Plan Review Details - Permit 16030026
Plan Review Stops For Permit 16030026
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-23 Cont ID  
Sent By jwitmer Date 2016-06-23 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2016-06-23 Time 14:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-13 Cont ID  
Sent By   Date 2016-05-13 Time   Rev Time 0.00
Received By   Date 2016-05-13 Time   Sent To  
Notes
2016-05-13 15:05:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030026
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES, LLC
 TEL: 561-803-8100
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 13/ 2016
 ACTION: DENIED
  
 BUILDING TYPE; III-A (PROTECTED)/ SPRINKLERED.
 PLEASE NOTE SHEETS LS-1 & A1 SHOWS PHASE III WITH A
 CONTINUATION OF WORK FROM PHASE II COVERED UNDER PERMIT
 12030123 (2007 FBC-B). UNDER THIS EDITION OF THE FBC
 CORRIDORS HAD TO BE FIRE RATING SO THE PHASE III PERMIT
 WILL CONTINUE THE 1 HOUR FIRE RATING OF THE NEW
 CORRIDORS.
  
 1) SHEET A1:
 1A-B) COMPLIED.
  
 1C) SEMI- COMPLIED. PLEASE NOTE SHEET A1 VERSES SHEET
 M-1, SHEET M-1 SHOWS DUCT BEING PARALLEL TO THE COMMON
 WALL BETWEEN ROOM 302 & 305 AS DEPICTED THE WALL GOES
 DIRECTLY THROUGH THE CENTER OF THE DUCT SINCE THE WALL
 TYPE B1 GOES ALL THE WAY TO THE UNDERSIDE OF THE ROOF
 DECK. THIS APPEARS TO BE A DISCREPANCY IN THE PLANS
 WHERE THE MAIN TRUNK LINE NEEDS TO BE SHIFTED TO EITHER
 SIDE OF WALL TYPE B1.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, EITHER
 WALL B1 DOES NOT CONTINUE TO THE ROOF DECK AND WILL
 NEED BRACING OR THE DUCT PLACEMENT NEEDS TO BE MOVED.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2) SHEET A2 SHOWS A SECTION THROUGH THE ROOF FOR THE
 CURB MOUNTED GRAVITY INTAKE VENTILATOR. PLEASE NOTE THE
 GRAVITY VENTILATOR WILL NEED TO SIT ON A CURB THAT IS
 MOUNTED TO THE ROOF FRAMING. THIS REVIEW NO CURB WAS
 SUBMITTED. PLEASE PROVIDE THE ATTACHMENT METHOD AND
 WIND DESIGN THAT SUPPORTS THE CURB AND GRAVITY
 VENTILATOR TO STAY IN PLACE IN A HIGH WIND EVENT.
 . 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 2A) SEMI-COMPLIED. , 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31) (D) ROOFING PRODUCTS AND ASSEMBLIES/
 CURBS/ INTAKE AND ROOF TOP EXHAUST FANS.
 PLEASE PROVIDE THE CONNECTION FROM THE ROOF TOP CURB TO
 THE GRAVITY VENTILATOR.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B COMPLIED. . 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2C) COMPLIED. PLEASE PROVIDE DETAILS FOR THE FRAMING
 REQUIRED AROUND THE NEW OPENING IN THE ROOF SYSTEM.
 THIS FRAMING SHOULD TIE BACK INTO THE MWFRS, (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 2D) SEE COMMENTS (2A-2C). FOR ALL ROOF TOP EQUIPMENT,
 CURBS & FANS DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB AND ROOF TOP FAN. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 09:44 Sent To  
Notes
2016-03-24 11:35:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030026
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES, LLC
 TEL: 561-803-8100
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 24/ 2016
 ACTION: DENIED
  
 BUILDING TYPE; III-A (PROTECTED)/ SPRINKLERED.
 PLEASE NOTE SHEETS LS-1 & A1 SHOWS PHASE III WITH A
 CONTINUATION OF WORK FROM PHASE II COVERED UNDER PERMIT
 12030123 (2007 FBC-B). UNDER THIS EDITION OF THE FBC
 CORRIDORS HAD TO BE FIRE RATING SO THE PHASE III PERMIT
 WILL CONTINUE THE 1 HOUR FIRE RATING OF THE NEW
 CORRIDORS.
  
