| 2016-03-10 06:39:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030005 |
| | ADD: 1309 N. FLAGLER DR. / 2ND FLOOR RENOVATION N.W. |
| | CORNER |
| | CONT: BMS CAT INC. |
| | TEL: 561-401-2522 |
| | E-MAIL: ?????????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MARCH 10/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.00 INDICATES IN NOTE 4 THE REMOVAL OF ALL |
| | FIRE INSULATION. DETAIL 3 OF THIS SHEET INDICATES THE |
| | INSTALLATION OF NEW FIRE PROOFING TO MATCH THE ORIGINAL |
| | SPECIFIED VALUES. THE PLANS INDICATE THIS BUILDING IS A |
| | BUILD. TYPE I-B WITH FIRE RATING OF: |
| | BEAMS / JOINTS 2 HR |
| | FLOOR/ CEILING 2 HR |
| | ROOF ROOF/CEILING 1HR |
| | SHAFT ENCLOSURES 2 HR |
| | 2014 FBC-B TABLE 601 |
| | |
| | 2) DETAIL 3 & 4 BOTH SHOW THE USE OF CLOSED CELL SPRAY |
| | FOAM INSULATION. PLEASE PROVIDE THE TESTING REPORT FOR |
| | THIS PRODUCT. THIS REPORT SHALL PROVIDE ALLOWABLE USES, |
| | LIMITATIONS, ALLOWABLE THICKNES ON VERTICAL SURFACES, |
| | THERMAL RESISTANCE (R-VALUES). DETAIL # 4 SHOWS THE |
| | FOAM SPRAY INSULATION ABOVE THE CEILING WHERE THE |
| | DRYWALL DOES NOT CONTINUE TO THE DECK ABOVE. HOW WILL |
| | COMPLIANCE WITH SECTION 2603.4 OF THE 2014 FBC-B BE |
| | MET. |
| | |
| | 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 2603.4.1 AND 2603.10, FOAM PLASTIC SHALL BE |
| | SEPARATED FROM THE INTERIOR OF A BUILDING BY AN |
| | APPROVED THERMAL BARRIER OF 1/2- INCH (12.7 MM) GYPSUM |
| | WALLBOARD OR A MATERIAL THAT IS TESTED IN ACCORDANCE |
| | WITH AND MEETS THE ACCEPTANCE CRITERIA OF BOTH THE |
| | TEMPERATURE TRANSMISSION FIRE TEST AND THE INTEGRITY |
| | FIRE TEST OF NFPA 275. COMBUSTIBLE CONCEALED SPACES |
| | SHALL COMPLY WITH SECTION 718. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | |
| | |
| | |
| | |
| | |