Plan Review Details - Permit 16030064
Plan Review Stops For Permit 16030064
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-09-13 Cont ID  
Sent By jwitmer Date 2016-09-13 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2016-09-13 Time 07:45 Sent To  
Notes
2016-09-13 11:37:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: TUES. SEPT. 09/13/2016
 ACTION: BUILDING PROVISO
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1) SHEET A3.1 & A3.2 SHOWS A WINDOW SCHEDULE, IN EACH
 BEDROOM THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE
 EGRESS REQUIREMENTS, SEE THE MIDDLE APARTMENTS 2 & 5
 BEDROOM # 2 IN EACH. THE WINDOW SCHEDULE SHOWS WINDOW
 STYLE (H) SINGLE HUNG WINDOW. THE OPENING SIZE IS 6-0X
 4-2 IN THE ELEVATIONS THE 6 FOOT DIMENSION IS A
 HORIZONTAL MEASUREMENT AND MULLION BETWEEN THE 2
 WINDOWS. WINDOWS MUST MEET THE REQUIREMENTS OF THE 2014
 FBC-B 1029 EMERGENCY ESCAPE & RESCUE.
  
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL. 107.3.4.2.
 CONTRACTOR TO SUBMIT TESTING REPORTS TO THE DESIGNER OF
 RECORD FOR REVIEW BEFORE SUBMITTING TO THE BUILDING
 DEPARTMENT.
  
 PROVIDE FLOOR ASSEMBLY TYPE WITH FLOOR INSULATION WHERE
 EITHER, TILE, VINYL TILE OR LAMINATED WOODS OCCUR ON
 THE 2ND FLOOR.
 (FBC-B 2014) FOR TILE, STONE, MARBLE AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 3) BUILDING PROVISO: DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-08-23 Cont ID  
Sent By jwitmer Date 2016-08-23 Time 13:40 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-08-23 13:40:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: 06/02/2016/ 07/12/2016 (OLD VOIDED SHEETS
 REMOVED)
 ACTION: DENIED
  
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 NOTICE: 1 SET OF PLANS IS MISSING SHEET A-2.1, THERE
 ARE (2) A-2.2 SHEETS IN THIS PLAN.
  
 1-2) CORRECTED.
  
 3A-B) COMPLIED.
  
 3C) 4TH REQUEST . NO NEW SHEETS. PLEASE NOTE THE
 RESPONSE INDICATES THE DETAIL HAS BEEN EXTENDED TO THE
 UNDERSIDE OF THE SHEATHING. DETAIL 1/A-4 SHEET A-3.1.
 2014 FBC-B SECTIONS 420.2 & 708.4 FOR TENANT SEPARATION
 WALL REQUIREMENTS. NOTE THE PLAN SHOWS THE WALL FIRE
 RATING STOPPING AT THE CEILING LINE, NOT CONTINUOUS IN
 THE FLOOR JOIST. THE PLANS ARE SILENT ABOUT THE 2ND
 FLOOR ABOVE THE CEILING LINE.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IN COMBUSTIBLE
 CONSTRUCTION WHERE THE FIRE PARTITIONS ARE NOT REQUIRED
 TO BE CONTINUOUS TO THE SHEATHING, DECK OR SLAB, THE
 SPACE BETWEEN THE CEILING AND THE SHEATHING, DECK OR
 SLAB ABOVE SHALL BE FIREBLOCKED OR DRAFT STOPPED IN
 ACCORDANCE WITH SECTIONS 718.2 AND 718.3 AT THE
 PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING
 TENANT SPACES IN COVERED AND OPEN MALL BUILDINGS, WALLS
 SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING
 UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB,
 IIIB AND VB CONSTRUCTION.
  
 3D) 4TH REVIEW/ REQUEST. THE RESPONSE INDICATES WINDOWS
 C & D ARE MARKED AS CASEMENT WINDOWS. PLEASE NOTE IN
 THE WINDOW SCHEDULE ALL WINDOWS ARE ALL SINGLE HUNG
 WINDOWS, SAME SHEET RED LINED DRAWINGS FROM BEFORE!!!
  
 SHEET A3.1 SHOWS A WINDOW SCHEDULE, IN EACH BEDROOM
 THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE EGRESS
 REQUIREMENTS OF:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 3E) COMPLIED.
  
 3F) 4TH REVIEW/ REQUEST. THE RESPONSE INDICATES A NEW
 SHEET A-5.1.1 WAS ADDED. NOTE IN EITHER SET OF PLANS.
 THE PLANS DO NOT INDICATE A CUT SECTION THROUGH THE
 FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G-K) COMPLIED.
  
 4A) COMPLIED.
  
 4B) 4TH REVIEW/ REQUEST. SHEET A3.2 THE 2ND FLOOR PORCH
 THE WINDOWS IN UNIT # 5 BEDROOM # 5 & THE LIVING ROOM
 ARE NOT IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. NOTE THESE WINDOWS WILL HAVE TO BE SAFETY
 WINDOWS AS WELL LOCATED IN A HAZARDOUS LOCATION. NOTE
 THIS SAME SITUATION OCCURS ON THE 1ST FLOOR. HAZARDOUS
 LOCATION A WALKABLE PATH ADJACENT TO THE EXTERIOR OF
 THE WINDOW.
 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS.
 THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH
 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS.
  
 5) BUILDING PROVISO: DEFERRED SUBMITTAL. 107.3.4.2.
 CONTRACTOR TO SUBMIT TESTING REPORTS TO THE DESIGNER OF
 RECORD FOR REVIEW BEFORE SUBMITTING TO THE BUILDING
 DEPARTMENT.
  
 PROVIDE FLOOR ASSEMBLY TYPE WITH FLOOR INSULATION WHERE
 EITHER, TILE, VINYL TILE OR LAMINATED WOODS OCCUR ON
 THE 2ND FLOOR.
 (FBC-B 2014) FOR TILE, STONE, MARBLE AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) BUILDING PROVISO: DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 4TH REVIEW/ REQUEST. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060021
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. AUG. 23/ 2016
 ACTION:
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 1) 4TH REVIEW/ REQUEST. PLEASE NOTE THE MINIMUM WINDOW
 SIZE FOR A SINGLE HUNG WINDOW IS:
 1ST FLOOR 37X59 5.33 SQ. FT.
 2ND FLOOR 37X63 5.78 SQ. FT.
 AT LEAST ONE WINDOW IN EACH BEDROOM SHALL COMPLY WITH:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
  
 2)BUILDING PROVISO: DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTAL 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-02 Cont ID  
Sent By jwitmer Date 2016-06-02 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2016-06-02 Time 13:51 Sent To  
Notes
2016-06-02 14:18:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: 06/02/2016/ 07/12/2016 (OLD VOIDED SHEETS
 REMOVED)
 ACTION: DENIED
  
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1-2) CORRECTED.
  