 1) SHEET A1:
 1A) PLEASE NOTE THE NEW FIRE RATED CORRIDOR WALLS ARE
 SHOWN WITH WALL TAGS B1 & B2 WITH THE EXCEPTION OF THE
 CORRIDOR WALL THAT SEPARATES TO ROOM 315. THIS NEW WALL
 DOES NOT SHOW AS A 1 HOUR FIRE RATED WALL. PLEASE SEE
 WALL TYPES ON SHEET A1, THIS WALL DOES NOT HAVE A WALL
 IDENTIFICATION TAG. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1B) PLEASE SEE THE DOOR SCHEDULE ON SHEET A-9, THE DOOR
 SCHEDULE DOES NOT EVEN HAVE A COLUMN INDICATING FIRE
 RATED DOORS. 2014 FBC-B TABLE 716.5.
  
 1C) PLEASE NOTE SHEET A9 VERSES SHEET M-1, SHEET M-1
 SHOWS DUCTS CROSSING THE 1 HOUR FIRE RATED WALLS
 WITHOUT THE BENEFIT OF FIRE DAMPERS SEE 2014 FBC-B
 717.1. ALSO SEE NOTES FROM THE MECHANICAL REVIEWER FOR
 NUMEROUS CODE VIOLATIONS INVOLVING DUCTS PENETRATING
 THE 1 HOUR FIRE RATED WALL.
  
 2) SHEET M1 NOTE # 2 INDICATES THE USE OF A 14 X 14
 INCH CURB MOUNTED GRAVITY INTAKE VENTILATOR GRENNHECK
 MODEL GRSR-16. SHEET M5 DETAIL 5 INDICATES A CUT
 SECTION OF THE INSTALLATION DETAIL. NOTE IN THE DETAIL
 INDICATES SEE ARCHITECTURAL & STRUCTURAL PLANS FOR CURB
 FRAMING AND ATTACHMENT TO ROOF.
  
 2A) , 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ INTAKE
 AND ROOF TOP EXHAUST FANS.
  
 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2C) PLEASE PROVIDE DETAILS FOR THE FRAMING REQUIRED
 AROUND THE NEW OPENING IN THE ROOF SYSTEM. THIS FRAMING
 SHOULD TIE BACK INTO THE MWFRS, (MAIN WIND FORCE
 RESISTING SYSTEM).
 2D) ) FOR ALL ROOF TOP EQUIPMENT, CURBS & FANS DETAILED
 ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM
 THE CURB AND ROOF TOP FAN. 2014 FBC-B 1604.4 ANALYSIS.
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 13:48 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-05-19 Cont ID  
Sent By mvaldes Date 2016-05-19 Time 09:49 Rev Time 0.00
Received By mvaldes Date 2016-05-19 Time 09:06 Sent To  
Notes
2016-05-19 09:51:26JOB PERMIT NUMBER: 16030026
 JOB ADDRESS: 425 24TH STREET
 WEST PALM BEACH FLORIDA
 DATE: MAY 19 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 THESE ARE COMMENTS TO YOUR RESPONSES!
  
