Plan Review Details - Permit 16030013
Plan Review Stops For Permit 16030013
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By vperez Date 2016-05-24 Time 11:28 Rev Time 0.00
Received By vperez Date 2016-05-24 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-04 Cont ID  
Sent By vperez Date 2016-03-04 Time 08:16 Rev Time 0.00
Received By vperez Date 2016-03-04 Time 08:16 Sent To  
Notes
2016-03-04 08:17:18INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE PROVIDE DATA SHEETS FOR CONDUCTORS BEING USED,
 NOT IN PACKAGE SUBMITTED. FBC 107.3.5
 2.CONSTRUCTION DOCUMENTS WILL REQUIRE ENGINEER SEAL AND
 SIGNATURE.
 3.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By pleduc Date 2016-05-23 Time   Rev Time 0.00
Received By pleduc Date 2016-05-23 Time 12:42 Sent To E
Notes
2016-05-23 13:59:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 1 OF 2 - THERE IS A MAG LOCK INDICATED AT THE
 ELEVATOR/MAILROOM DOUBLE DOOR. A REQUEST TO EXIT IS NOT
 INDICATED AT THIS DOOR AND MAY BE REQUIRED.
  
 PLEASE REVIEW THIS PROPOSED INSTALLATION AND IF
 REQUIRED AT THIS DOOR PROVIDE A REQUEST TO EXIT FOR THE
 FIRE INSPECTOR TO REVIEW AND TEST. IF NOT REQUIRED,
 PLEASE BE PREPARED TO DISCUSS AND DEMONSTRATE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-04 Time 12:27 Rev Time 0.15
Received By   Date 2016-03-02 Time   Sent To  
Notes
2016-03-03 08:34:41WILL REQUIRE ENGINEER SEAL AND SIGNATURE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-24 Cont ID  
Sent By vperez Date 2016-05-24 Time 11:28 Rev Time 0.00
Received By vperez Date 2016-05-24 Time 11:28 Sent To  
Notes
2016-05-23 09:46:06ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-04 Cont ID  
Sent By pleduc Date 2016-03-04 Time   Rev Time 0.00
Received By pleduc Date 2016-03-01 Time 14:05 Sent To  
Notes
2016-03-04 08:17:343/4 TO CAROLINE