 3A-B) COMPLIED.
  
 3C) 2014 FBC-B SECTIONS 420.2 & 708.4 FOR
 TENANTSEPERATION WALL REQUIREMENTS. NOTE THE PLAN SHOWS
 THE WALL FIRE RATING STOPPING AT THE CEILING LINE, NOT
 CONTINIOUS IN THE FLOOR JOIST. THE PLANS ARE SILENT
 ABOUT THE 2ND FLOOR ABOVE THE CEILING LINE.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IN COMBUSTIBLE
 CONSTRUCTION WHERE THE FIRE PARTITIONS ARE NOT REQUIRED
 TO BE CONTINUOUS TO THE SHEATHING, DECK OR SLAB, THE
 SPACE BETWEEN THE CEILING AND THE SHEATHING, DECK OR
 SLAB ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN
 ACCORDANCE WITH SECTIONS 718.2 AND 718.3 AT THE
 PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING
 TENANT SPACES IN COVERED AND OPEN MALL BUILDINGS, WALLS
 SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING
 UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB,
 IIIB AND VB CONSTRUCTION.
  
 3D) SHEET A3.1 SHOWS A WINDOW SCHEDULE, IN EACH BEDROOM
 THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE EGRESS
 REQUIREMENTS OF:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE
 FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 3E) COMPLIED.
  
 3F) . THE PLANS DO NOT INDICATE A CUT SECTION THROUGH
 THE FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G-K) COMPLIED.
  
 4A) COMPLIED.
  
 4B) SHEET A3.2 THE 2ND FLOOR PORCH THE WINDOWS IN UNIT
 # 5 BEDROOM # 5 & THE LIVING ROOM ARE NOT IDENTIFIED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NOTE
 THESE WINDOWS WILL HAVE TO BE SAFETY WINDOWS AS WELL
 LOCATED IN A HAZARDOUS LOCATION. NOTE THIS SAME
 SITUATION OCCURS ON THE 1ST FLOOR. HAZARDOUS LOCATION A
 WALKABLE PATH ADJACENT TO THE EXTERIOR OF THE WINDOW.
 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS.
 THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH
 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS.
  
 5) BUILDING PROVISO: PROVIDE FLOOR ASSEMBLY TYPE WITH
 FLOOR INSULATION WHERE EITHER, TILE, VYNAL TILE OR
 LAMINATED WOODS OCCUR ON THE 2ND FLOOR.
 (FBC-B 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) DEFERRED SUBMITTALS: 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 02/ 2016
 ACTION:
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 1) AT LEAST ONE WINDOW IN EACH BEDROOM SHALL COMPLY
 WITH:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE
 FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
  
 2) DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTAL 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 07:00 Sent To  
Notes
2016-04-21 07:54:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. APRIL 21/ 2016
 ACTION: DENIED
  
 NOTICE!!!!!!! !!!!!!!!!!!!! CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 PLEASE READ!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED
 SHEETS & REPLACE ANY PAGES AS NECESSARY. OLD SHEETS
 LEFT IN PLANS. REVIEW FAILS.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1) CORRECTED. 2ND REQUEST.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. .
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 2) 2ND REQUEST. THE COVER-SHEET A-0.0 UNDER THE HEADING
 PROJECT DATA;
  
 2A) 2ND REQUEST. UNDER THE WIND DESIGN THE PLANS ONLY
 LIST THE R2 OCCUPANCY NOT THE R3 SINGLE FAMILY UNIT.
 PLANS AND DESIGN CRITERIA NEED TO BE SPLIT INTO 2
 PERMITS AND PACKAGES SO EACH BUILDING AND ASSOCIATED
 OCCUPANCY CAN BE REVIEWED UNDER THE APPROPRIATE CODE.
 107,2,1,4,
  
 2B) ) 2ND REQUEST. THE PROJECT DATA SHEET INDICATES
 THIS IS A LEVEL II ALTERATION. IT APPEARS MORE LIKE A
 LEVEL II LIMITED ALTERATION.2014 FBC-EXIST. BLDG. CODE
 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK
 AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE
 BUILDING. THIS REVIEW WILL BE TREATED AS SUCH, PLEASE
 UPDATE PLANS.
  
 2C) 2ND REQUEST. UNDER THE HEADING PROJECT DATA THERE
 ARE (2) CODES THAT ARE MISSING IN THE DESIGN CRITERIA,
 FOR THE COMMERCIAL 6 UNIT APARTMENT BUILDING THE 2014
 FBC-BUILDING, AND FOR THE SINGLE FAMILY DWELLING UNIT
 THE 2014 FBC-RESIDENTIAL CODE, 2 SEPARATE AND DISTINCT
 CODES. THE RESIDENTIAL CODE DEALS STRICTLY WITH 1-2
 FAMILY DWELLING UNITS!!!!!!!!!! SEE SCOPING AND TITLE
 REQUIREMENTS IN EACH CODE. 101.1 TITLE/ SCOPE 101.2..
  
 2D) COMPLIED. UNDER THE HEADING APARTMENT BUILDING
 SCOPE OF WORK THE PLANS INDICATE THIS IS A 6 STORY
 BUILDING. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2E)2ND REQUEST. THE PLANS DO NOT DECLARE IF THIS
 BUILDING IS FIRE SPRINKLERED OR NOT. IF FIRE
 SPRINKLERED WHAT TYPE OF FIRE SPRINKLER IS DESIGN?
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS.
  
 2F) COMPLIED
  
 2G) COMPLIED..
  
 3) 2ND REQUEST. CODE SUMMARY. SHEET A-3.3 ALL INDICATE
 THE PLANS WERE DESIGNED TO THE 2014 FLORIDA BUILDING
 CODE. PLEASE NOTE THE 2014 FLORIDA BUILDING CODE IS FOR
 COMMERCIAL BUILDINGS (APARTMENT BUILDINGS / R2). THIS
 SHEET IS THE FLOOR PLAN FOR THE SINGLE FAMILY HOUSE
 (R3). THE CODE FOR THE SINGLE FAMILY HOUSE IS THE 2014
 FBC-RESIDENTIAL CODE.
  
  
 SHEET A-3.1 / 1ST FLOOR PLAN OF THE 2 STORY R2
 APARTMENT BUILDING. TITLE BLOCK INDICATES 1ST FLOOR
 ELECTRIC PLAN?????? THIS PLAN APPEARS TO BE THE
 ARCHITECTURAL PLAN.
  
