Plan Review Details - Permit 16030035
Plan Review Stops For Permit 16030035
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 06:30 Sent To  
Notes
2016-03-15 07:16:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030035
 ADD: 100 S. DIXIE HWY. SUITE # 200
 CONT: NORTHSTAR CONSTRUCTION
 TEL: 718-208-3011
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 15/ 2016
 ACTION: DENIED
  
 1) SHEET A2. THE COVERSHEET INDICATES THIS IS A
 BUSINESS OCCUPANCY. PLEASE EXPLAIN THE USE OF THIS
 SPACE IF THIS IS A BUSINESS OCCUPANCY.
 2014 FBC-B 304.1 BUSINESS GROUP B. BUSINESS GROUP B
 OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING
 OR STRUCTURE, OR A PORTION THEREOF, FOR OFFICE,
 PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS, INCLUDING
 STORAGE OF RECORDS AND ACCOUNTS.
  
 2) SHEET A2. THE PLANS INDICATE IN OFFICE # 5 2 DOORS
 IN SERIES, PLEASE PROVIDE COMPLIANCE WITH: 2014
 FBC-ACCESSIBILITY CODE 404.2.6 DOORS IN SERIES.
  
 3) SHEET A2 PLEASE PROVIDE COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 403.5.2 FOR THE OFFICES 3-6.
  
 4) SHEET A2 PLEASE SHOW COMPLIANCE WITH THE DOOR FROM
 THE LOBBY INTO THE TENANT CORRIDOR2014 FBC-ACCESS. CODE
 404.2.4 MANEUVERING CLEARANCES.
 FIGURE 404.2.4.1(A).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-03 Cont ID  
Sent By vperez Date 2016-05-03 Time 07:10 Rev Time 0.00
Received By vperez Date 2016-05-03 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By vperez Date 2016-03-08 Time 10:45 Rev Time 0.00
Received By vperez Date 2016-03-08 Time 08:19 Sent To  
Notes
2016-03-08 11:04:11INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE DELETE FROM GENERAL NOTES ALL REFERENCES
 PERTAINING TO RESIDENTIAL INSTALLATIONS.
 2.ADD GENERAL NOTES INDICATING NEC 410.130G
 REQUIREMENTS FOR FLORESCENT LUMINAIRES.
 3.CLARIFY MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY
 CONSERVATION CODE 2014 5TH EDITION FOR ALL LIGHTINGS.
 FBC EC 405.2
 4.CORRECT TYPO TO INDICATE NEC 2011 NOT NEC 2010.
 5.SHOW LIGHTING AND POWER CIRCUIT DESIGNATION ON FLOOR
 PLAN. FBC 107.3.5
 6.SHOW PER NEC 700.12F THAT UNIT EQUIPMENT IS SERVED
 FROM THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCH.
 7.CLARIFY EXISTING PANEL C VOLTAGE. IS IT A SINGLE
 PHASE 120/240? SHOWN AS 208/240. NOTE THAT SINGLE PHASE
 IS CALLED OUT BUT PHASE A, B, C 3/PHASE ARRANGEMENT IS
 SHOWN. REFLECT AN ACCURATE PANEL SCHEDULE FOR APPROVAL.
 FBC 107.3.5
 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By pleduc Date 2016-04-27 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 09:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-07 Cont ID  
Sent By pleduc Date 2016-03-07 Time   Rev Time 0.00
Received By pleduc Date 2016-03-04 Time 16:49 Sent To  
Notes
2016-03-07 11:51:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET A & A 3 - THERE IS AN INCORRECT REFERENCE TO
 THE FIRE CODE -
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-26 Cont ID  
Sent By ccole Date 2016-05-26 Time 17:39 Rev Time 0.00
Received By ccole Date 2016-05-26 Time 10:54 Sent To  
Notes
2016-05-26 10:55:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-04-19 Time 15:32 Sent To  
Notes
2016-04-19 15:32:39C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2016-03-01 Time 12:26 Sent To  
Notes
2016-03-08 11:04:273/8 TO C12
2016-03-02 12:27:01C12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-26 Cont ID  
Sent By ccole Date 2016-05-26 Time 17:39 Rev Time 0.00
Received By ccole Date 2016-05-27 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-25 Cont ID  
Sent By ccole Date 2016-04-25 Time 16:56 Rev Time 0.00
Received By ccole Date 2016-04-25 Time 16:56 Sent To  
Notes
2016-04-25 17:09:092ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030035
 4/25/16
  
 1) THE NEW AC PLAN SHOWS 5" DIAMETER FLEX DUCTS
 CONNECTING TO NEW 4X4 DIFFUSERS- PLEASE CLARIFY HOW THE
 5" WILL CONNECT TO THE 4" COLLAR AND PROVIDE AN AIR
 DEVICE SCHEDULE ON THE PLANS.
 2) THE VENTILATION CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH REQUIRES OFFICE SPACES TO BE
 CALCULATED USING AN OCCUPANT DENSITY OF 5 PERSONS PER
 SF. AND LOBBIES AT 10 PERSONS PER SF. THE VENTILATION
 IS THEN CALCULATED AT 5CFMS PER PERSON + .06 CFMS PER
 SF.
 3) PLEASE SHOW ALL DUCT ALTERATIONS IN THE NEW LOBBY
 AND OPEN OFFICE ROOMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 15:43 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 15:43 Sent To  
Notes
2016-03-10 15:53:211ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16030035
 3/10/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING:
 ALTERED EXISTING SYSTEMS.
 "IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62." PLEASE PROVIDE A VENTILATION
 CALCULATION IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL.
 2) THE PLAN IS IN COMPLETE: SOME DUCT SIZES NOT SHOWN,
 DUCT TYPES NOT IDENTIFIED, CFM'S AT DIFFUSERS AND
 RETURNS NOT SHOWN, RETURN GRILLS AT BACK ROOMS OF
 OFFICES 3 & 4 NOT SHOWN.
 3) PLEASE CLARIFY IF THIS IS A PLENUM CEILING: PROVIDE
 A NOTE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-05-03 Cont ID  
Sent By gearl Date 2016-05-03 Time 11:49 Rev Time 0.00
Received By skennedy Date 2016-05-03 Time   Sent To  
Notes
2016-05-20 18:09:59THERE IS NO PLUMBING WORK.
2016-05-03 11:49:07 
  
 1. 918.8 FBC PLUMBING -- VENT REQUIRED/ NEED TO HAVE
 ONE VENT TO EXTENT TO THE OUTDOORS

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-12 Cont ID  
Sent By tklarge Date 2016-03-12 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-03-12 Time 06:22 Sent To  
Notes
2016-03-12 06:35:401) SHT. A - SCOPE OF WORK STATES THAT THERE IS NO
 PLUMBING WORK TO BE DONE, YET THERE IS A PLUMBING SHEET
 SHOWING A NEW HANDICAPPED TOILET ROOM, DRINKING
 FOUNTAINS AND A BREAK ROOM. CLARIFY. IF NO PLUMBING
 WORK IS TO BE DONE, REMOVE THIS SCOPE FROM THE PLANS
 AND ALSO THE PERMIT APPLICATION. FBC 107.2.1.
 2) THE ADDRESS ON THE PLUMBING PLAN IS 9070 KIMBERLY
 BLVD.#12, BOCA RATON. I DO NOT THINK THIS PLAN BELONGS
 IN THIS PACKAGE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  