 - SHEET E-2 IS MISSING FROM ONE SET OF THE NEWLY
 SUBMITTED PLANS. FURTHERMORE THE EXIT SIGN BY BACKSTAGE
 313 DOUBLE DOORS IS MISSING ?FBC-1011
 - THE RESPONSE NARRATIVE INDICATES SHEET E-01 HAS ADDED
 NOTES WHEN IN REALITY THE NOTES WERE CLOUDED TO SHEET
 E-0. PRIOR COMMENTS COMPLIED.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A
 QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING
 EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL
 FORM. THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER?S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By mvaldes Date 2016-03-07 Time 17:08 Rev Time 0.00
Received By mvaldes Date 2016-03-07 Time 17:08 Sent To  
Notes
2016-03-07 17:11:11JOB PERMIT NUMBER: 16030026
 JOB ADDRESS: 425 24TH STREET
 WEST PALM BEACH FLORIDA
 DATE: MARCH 7 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC-B 1011. EXIT SIGNAGE REQUIRED. MISSING EXIT SIGNS
 BY DOUBLE DOORS IN THE FOLLOWING LOCATIONS MEDIA ARTS
 ROOM , CLASSROOM 305 , AND BACKSTAGE 313. FURTHERMORE
 AN EXIT SIGN IS MISSING IN SINGLE DOOR BY HALLWAY 3
 LEADING TO HALLWAY 4.
 - FBC E C405.4 EXIT SIGNS SHALL NOT EXCEED 5 WATT PER
 SIDE 27. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT. ( KEEP IN MIND WHEN ADDING EXIT
 SIGNS. )
 - PLEASE ADD TO ELECTRICAL GENERAL NOTES NEC 300.21
 OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR THROUGH
 FIRE-RESISTANT-RATED WALLS, PARTITIONS , FLOORS, OR
 CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS
 TO MAINTAIN THE FIRE RESISTANCE RATING. NEC 300.7 A
 PROPERLY SEALING OF CONDUITS IS REQUIRED WHEN EXPOSED
 TO DIFFERENT TEMPERATURES.
 - PROVIDE ARC-FLASH HAZARD WARNING LABEL AND AVAILABLE
 FAULT CURRENT MARKING IN ACCORDANCE WITH NEC 110.16 ,
 110.24
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By pleduc Date 2016-06-21 Time   Rev Time 0.00
Received By pleduc Date 2016-06-21 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-04 Cont ID  
Sent By J.Walker Date 2016-03-04 Time   Rev Time 0.35
Received By   Date 2016-03-03 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 13:49 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 13:49 Sent To  
Notes
2016-06-13 10:19:15C05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-19 Cont ID  
Sent By mvaldes Date 2016-05-19 Time 09:53 Rev Time 0.00
Received By mvaldes Date 2016-05-03 Time 09:22 Sent To  
Notes
2016-05-04 09:23:00C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2016-03-01 Time 12:53 Sent To  
Notes
2016-03-01 12:53:33C05

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 12:26 Rev Time 0.00
Received By ccole Date 2016-06-14 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-09 Cont ID  
Sent By ccole Date 2016-05-09 Time 17:16 Rev Time 0.00
Received By ccole Date 2016-05-09 Time 17:16 Sent To  
Notes
2016-05-09 17:47:332ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030026
 5/9/16
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE
 RELOCATE THE 14X16 DUCT SHOWN ON TOP OF THE WALL
 BETWEEN THE CLASSROOM AND MEDIA ARTS ROOM.
 2) SHEET M-1: IT APPEARS THAT THE THERMOSTAT FOR AHU-3
 IS MISLABELED AS AHU-2 BY THE 38X24 RETURN GRILL.
 3) M-3: THE FRESH AIR CALCULATION FOR THE MULTI-PURPOSE
 ROOM MUST BE 7.5 CFM PER PERSON- TABLE 403.3.
 4) M-5: THE GRAVITY VENTILATOR DETAIL IS NOT LEGIBLE-
 APPEARS TO BE A NEGATIVE IMAGE. PLEASE PROVIDE A CLEAR
 DETAIL AND EQUIPMENT SCHEDULE.
 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOFTOP EQUIPMENT AND CLEARANCE DISTANCE
 MEASUREMENTS FOR ALL MECHANICAL AND GRAVITY AIR INTAKES
 TO EXHAUST AND VENT OUTLETS- SECTION 401.4.
 6) M-5: THE UNIT DATA IN THE CONDENSING UNIT DETAIL
 APPEARS NOT TO BE CONSISTENT WITH THE SIZES OF THE NEW
 CU-2 & 3 WHICH APPEAR TO MUCH LARGER DIMENSIONALLY.
 PLEASE PROVIDE SITE SPECIFIC DESIGN DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 14:12 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 13:24 Sent To  
Notes
2016-03-10 15:10:231ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030026
 3/10/16
  
 1) SHEETS M-1 & M-2: A) FLEX DUCTS SHALL NOT PASS
 THROUGH THE FIRE-RATED CORRIDOR WALLS OR THE FIRE-RATED
 CLASSROOM 305/MEDIA ARTS 302 WALL.
 2) M1 & M2: THE 14X16 TRUNK FROM AHU-2 IS SHOWN ON THE
 PLAN TO BE LOCATED ON TOP OF A THE FIRE-RATED CLASSROOM
 305/MEDIA ARTS 302- PLEASE RELOCATE THE DUCT PER
 SECTION 607.5.3.
 3) M1 & M2: FIRE DAMPER MISSING AT THE 38X24 RETURN
 GRILL LOCATED IN THE FIRE-RATED BACK STAGE/PERFORMANCE
 AREA WALL- SECTION 607.5.3.
 4) M1 & M2: THE FIBERGLASS DUCTS PENETRATING THE
 FIRE-RATED CORRIDOR PARTITION ARE PERMITTED TO BE
 INSTALLED WITHOUT DAMPERS BUT REQUIRE STEEL SLEEVES PER
 SECTIONS 607.1.1 & 607.5.3 FBC-14 MECHANICAL.
 5) A-1.1 & M-2: THE SCOPE OF WORK OUTLINE ON A-1.1 DOES
 NOT INCLUDE THE STORAGE ROOM, HOWEVER AC IS BEING
 SUPPLIED TO IT ON M-2.
 6) M-1 & M-2: PLEASE PROVIDE NOTES #7 & 15 ON THE
 PLANS.
 7) M-2: THE PLAN INDICATES A TOTAL OF 4800 CFM RETURN
 AIR FROM THE PERFORMANCE AREA TO AHU-3, HOWEVER THE
 TOTAL SUPPLY AIR TO THE AREA IS 6280 CFM- PLEASE
 CLARIFY.
 8) THE ENERGY CONSERVATION FORM LISTS AHU/CU-1 & 2,
 HOWEVER THE PLAN IS INDICATING AHU/CU- 2 & 3- PLEASE
 CORRECT.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND MIAMI-DADE
 NOA'S FOR THE GREENHECK GRAVITY INTAKE VENTILATOR
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR.
 10) PROVIDE A ROOF PLAN INDICATING THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FROM THE AIR INTAKES TO
 EXHAUST AND VENT OUTLETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-03-12 Cont ID  
Sent By tklarge Date 2016-03-12 Time 07:33 Rev Time 0.00
Received By tklarge Date 2016-03-12 Time 06:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-06-20 Cont ID  
Sent By njwira Date 2016-06-20 Time 16:07 Rev Time 0.00
Received By njwira Date 2016-06-17 Time 16:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By dkittred Date 2016-05-06 Time 16:52 Rev Time 0.00
Received By dkittred Date 2016-05-06 Time 12:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By dkittedg Date 2016-03-22 Time 16:41 Rev Time 0.00
Received By dkittred Date 2016-03-21 Time 12:44 Sent To  
Notes
2016-03-22 16:41:16PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/22/16
  
 1. CHANGES ARE BEING PROPOSED TO THE SITE INCLUDING THE
 ADDITION OF AC UNITS AND FENCE/WALL SCREENING AROUND
 THE MECHANICAL EQUIPMENT. AS A RESULT OF MAKING CHANGES
 TO THE SITE, TWO COPIES OF THE PROPERTY SURVEY SHALL BE
 SUBMITTED WITH THE APPLICATION.
  
 2. INDICATE SETBACKS FOR MECHANICAL EQUIPMENT (E.G. AC
 UNITS, ETC.) ON THE SITE PLAN.
  
 3. SCREENING MUST BE PROVIDED AROUND MECHANICAL
 EQUIPMENT IN ACCORDANCE WITH ZLDR SEC. 94-444(B). A
 SEPARATE PERMIT IS REQUIRED FOR THE REQUIRED FENCE/WALL
 AROUND THE MECHANICAL EQUIPMENT. PROPOSED MATERIAL AND
 HEIGHT WILL NEED TO DEMONSTRATE COMPLIANCE WITH ZLDR
 SEC. 94-213(D).
  
  
 GENERAL COMMENTS:
  
 A. ALL CODE REFERENCES CAN BE FOUND ON WWW.MUNICODE.COM
 BY NAVIGATING TO THE CITY OF WEST PALM BEACH CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  