  
 3A) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLARED
 THIS BUILDING TYPE AS A I-B BUILDING TYPE OF
 CONSTRUCTION, SEE CODE SUMMARY TABLE 503 HEADING.
 PLEASE NOTE ALL TRUSSES AND ROOF SHEATHING HAD TO BE
 INSTALLED WITH FIRE RETARDANT TREATED PLYWOOD. ALL NEW
 FRAMING MEMBERS AND ROOF SHEATHING WILL NEED TO COMPLY
 WITH FBC-B 603.1.1.3. 1. FIRE-RETARDANT-TREATED WOOD
 SHALL BE PERMITTED IN: 1.3. ROOF CONSTRUCTION,
 INCLUDING GIRDERS, TRUSSES, FRAMING AND DECKING.
  
 3B) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT
 OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT
 CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE
 2014 FBC-EXISTING BUILDING CODE NOR THE 2014
 FBC-BUILDING CODE.
  
 3C) 2ND REQUEST. DETAIL 1/ A-4 OF SHEET A-3.1
 REFERENCES THE SFBC ITEM # 79 SECT. 37B. PLEASE UPDATE
 PLANS TO THE CURRENT 2014 FBC-B AND CURRENT CODE
 SECTIONS FOR TENANT SEPARATION REQUIREMENTS FOR TENANT
 SEPARATION WALLS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
  
 3D) 2ND REQUEST. IN UNIT # 2 THE WINDOWS IN THE BEDROOM
 #1, BATHROOM & KITCHEN ARE NOT IDENTIFIED. NOR ARE THE
 WINDOWS IN THE WINDOW SCHEDULE D-G NOT IDENTIFIED AS TO
 SIZE AND TYPE OF WINDOW. THE WINDOW SCHEDULE DOES NOT
 EVEN IDENTIFY THERE IS A WINDOW TYPE H LOCATED ON THE
 PLANS.
  
 3E) 2ND REQUEST. PLEASE PROVIDE WHAT THE SILL HEIGHT OF
 THE WINDOW IS LOCATED IN THE BATHROOMS, PLEASE SHOW
 COMPLIANCE WITH FBC-B 2406.4.5.
  
 3F) 2ND REQUEST. THE PLANS DO NOT INDICATE A CUT
 SECTION THROUGH THE FLOOR/ CEILING ASSEMBLY OF THE 1ST
 FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G) 2ND REQUEST. THE PLANS SHOW A HATCHED AREA WHERE
 THE CEILINGS ARE DROPPED TO 7 FEET ABOVE THE FINISH
 FLOOR. THE PLAN STILL SHOWS A HATCHED AREA FOR IN THE
 BATHROOM BUT THE PLANS INDICATE ALSO A 8 FOOT FLAT
 CEILING HEIGHT. DISCREPANCY IN PLANS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3H) COMPLIED.
  
 3I) 2ND REQUEST. PLEASE NOTE THIS ARCHITECTURAL SHEET
 IS LABELED ELECTRICAL 1ST FLOOR PLAN. PLEASE CORRECT
 AND UPDATE THIS SHEET.
  
 3K) SHEET 3.5 THIS SHEET LIST THE SINGLE FAMILY HOUSE
 AS A R1 OCCUPANCY. 2014 FBC-B 310.5.
  
 4A) 2ND REQUEST. SHEET A-3.2 2ND STORY FLOOR PLAN OF
 THE R2 APARTMENT BUILDING. HAS THE SAME ISSUES AS THE
 1ST FLOOR LAYOUT. SEE COMMENTS 3D-3H.
  
 4B) 2ND FLOOR. SHEET A3.2 THE 2ND FLOOR PORCH THE
 WINDOWS IN UNIT # 5 BEDROOM # 5 & THE LIVING ROOM ARE
 NOT IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. NOTE THESE WINDOWS WILL HAVE TO BE SAFETY
 WINDOWS AS WELL LOCATED IN A HAZARDOUS LOCATION.
 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS.
 THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH
 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS.
  
 5) 2ND REQUEST. THE 2ND STORY FLOOR SYSTEM DOES NOT
 PROVIDE HOW COMPLIANCE WITH STRUCTURE BORNE SOUND WILL
 BE ACHIEVED, SHOW COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5C) 2ND FLOOR. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) 2ND REQUEST, PLEASE PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 7) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 02/ 2016
 ACTION: DENIED
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 PLEASE READ!!!!!!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED
 SHEETS & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A3.3
 1A) 2ND REQUEST. IT APPEARS THE WIDTH AND HEIGHT
 DIMENSIONS OF THE WINDOW WERE REVERSED COMPARED TO THAT
 OF THE R2 APARTMENT BUILDING. 2014 FBC-R 310.1.1-3.
  
 1B) 2ND REQUEST. PLEASE SHOW WHAT THE SILL HEIGHT WILL
 BE FOR THE WINDOWS WITHIN BOTH BATHROOMS AND COMPLIANCE
 WITH
 R308.4.5.
  
 1C) 2ND REQUEST. SHEET S-2.3SF THE DEMO PLAN THERE ARE
 NO WALLS BEING DEMO-ED BETWEEN THE LIVING ROOM AND THE
 DINING ROOM. SHEET A3.3 IT IS NOT CLEAR IF A NEW WALL
 IS TO BE BUILT BETWEEN THESE ROOMS OR IF A HEADER IS
 BEING INSTALLED. NOTE THIS WILL BLOCK OFF ACCESS TO THE
 REMAINDER OF THE RESIDENCE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) 2ND REQUEST. THE FRONT AND REAR DOORS ARE BEING
 REPLACED BUT THE WIDTH OF THE DOOR IS UNKNOWN IN THE
 DOOR SCHEDULE. PLEASE SHOW COMPLIANCE WITH R3.11.2.
  
 1E) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT
 OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT
 CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE
 2014 FBC-EXISTING BUILDING CODE NOR THE 2014 FLORIDA
 RESIDENTIAL CODE. PLEASE NOTE ALL CODE REFERENCES,
 TABLE 503, TABLE 602 AND CHAPTER 7 ARE ALL REFERENCES
 TO THE FBC-BUILDING THE COMMERCIAL CODE. THIS IS A
 STAND ALONE SINGLE FAMILY DWELLING WHICH SHOULD BE
 REVIEWED UNDER THE 2014 FBC-RESIDENTIAL CODE.
  
