUSE IS THE 2014 |
| | FBC-RESIDENTIAL CODE. |
| | |
| | |
| | SHEET A-3.1 / 1ST FLOOR PLAN OF THE 2 STORY R2 |
| | APARTMENT BUILDING. TITLE BLOCK INDICATES 1ST FLOOR |
| | ELECTRIC PLAN?????? THIS PLAN APPEARS TO BE THE |
| | ARCHITECTURAL PLAN. |
| | |
| | |
| | 3A) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLARED |
| | THIS BUILDING TYPE AS A I-B BUILDING TYPE OF |
| | CONSTRUCTION, SEE CODE SUMMARY TABLE 503 HEADING. |
| | PLEASE NOTE ALL TRUSSES AND ROOF SHEATHING HAD TO BE |
| | INSTALLED WITH FIRE RETARDANT TREATED PLYWOOD. ALL NEW |
| | FRAMING MEMBERS AND ROOF SHEATHING WILL NEED TO COMPLY |
| | WITH FBC-B 603.1.1.3. 1. FIRE-RETARDANT-TREATED WOOD |
| | SHALL BE PERMITTED IN: 1.3. ROOF CONSTRUCTION, |
| | INCLUDING GIRDERS, TRUSSES, FRAMING AND DECKING. |
| | |
| | 3B) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT |
| | OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT |
| | CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE |
| | 2014 FBC-EXISTING BUILDING CODE NOR THE 2014 |
| | FBC-BUILDING CODE. |
| | |
| | 3C) 2ND REQUEST. DETAIL 1/ A-4 OF SHEET A-3.1 |
| | REFERENCES THE SFBC ITEM # 79 SECT. 37B. PLEASE UPDATE |
| | PLANS TO THE CURRENT 2014 FBC-B AND CURRENT CODE |
| | SECTIONS FOR TENANT SEPARATION REQUIREMENTS FOR TENANT |
| | SEPARATION WALLS. 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING |
| | UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING |
| | UNITS IN THE SAME BUILDING AND WALLS SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 708. |
| | |
| | |
| | 3D) 2ND REQUEST. IN UNIT # 2 THE WINDOWS IN THE BEDROOM |
| | #1, BATHROOM & KITCHEN ARE NOT IDENTIFIED. NOR ARE THE |
| | WINDOWS IN THE WINDOW SCHEDULE D-G NOT IDENTIFIED AS TO |
| | SIZE AND TYPE OF WINDOW. THE WINDOW SCHEDULE DOES NOT |
| | EVEN IDENTIFY THERE IS A WINDOW TYPE H LOCATED ON THE |
| | PLANS. |
| | |
| | 3E) 2ND REQUEST. PLEASE PROVIDE WHAT THE SILL HEIGHT OF |
| | THE WINDOW IS LOCATED IN THE BATHROOMS, PLEASE SHOW |
| | COMPLIANCE WITH FBC-B 2406.4.5. |
| | |
| | 3F) 2ND REQUEST. THE PLANS DO NOT INDICATE A CUT |
| | SECTION THROUGH THE FLOOR/ CEILING ASSEMBLY OF THE 1ST |
| | FLOOR CEILING. |
| | THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2 |
| | HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS |
| | SHOWING THE ASSEMBLY. |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS |
| | (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | & CEILINGS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| | |
| | 3G) 2ND REQUEST. THE PLANS SHOW A HATCHED AREA WHERE |
| | THE CEILINGS ARE DROPPED TO 7 FEET ABOVE THE FINISH |
| | FLOOR. THE PLAN STILL SHOWS A HATCHED AREA FOR IN THE |
| | BATHROOM BUT THE PLANS INDICATE ALSO A 8 FOOT FLAT |
| | CEILING HEIGHT. DISCREPANCY IN PLANS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3H) COMPLIED. |
| | |
| | 3I) 2ND REQUEST. PLEASE NOTE THIS ARCHITECTURAL SHEET |
| | IS LABELED ELECTRICAL 1ST FLOOR PLAN. PLEASE CORRECT |
| | AND UPDATE THIS SHEET. |
| | |
| | 3K) SHEET 3.5 THIS SHEET LIST THE SINGLE FAMILY HOUSE |
| | AS A R1 OCCUPANCY. 2014 FBC-B 310.5. |
| | |