 2) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 3) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) 2ND REQUEST, WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By jwitmer Date 2016-03-18 Time 10:36 Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time 07:43 Sent To  
Notes
2016-03-18 10:35:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 18/ 2016
 ACTION: DENIED
 6 UNIT/ R2 / APARTMENT BUILDING
 1) THE CONTRACTOR NEEDS TO SPLIT THIS PERMIT PACKAGE
 INTO (2) SEPARATE PERMITS AND PLANS SINCE THERE ARE (2)
 TYPES OF BUILDINGS BEING RENOVATED. A COMMERCIAL
 APARTMENT BUILDING ( COMMERCIAL REMODEL) AND A SINGLE
 FAMILY DWELLING( RESIDENTIAL REMODEL) UNLESS THERE IS A
 USE THAT HAS NOT BEEN DECLARED SUCH AS A SOBER HOME,
 HALF-WAY HOUSE, ETC... NOTE THERE ARE (2) DIFFERENT
 OCCUPANCY TYPE R2 & R3 AND NEED TO BE REVIEWED UNDER
 THEIR APPROPRIATE CODES (FBC-BUILDING &
 FBC-RESIDENTIAL) AS WELL AS FOR INSPECTION PURPOSE AND
 FOR RECORD KEEPING .
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. .
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 2) THE COVER-SHEET A-0.0 UNDER THE HEADING PROJECT
 DATA;
 2A) UNDER THE WIND DESIGN THE PLANS ONLY LIST THE R2
 OCCUPANCY NOT THE R3 SINGLE FAMILY UNIT. PLANS AND
 DESIGN CRITERIA NEED TO BE SPLIT INTO 2 PERMITS AND
 PACKAGES SO EACH BUILDING AND ASSOCIATED OCCUPANCY CAN
 BE REVIEWED UNDER THE APPROPRIATE CODE. 107,2,1,4,
  
 2B) THE PROJECT DATA SHEET INDICATES THIS IS A LEVEL II
 ALTERATION. IT APPEARS MORE LIKE A LEVEL II LIMITED
 ALTERATION.2014 FBC-EXIST. BLDG. CODE 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE AGGREGATE AREA OF THE BUILDING. THIS
 REVIEW WILL BE TREATED AS SUCH, PLEASE UPDATE PLANS.
  
 2C) UNDER THE HEADING PROJECT DATA THERE ARE (2) CODES
 THAT ARE MISSING IN THE DESIGN CRITERIA, FOR THE
 COMMERCIAL 6 UNIT APARTMENT BUILDING THE 2014
 FBC-BUILDING, AND FOR THE SINGLE FAMILY DWELLING UNIT
 THE 2014 FBC-RESIDENTIAL CODE, 2 SEPARATE AND DISTINCT
 CODES. THE RESIDENTIAL CODE DEALS STRICTLY WITH 1-2
 FAMILY DWELLING UNITS!!!!!!!!!! SEE SCOPING AND TITLE
 REQUIREMENTS IN EACH CODE. 101.1 TITLE/ SCOPE 101.2..
  
 2D) UNDER THE HEADING APARTMENT BUILDING SCOPE OF WORK
 THE PLANS INDICATE THIS IS A 6 STORY BUILDING.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2E) THE PLANS DO NOT DECLARE IF THIS BUILDING IS FIRE
 SPRINKLERED OR NOT. IF FIRE SPRINKLERED WHAT TYPE OF
 FIRE SPRINKLER IS DESIGN? 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
  
 2F) UNDER THE HEADING SINGLE FAMILY RESIDENCE THE PLANS
 INDICATE A 1 STORY HISTORIC BUILDING WHERE AS THE PLANS
 INDICATE A 2 STORY BUILDING. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2G) THE TITLEBLOCK FOR ALL SHEETS HAS THE PRINTED NAME
 CROSSED OUT THAT WASN?T THE NAME OF THE ARCHITECT
 SEALING THE PLANS. ADMINISTRATIVE CODE 61G-16.004 (6) A
 SPACE REQUIRED FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT.
  
 3) SHEETS A-1.2, A-2.1, A-3.1, A-3.2, & A-3.3 ALL
 INDICATE THE PLANS WERE DESIGNED TO THE 2012 FLORIDA
 BUILDING CODE. PLEASE NOTE THE 2014 FLORIDA BUILDING
 CODE, 5TH EDITION WAS ADOPTED STATEWIDE ON JUNE 30/
 2015. PLEASE CORRECT PLANS.
  
 SHEET A-3.1 / 1ST FLOOR PLAN OF THE 2 STORY R2
 APARTMENT BUILDING.
 3A) THE DESIGNER OF RECORD HAS DECLARED THIS BUILDING
 TYPE AS A I-B BUILDING TYPE OF CONSTRUCTION. PLEASE
 NOTE ALL TRUSSES AND ROOF SHEATHING HAD TO BE INSTALLED
 WITH FIRE RETARDANT TREATED PLYWOOD. ALL NEW FRAMING
 MEMBERS AND ROOF SHEATHING WILL NEED TO COMPLY WITH
 FBC-B 603.1.1.3. 1. FIRE-RETARDANT-TREATED WOOD SHALL
 BE PERMITTED IN: 1.3. ROOF CONSTRUCTION, INCLUDING
 GIRDERS, TRUSSES, FRAMING AND DECKING.
  
 3B) CODE SUMMARY ON THIS SHEET LIST A LOT OF CODE
 SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT CODE THESE
 SECTIONS WERE TAKEN FROM, NOT FOUND IN THE 2014
 FBC-EXISTING BUILDING CODE NOR THE 2014 FBC-BUILDING
 CODE.
  
 3C) DETAIL 1/ A-4 OF SHEET A-3.1 REFERENCES THE SFBC
 ITEM # 79 SECT. 37B. PLEASE UPDATE PLANS TO THE CURRENT
 2014 FBC-B AND CURRENT CODE SECTIONS FOR TENANT
 SEPARATION REQUIREMENTS FOR TENANT SEPARATION WALLS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
  
 3D) IN UNIT # 2 THE WINDOWS IN THE BEDROOM #1, BATHROOM
 & KITCHEN ARE NOT IDENTIFIED. NOR ARE THE WINDOWS IN
 THE WINDOW SCHEDULE D-G NOT IDENTIFIED AS TO SIZE AND
 TYPE OF WINDOW. THE WINDOW SCHEDULE DOES NOT EVEN
 IDENTIFY THERE IS A WINDOW TYPE H LOCATED ON THE PLANS.
  
 3E) PLEASE PROVIDE WHAT THE SILL HEIGHT OF THE WINDOW
 IS LOCATED IN THE BATHROOMS, PLEASE SHOW COMPLIANCE
 WITH FBC-B 2406.4.5.
  
 3F) THE PLANS DO NOT INDICATE A CUT SECTION THROUGH THE
 FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G) THE PLANS SHOW A HATCHED AREA WHERE THE CEILINGS
 ARE DROPPED TO 7 FEET ABOVE THE FINISH FLOOR. THE PLAN
 STILL SHOWS A HATCHED AREA FOR IN THE BATHROOM BUT THE
 PLANS INDICATE ALSO A 8 FOOT FLAT CEILING HEIGHT.
 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3H) THE CLOSET WHERE THE A/C AIR HANDLER SITS DOORS 4 &
 13 ARE INDICATED AS A FULL LOUVER BUT DOES NOT INDICATE
 IF THIS DOOR IS WOOD OR METAL LOUVER DOOR. 2014 FBC-M
 602.2.1.
  
 3I) PLEASE NOTE THIS ARCHITECTURAL SHEET IS LABELED
 ELECTRICAL 1ST FLOOR PLAN. PLEASE CORRECT AND UPDATE
 THIS SHEET.
  
 4) SHEET A-3.2 2ND STORY FLOOR PLAN OF THE R2 APARTMENT
 BUILDING. HAS THE SAME ISSUES AS THE 1ST FLOOR LAYOUT.
 SEE COMMENTS 3D-3H.
  
 4A) INDICATES HOW THE
  
 5) THE 2ND STORY FLOOR SYSTEM DOES NOT PROVIDE HOW
 COMPLIANCE WITH STRUCTURE BORNE SOUND WILL BE ACHIEVED,
 SHOW COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 7) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 18/ 2016
 ACTION: DENIED
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 1) SHEET A3.3
 1A) IT APPEARS THE WIDTH AND HEIGHT DIMENSIONS OF THE
 WINDOW WERE REVERSED COMPARED TO THAT OF THE R2
 APARTMENT BUILDING. 2014 FBC-R 310.1.1-3.
  
 1B) PLEASE SHOW WHAT THE SILL HEIGHT WILL BE FOR THE
 WINDOWS WITHIN BOTH BATHROOMS AND COMPLIANCE WITH
 R308.4.5.
  
 1C) SHEET S-2.3SF THE DEMO PLAN THERE ARE NO WALLS
 BEING DEMO-ED BETWEEN THE LIVING ROOM AND THE DINING
 ROOM. SHEET A3.3 IT IS NOT CLEAR IF A NEW WALL IS TO BE
 BUILT BETWEEN THESE ROOMS OR IF A HEADER IS BEING
 INSTALLED. NOTE THIS WILL BLOCK OFF ACCESS TO THE
 REMAINDER OF THE RESIDENCE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) THE FRONT AND REAR DOORS ARE BEING REPLACED BUT THE
 WIDTH OF THE DOOR IS UNKNOWN IN THE DOOR SCHEDULE.
 PLEASE SHOW COMPLIANCE WITH R3.11.2.
  
 1E) CODE SUMMARY ON THIS SHEET LIST A LOT OF CODE
 SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT CODE THESE
 SECTIONS WERE TAKEN FROM, NOT FOUND IN THE 2014
 FBC-EXISTING BUILDING CODE NOR THE 2014 FLORIDA
 RESIDENTIAL CODE.
  
 2) PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 3) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-08-04 Cont ID  
Sent By vperez Date 2016-08-04 Time 09:20 Rev Time 0.00
Received By vperez Date 2016-08-04 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-24 Cont ID  
Sent By vperez Date 2016-05-24 Time 10:41 Rev Time 0.00
Received By vperez Date 2016-05-24 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By vperez Date 2016-04-13 Time 14:55 Rev Time 0.00
Received By vperez Date 2016-04-13 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By vperez Date 2016-03-09 Time 09:55 Rev Time 0.00
Received By vperez Date 2016-03-08 Time 13:33 Sent To  
Notes
2016-03-09 09:58:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE SERVICE LOAD CALCULATION TO VERIFY
 SERVICE CONDUCTORS SELECTED AND SHOWN AT 2/0 CU. NEC
 310.15B16
 2. LABEL MAINS 1 OF 6, 2 OF 6 ETC. PER NEC 230.71
 3. PROVIDE SIGNAGE TO INDICATE MULTIPLE SERVICES TO
 PROPERTY. SERVICE 1 OF 2 AND 2 OF 2 PER NEC 230.2E NOTE
 FOR FIRST RESPONDERS.
 4. VERIFY SIZE OF GROUNDING ELECTRODE CONDUCTOR WHEN
 SERVICE CALCULATION IS PROVIDED. NEC 250.66.
 5. CLARIFY EXTERIOR EMERGENCY LIGHTING SOURCE OF POWER,
 IS THERE A HOUSE PANEL FOR BUILDING EXTERIOR. CLARIFY
 MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY CONSERVATION
 CODE 2014 5TH EDITION FOR ALL EXTERIOR LIGHTING. FBC EC
 405.2
 6. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT
 BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION
 FAMILY, NEC 2011.
 7. GRADE LEVEL UNITS TO BE PROVIDED WITH RECEPTACLE
 OUTLET PER NEC 210.52E2
 8. UNITS SHOWN ON SHEET E-1.3 ADDRESS WALL SPACING IN
 BED #5 WALL SPACE, NEC 210.52A2
 9. BATHROOM 1 AND 2 RECEPTACLES TO BE LABELED GFCI. NEC
 210.8A1
 10. ADD A RECEPTACLE OUTLET TO UNIT #5 BATHROOM TO BE
 GFCI PROTECTED NEC 210.8A1
 11. ADDESS FIRE COMMENTS RELATED TO ELECTRICAL
 INSTALLATION FBC 107.3.5
 12. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-05-23 Cont ID  
Sent By pleduc Date 2016-05-23 Time   Rev Time 0.00
Received By pleduc Date 2016-05-23 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By pleduc Date 2016-04-11 Time   Rev Time 0.00
Received By pleduc Date 2016-04-11 Time 16:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By pleduc Date 2016-03-07 Time   Rev Time 0.00
Received By pleduc Date 2016-03-04 Time 16:50 Sent To  
Notes
2016-03-07 14:37:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 3.1 - STORAGE UNDER THE EXIT STAIRS IS
 INDICATED. PLEASE PROVIDE INDICATIONS THAT COMPLY WITH
 THE REQUIREMENTS OF NFPA 101, CHAPER 7 MEANS OF EGRESS,
 7.2.2.5.3 USABLE SPACE.
  
 2. SHEET A 3.1 - THERE ARE WINDOWS INDICATED ALONG THE
 EXIT STAIRWAY. PLEASE PROVIDE INDICATIONS THAT COMPLY
 WITH THE REQUIREMENTS OF NFPA 101, CHAPER 7 MEANS OF
 EGRESS, 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE
 STAIRS.
  
 3. SHEET A 5.1 - THERE IS NO STAIR AND/OR HANDRAIL AND
 GUARD DETAIL. PLEASE PROVIDE DETAILS THAT COMPLY WITH
 THE REQUIREMENTS OF NFPA 101, CHAPER 7 MEANS OF EGRESS,
 7.2.2 STAIRS.
  
 4. SHEET A 5.1 - PLEASE PROVIDE DETAILS THAT COMPLY
 WITH THE REQUIREMENTS OF NFPA 101, CHAPER 7 MEANS OF
 EGRESS, 7.2.2.6.2 VISUAL PROTECTION.
  
 4. SHEET A 3.1 - THE WINDOW SCHEDULE DOES NOT HAVE
 INFORMATION CORRESPONDING WITH WINDOWS MARKED D, E, F,
 OR G. PLEASE PROVIDE.
  
 5. FIRE SPRINKLER - THERE IS NO SHEET SHOWING THE
 CONCEPTUAL FIRE SPRINKLER PALN. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 SEPARATE SHOP DRAWINGS SHALL BE SUBMITTED CONFORMING TO
 THE ABOVE.
  
 6. SHEET A 5.1 - PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 7. SHEET E 1.2 - PROVIDE EXIT SIGNAGE AT THE TOP OF THE
 STAIRS PER THE REQUIREMENTS OF NFPA 101, CHAPER 7 MEANS
 OF EGRESS, 7.10 MARKING OF MEANS OF EGRESS.
  
 8. SHEET E 1.1 - PROVIDE A SMOKE DETECTOR IN THE
 IMMEDIATE AREA OUTSIDE EACH BEDROMM IN UNITS 1, 2, AND
 3.
  
 9. SHEET E 1.2 - PROVIDE A SMOKE DETECTOR IN THE
 IMMEDIATE AREA OUTSIDE EACH BEDROMM IN UNITS 4, 5, AND
 6.
  
 10. SHEET E 1.1 & 1.2 - PROVIDE INDICATIONS THAT SMOKE
 ALARMS ARE INTERCONNECTED PER NFPA 101, CHAPTER 9 SMOKE
 ALARMS, 9.6.2.10.3
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-06-21 Cont ID  
Sent By fmittner Date 2016-06-21 Time 15:33 Rev Time 0.00
Received By fmittner Date 2016-06-21 Time 15:33 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-04-19 Cont ID  
Sent By destabro Date 2016-04-19 Time 16:11 Rev Time 0.00
Received By destabro Date 2016-04-19 Time 16:11 Sent To  
Notes
2016-04-19 16:12:48TRIM AND DETAILS SHOULD BE REPAIRED IF POSSIBLE, AND
 REPLACED IN-KIND ONLY IF BEYOND REPAIR. PLANS INDICIATE
 FULL REPLACEMENT, WHICH WAS ADDRESSED IN THE FIRST
 HISTORICAL REVIEW, WITHOUT CONSIDERATION OF EXISTING
 CONDITIONS. QUESTIONS MAY BE DIRECTED TO DESIREE
 ESTABROOK @ 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-03-18 Cont ID  
Sent By fmittner Date 2016-03-18 Time 15:26 Rev Time 0.00
Received By fmittner Date 2016-03-18 Time 15:26 Sent To Z
Notes
2016-03-18 15:29:19ROUTED TO ANA MARIA APONTE FOR ZONING REVIEW.
2016-03-18 15:28:50TRIM AND DETAILS SHALL NOT BE REMOVED AS INDICATED ON
 PLANS, REPAIR AND REUSE WHEREVER POSSIBLE. SCHEDULE
 SITE VISIT OR PROVIDE DETAILS OF AREAS THAT ARE IN NEED
 OF REPLACEMENT. QUESTIONS CONTACT FRIEDERIKE MITTNER AT
 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-09-13 Cont ID  
Sent By jwitmer Date 2016-09-13 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2016-09-08 Time 15:40 Sent To  
Notes
2016-09-09 15:40:52RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 15:22 Rev Time 0.00
Received By ccole Date 2016-07-29 Time 13:19 Sent To  
Notes
2016-07-29 13:20:09C26

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-21 Cont ID  
Sent By   Date 2016-06-21 Time   Rev Time 0.00
Received By lmarchan Date 2016-05-18 Time 15:12 Sent To  
Notes
2016-05-19 15:13:21C32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-02 Cont ID  
Sent By cpuell Date 2016-05-02 Time 16:40 Rev Time 0.00
Received By cpuell Date 2016-04-07 Time 08:42 Sent To  
Notes
2016-04-08 08:42:57C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-30 Cont ID  
Sent By lmarchan Date 2016-03-30 Time 11:17 Rev Time 0.00
Received By lmarchan Date 2016-03-01 Time 09:03 Sent To  
Notes
2016-03-09 10:01:403/9 TO C06
2016-03-02 09:07:13C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-18 Cont ID  
Sent By jwitmer Date 2016-03-18 Time 10:36 Rev Time 0.00
Received By jwitmer Date 2016-03-18 Time 10:36 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2016-03-29 Cont ID  
Sent By rcaranci Date 2016-03-29 Time 16:56 Rev Time 0.00
Received By rcaranci Date 2016-03-29 Time 16:56 Sent To  
Notes
2016-03-29 17:03:32PLEASE SUBMIT THE CORRECTED LANDSCAPE PLAN AS A
 SEPARATE LANDSCAPE PERMIT.
 REVIEW COMMENTS PROVIDED AS A COURTESY FOR RESUBMITTAL:
 1. PLEASE PROVIDE A LANDSCAPE PLAN SIGNED AND SEALED BY
 A REGISTERED LANDSCAPE ARCHITECT PER CODE SECTION
 94-442(A).
 2. PLEAS PROVIDE THE WATER USE CATEGORY FOR EACH PLANT
 ON THE PLANT LIST AND SHOW COMPLIANCE WITH SECTION
 94-442 (G) FLORIDA FRIENDLY LANDSCAPING.
 PLEASE ADDRESS ALL ZONING COMMENTS FOR CONFIGURATION OF
 PARKING, LANDSCAPE AREAS ADJACENT TO PARKING, AND
 SCREENING OF TRASH CONTAINER STORAGE AREAS.
 CONTACT RAY CARANCI, LANDSCAPE PLANNER 561-822-1462

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2016-09-13 Cont ID  
Sent By ccole Date 2016-09-13 Time 15:27 Rev Time 0.00
Received By ccole Date 2016-09-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 16:57 Rev Time 0.00
Received By ccole Date 2016-09-09 Time 16:57 Sent To  
Notes
2016-09-09 16:57:475TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16030064
 9/9/16
  
 1) THE ARCHITECT OF RECORD HAS PLACED HIS SIGNATURE BUT
 NOT HIS SEAL ON SHEET M1.3- REFER TO SECTION
 61G1-16.003 FAC AND PROVIDE THE SEAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 14:45 Rev Time 0.00
Received By ccole Date 2016-08-30 Time 14:45 Sent To  
Notes
2016-08-30 15:08:574TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16030064
 8/30/16
  
 1) THE MECHANICAL PLANS FOR THE SINGLE FAMIY HOME WERE
 NOT RESUBMITTED. PLEASE PROVIDE THE PLANS.
  
 2) SHEET M2.1: THE ENGINEER'S TITLE BLOCK HAS BEEN
 PLACED ON THE PLAN. IN ACCORDANCE WITH SECTION
 61G1-23.002 FLORIDA ADMINISTRATIVE CODE, THE ENGINEER
 MUST PLACE HIS SIGNATURE AND SEAL ON THE PLAN, OR
 REMOVE THE TITLE BLOCK IF THE ARCHITECT OF RECORD IS
 SIGNING OFF.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-05-26 Cont ID  
Sent By   Date 2016-05-26 Time   Rev Time 0.00
Received By ccole Date 2016-05-26 Time 07:31 Sent To  
Notes
2016-05-26 07:35:132ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030064
 5/26/16
  
 THE PREVIOUS 1ST REVIEW COMMENTS STILL EXIST- I AM
 RE-PRINTING THEM BELOW FOR REVIEW. PLEASE NOTE THAT
 THERE ARE NOW TWO M-1.3 PLAN SHEETS IN THE REVISED PLAN
 SETS- M-1.2 IS NOT IN THE SETS HOWEVER IT IS IN THE
 INDEX. PLEASE NOTE THAT A NARRATIVE RESPONSE FROM THE
 DESIGN PROFESSIONAL ADDRESSING THE MECHANICAL COMMENTS
 WAS NOT SUBMITTED.
  
 1) SHEETS M-1.1 & M-1.3 APARTMENT BUILDING: THE 1.5 TON
 AC SYSTEM SPECIFIED FOR UNIT #2 WILL ONLY PRODUCE 600
 CFM'S OF SUPPLY AIR HOWEVER THE PLAN INDICATES A TOTAL
 SUPPLY OF 665 CFM'S
 2) M-1.1 & M-1.2: THE PLANS DO NOT INDICATE HOW MINIMUM
 O/A FOR LIVING AREAS AND MINIMUM KITCHEN EXHAUST WILL
 BE PROVIDED- SEE TABLE 403.3 AND SHOW COMPLIANCE.
 3) M-1.1 & M-1.2: IF REVISING THE AC FLOOR PLANS PLEASE
 PRINT THE DIMENSIONS OF ALL MAIN TRUNK DUCTS (UNIT #5
 TRUNK DIMENSIONS NOT SHOWN).
 4) M-1.1: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CONDENSER PADS AND TIE DOWN OF THE
 NEW CONDENSERS- SECTION 301.15
 4) M1.3, SINGLE FAMILY: SHOW THE LOCATIONS OF THE
 CONDENSERS AND PROVIDE WINDLOAD ENGINEERING FOR TIE
 DOWN OF THE NEW CONDENSERS PER SECTION M1301.1 FBC-14
 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-22 Cont ID  
Sent By ccole Date 2016-04-22 Time 14:01 Rev Time 0.00
Received By ccole Date 2016-04-22 Time 14:01 Sent To  
Notes
2016-04-22 15:15:192ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030064
 4/22/16
  
 1) SHEETS M-1.1 & M-1.3 APARTMENT BUILDING: THE 1.5 TON
 AC SYSTEM SPECIFIED FOR UNIT #2 WILL ONLY PRODUCE 600
 CFM'S OF SUPPLY AIR HOWEVER THE PLAN INDICATES A TOTAL
 SUPPLY OF 665 CFM'S
 2) M-1.1 & M-1.2: THE PLANS DO NOT INDICATE HOW MINIMUM
 O/A FOR LIVING AREAS AND MINIMUM KITCHEN EXHAUST WILL
 BE PROVIDED- SEE TABLE 403.3 AND SHOW COMPLIANCE.
 3) M-1.1 & M-1.2: IF REVISING THE AC FLOOR PLANS PLEASE
 PRINT THE DIMENSIONS OF ALL MAIN TRUNK DUCTS.
 4) M-1.1: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CONDENSER PADS AND TIE DOWN OF THE
 NEW CONDENSERS- SECTION 301.15
 4) M1.3, SINGLE FAMILY: SHOW THE LOCATIONS OF THE
 CONDENSERS AND PROVIDE WINDLOAD ENGINEERING FOR TIE
 DOWN OF THE NEW CONDENSERS PER SECTION M1301.1 FBC-14
 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By hmoser Date 2016-03-08 Time 11:32 Rev Time 0.00
Received By hmoser Date 2016-03-08 Time 10:01 Sent To  
Notes
2016-03-08 11:31:28PLAN DENIED
  
 1) DOOR SCHEDULE SHOWS AIR HANDLER CLOSET DOOR WOOD.
 REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S 2014
 FBC (M)
 2) REFER TO SECTION 601.5 BALANCED RETURN AIR 2014 FBC
 (M)
 3) PROVIDE DUCT SIZE ON THE PLAN. PER SECTION 107 FBC
 2014
 4) PROVIDE EQUIPMENT SCHEDULE ON PLAN 107 FBC 2014.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2016-08-23 Time 09:24 Sent To  
Notes
2016-08-23 09:43:32 
 PROVISO: SEPARATE PERMIT REQUIRED FOR THE BACKFLOWS ON
 FIRE SPRINKLER LINE AND POTABLE WATER METERS FOR
 APARTMENT BUILDING.
 1. THE AMES 3000SS BACK FLOW THAT IS SPACED OUT FOR THE
 FIRE LINE DOES NOT MEET THE LEAD FREE REQUIREMENTS PER
 THE UNIVERSITY OF SOUTHERN CALIFORNIA?S ( USC ) LIST OF
 APPROVED DEVICES.
  
 DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION DEVICE
 PERMITS
  
 EFFECTIVE DATE: JANUARY 4TH, 2016
  
 THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE
 FOLLOWING DOCUMENTATION:
  
 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS
 SHALL BE ON THE JOBSITE FOR INSPECTION.
 PLEASE REFER TO THE ATTACHED DOCUMENT FOR INFORMATION
 REGARDING THE CITY OF WEST PALM BEACH APPROVED
 CONTRACTOR?S LIST FOR CERTIFYING / RECERTIFYING
 BACKFLOW DEVICES.
 THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS
 APPROXIMATELY 72 HOURS.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
 QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE
 DIRECTED TO:
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-05-31 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 13:42 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 14:26 Sent To  
Notes
2016-05-23 15:01:30REVIEW: FBC 2014
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENT:
  
  
  
 1) HAS NOT COMPLIED : THE CONTRACTOR NEEDS TO SPLIT
 THIS PERMIT PACKAGE INTO (2) SEPARATE PERMITS AND PLANS
 SINCE THERE ARE (2) TYPES OF BUILDINGS BEING RENOVATED.
 A COMMERCIAL APARTMENT BUILDING ( COMMERCIAL REMODEL)
 AND A SINGLE FAMILY DWELLING( RESIDENTIAL REMODEL)
 UNLESS THERE IS A USE THAT HAS NOT BEEN DECLARED SUCH
 AS A SOBER HOME, HALF-WAY HOUSE, ETC... NOTE THERE ARE
 (2) DIFFERENT OCCUPANCY TYPE R2 & R3 AND NEED TO BE
 REVIEWED UNDER THEIR APPROPRIATE CODES (FBC-BUILDING &
 FBC-RESIDENTIAL) AS WELL AS FOR INSPECTION PURPOSE AND
 FOR RECORD KEEPING .
  
 2. THE DEMO PLAN FOR SINGLE FAMILY HOME SHOWS DEMO WORK
 BUT THERE'S NO INDICATION OF WHAT PLUMBING WORK IS
 BEING DONE PLEASE CLARIFY. PER. WPB AMEND TO FBC
 107.2.1
  
 3. IN BOTH SETS OF PLANS THERE ARE DUPLICATE PAGES IN
 PLUMBING PLEASE REMOVE ALSO MARK AS VOID OR REMOVE
 PREVIOUSLY STAMPED PAGE. . PER. WPB AMEND TO FBC
 107.2.1
  
 4. THE BACK FLOW SUBMITTED FOR THE FIRE SPRINKLER DOES
 NOT MEET LEAD FREE REQUIREMENTS ALL BACK FLOWS SHALL
 MEET THESE REQUIREMENTS
 A) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 B) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 C) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 D) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 E) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
 QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE
 DIRECTED TO:
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-20 Cont ID  
Sent By tklarge Date 2016-04-20 Time 10:19 Rev Time 0.00
Received By tklarge Date 2016-04-20 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By gjohnson Date 2016-03-14 Time 15:11 Rev Time 0.00
Received By gjohnson Date 2016-03-14 Time 13:31 Sent To  
Notes
2016-03-14 15:11:301ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1. SHT. A-0.0 SCOPE OF WORK #1 RENOVATION OF 6 STORY.
 THE REST OF THE PLAN INDICATES 2 STORY PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
 2. THE VALUATION OF THIS JOB MAYBE LOW FOR THE COMPLETE
 PROJECT PLEASE PROVIDE A DETAILED QUANTITY ESTIMATES,
 AND/OR BONA FIDE SIGNED CONTRACTS.
 PER WPB AMEND. TO FBC SEC 109.3
 3. THIS PROJECT FALLS UNDER FBC 2014 5TH EDITION, MEP
 SHEETS CODE BLOCKS NEED TO BE CORRECTED.
 PER WPB AMEND. TO FBC SEC 107.2.1
 4.SHT. A-3.3 SCOPE OF WORK #10 ADD NEW BATHROOM,
 CLARIFY IS BATH #2 NEW OR EXISTING.
 PER WPB AMEND. TO FBC SEC 107.2.1
 5. IT IS INDICATED ON THE PLAN THAT IN THE SINGLE
 FAMILY DWELLING THERE IS A NEW WASHING MACHINE IN BATH
 #2 LIN CLOSET. PROVIDE PLUMBING RISER DIAGRAM FOR ALL
 NEW PIPING INCLUDE REPLACEMENT OF EXISTING.
 PER WPB AMEND. TO FBC SEC 107.2.1
 6. A BACKFLOW IS REQUIRED ON WATER SERVICE OF MULTI
 FAMILY DWELLING. SEPARATE PERMIT REQUIRED.
 PER CITY OF WEST PALM BEACH CROSS CONNECTION MANUAL.

Review Stop Z ZONING
Rev No 4 Status P Date 2016-08-22 Cont ID  
Sent By   Date 2016-08-22 Time   Rev Time 0.00
Received By kmartin Date 2016-08-19 Time 09:50 Sent To  
Notes
2016-08-22 09:10:22PROVISO
 PERMIT DOES NOT INCLUDE PARKING IMPROVEMENTS.
  

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2016-06-16 Time   Rev Time 0.00
Received By kmartin Date 2016-06-16 Time 13:22 Sent To  
Notes
2016-06-16 13:22:33PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. FOR MORE
 INFORMATION, PLEASE CONTACT KEVIN MARTIN AT
 561-822-1426.

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2016-05-02 Time   Rev Time 0.00
Received By kmartin Date 2016-06-16 Time 11:51 Sent To  
Notes
2016-05-02 15:32:02COMMERCIAL BUILDING WILL NOT BE ALLOWED. PREVIOUS
 COMMENTS HAVE NOT BEEN ADDRESSED. FOR MORE INFORMATION,
 PLEASE CONTACT KEVIN MARTIN AT 561-822-1426.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By aaponte Date 2016-03-22 Time 13:56 Rev Time 0.00
Received By aaponte Date 2016-03-22 Time 13:56 Sent To  
Notes
2016-03-22 14:12:121. PLEASE SUBMIT A SURVEY OF THE PROPERTY.
 2. PARKING AREAS SHALL BE LOCATED BEHIND THE BUILDING
 (SEC 94-128(E)B. PROPOSED SURFACE PARKING AT THE NE
 CORNER WILL NOT BE PERMITTED.
 3. PARKING SPACES ON SOUTH SIDE OF PROPERTY CAN BE 18'
 LONG.
 4. PARKING STRIPING SHALL FOLLOW CITY STANDARDS (SEC
 94-485).
 5. GARBAGE RECEPTACLES SHALL BE ENCLOSED WITH AN OPAQUE
 FENCE OR WALL, AND LANDSCAPE SHALL BE PROVIDED AROUND
 IT.
 6. A 5' LANDSCAPE BUFFER SHALL BE PROVIDED ON THE TWO
 ENDS OF THE PARKING SPACES, AND GARBAGE ENCLOSURE SHALL
 NOT BE INTALLED WITHIN SUCH BUFFER.
 7. THE PARKING DRIVE AISLE IS ENCROACHING INTO THE
 SOUTH PROPERTY LINE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.