| | 4A) 2ND REQUEST. SHEET A-3.2 2ND STORY FLOOR PLAN OF |
| | THE R2 APARTMENT BUILDING. HAS THE SAME ISSUES AS THE |
| | 1ST FLOOR LAYOUT. SEE COMMENTS 3D-3H. |
| | |
| | 4B) 2ND FLOOR. SHEET A3.2 THE 2ND FLOOR PORCH THE |
| | WINDOWS IN UNIT # 5 BEDROOM # 5 & THE LIVING ROOM ARE |
| | NOT IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. NOTE THESE WINDOWS WILL HAVE TO BE SAFETY |
| | WINDOWS AS WELL LOCATED IN A HAZARDOUS LOCATION. |
| | 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS. |
| | THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH |
| | 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| | LOCATIONS REQUIRING SAFETY GLAZING MATERIALS. |
| | |
| | 5) 2ND REQUEST. THE 2ND STORY FLOOR SYSTEM DOES NOT |
| | PROVIDE HOW COMPLIANCE WITH STRUCTURE BORNE SOUND WILL |
| | BE ACHIEVED, SHOW COMPLIANCE WITH: |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 5C) 2ND FLOOR. FLAME SPREAD- FBC-B 2014 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 |
| | 720.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | 6) 2ND REQUEST, PLEASE PROVIDE COMPLIANCE WITH: 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | 7) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. JUNE 02/ 2016 |
| | ACTION: DENIED |
| | |
| | HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE |
| | |
| | PLEASE READ!!!!!!!!!!!! WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED |
| | SHEETS & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) SHEET A3.3 |
| | 1A) 2ND REQUEST. IT APPEARS THE WIDTH AND HEIGHT |
| | DIMENSIONS OF THE WINDOW WERE REVERSED COMPARED TO THAT |
| | OF THE R2 APARTMENT BUILDING. 2014 FBC-R 310.1.1-3. |
| | |
| | 1B) 2ND REQUEST. PLEASE SHOW WHAT THE SILL HEIGHT WILL |
| | BE FOR THE WINDOWS WITHIN BOTH BATHROOMS AND COMPLIANCE |
| | WITH |
| | R308.4.5. |
| | |
| | 1C) 2ND REQUEST. SHEET S-2.3SF THE DEMO PLAN THERE ARE |
| | NO WALLS BEING DEMO-ED BETWEEN THE LIVING ROOM AND THE |
| | DINING ROOM. SHEET A3.3 IT IS NOT CLEAR IF A NEW WALL |
| | IS TO BE BUILT BETWEEN THESE ROOMS OR IF A HEADER IS |
| | BEING INSTALLED. NOTE THIS WILL BLOCK OFF ACCESS TO THE |
| | REMAINDER OF THE RESIDENCE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1D) 2ND REQUEST. THE FRONT AND REAR DOORS ARE BEING |
| | REPLACED BUT THE WIDTH OF THE DOOR IS UNKNOWN IN THE |
| | DOOR SCHEDULE. PLEASE SHOW COMPLIANCE WITH R3.11.2. |
| | |
| | 1E) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT |
| | OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT |
| | CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE |
| | 2014 FBC-EXISTING BUILDING CODE NOR THE 2014 FLORIDA |
| | RESIDENTIAL CODE. PLEASE NOTE ALL CODE REFERENCES, |
| | TABLE 503, TABLE 602 AND CHAPTER 7 ARE ALL REFERENCES |
| | TO THE FBC-BUILDING THE COMMERCIAL CODE. THIS IS A |
| | STAND ALONE SINGLE FAMILY DWELLING WHICH SHOULD BE |
| | REVIEWED UNDER THE 2014 FBC-RESIDENTIAL CODE. |
| | |
| | 2) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH: 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | 3) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) 2ND REQUEST, WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |