Plan Review Details - Permit 16030005
Plan Review Stops For Permit 16030005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-06-22 Cont ID  
Sent By   Date 2016-06-22 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2016-06-22 Time 06:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 05:48 Sent To  
Notes
2016-03-10 06:39:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030005
 ADD: 1309 N. FLAGLER DR. / 2ND FLOOR RENOVATION N.W.
 CORNER
 CONT: BMS CAT INC.
 TEL: 561-401-2522
 E-MAIL: ??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 10/2016
 ACTION: DENIED
  
 1) SHEET A1.00 INDICATES IN NOTE 4 THE REMOVAL OF ALL
 FIRE INSULATION. DETAIL 3 OF THIS SHEET INDICATES THE
 INSTALLATION OF NEW FIRE PROOFING TO MATCH THE ORIGINAL
 SPECIFIED VALUES. THE PLANS INDICATE THIS BUILDING IS A
 BUILD. TYPE I-B WITH FIRE RATING OF:
 BEAMS / JOINTS 2 HR
 FLOOR/ CEILING 2 HR
 ROOF ROOF/CEILING 1HR
 SHAFT ENCLOSURES 2 HR
 2014 FBC-B TABLE 601
  
 2) DETAIL 3 & 4 BOTH SHOW THE USE OF CLOSED CELL SPRAY
 FOAM INSULATION. PLEASE PROVIDE THE TESTING REPORT FOR
 THIS PRODUCT. THIS REPORT SHALL PROVIDE ALLOWABLE USES,
 LIMITATIONS, ALLOWABLE THICKNES ON VERTICAL SURFACES,
 THERMAL RESISTANCE (R-VALUES). DETAIL # 4 SHOWS THE
 FOAM SPRAY INSULATION ABOVE THE CEILING WHERE THE
 DRYWALL DOES NOT CONTINUE TO THE DECK ABOVE. HOW WILL
 COMPLIANCE WITH SECTION 2603.4 OF THE 2014 FBC-B BE
 MET.
  
 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.10, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2- INCH (12.7 MM) GYPSUM
 WALLBOARD OR A MATERIAL THAT IS TESTED IN ACCORDANCE
 WITH AND MEETS THE ACCEPTANCE CRITERIA OF BOTH THE
 TEMPERATURE TRANSMISSION FIRE TEST AND THE INTEGRITY
 FIRE TEST OF NFPA 275. COMBUSTIBLE CONCEALED SPACES
 SHALL COMPLY WITH SECTION 718.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By vperez Date 2016-06-17 Time 10:57 Rev Time 0.00
Received By vperez Date 2016-06-17 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-02 Cont ID  
Sent By rlecky Date 2016-03-02 Time 14:40 Rev Time 0.00
Received By rlecky Date 2016-03-02 Time 13:19 Sent To  
Notes
2016-03-02 14:42:41PROVIDE AN ELECTRICAL PLAN WHICH SHOWS THE WIRING
 METHOD, LOCATION AND TYPE OF FIXTURES INCLUDING THEIR
 SUPPORT AND SWITCHING. NEC 517.12
  
 SHOW THE EXISTING ELECTRICAL SYSTEMS FOR THE PATIENT
 ROOMS. NEC 517.10
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By pleduc Date 2016-06-21 Time   Rev Time 0.00
Received By pleduc Date 2016-06-21 Time 12:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 09:56 Sent To  
Notes
2016-03-03 10:09:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101,
 INCLUDING CHAPTER 43 BUILDING REHABILITATION, ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 2. THE DUST PARTITION PROJECTS INTO A FIRE RATED
 CORRIDOR. PROVIDE FOR THE REQUIRED FIRE RATING IN THIS
 CORRIDOR. INDICATE THE LOCATION OF EXISTING FIRE
 SPRINKLER TO ENSURE REQUIRED COVERAGE AND THAT THEY
 WON'T BE BLOCKED.
  
 3. PROVIDE THE FIRE RATING SPEC'S FOR FLOOR PLAN NOTE #
 6.
  
 4. PROVIDE AND INDICATE THE AREAS IN EACH ROOM OF FIRE
 RESISTNACE RATING PER THE FIRE RESISTANCE SCHEDULE.
  
 5. PROVIDE THE LOCATION OF THE EXISTING FIRE ALARM
 DEVICES AND INDICATE IF THEY WILL BE REMOVED/REPLACED.
  
 6. PROVIDE THE LOCATION OF THE EXISTING FIRE SPRINKLERS
 AND INDICATE IF THEY WILL BE REMOVED/REPLACED.
  
 7. PROVIDE A NOTE INDICATING AND ENSURING THE
 FOLLOWING.
  
 A. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 B. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 C. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-22 Cont ID  
Sent By   Date 2016-06-22 Time 06:59 Rev Time 0.00
Received By cpuell Date 2016-06-07 Time 14:04 Sent To  
Notes
2016-06-07 14:04:42B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 09:45 Rev Time 0.00
Received By ccole Date 2016-03-01 Time 09:57 Sent To  
Notes
2016-03-01 09:57:57B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 06:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-10 Cont ID  
Sent By ccole Date 2016-06-10 Time 08:19 Rev Time 0.00
Received By ccole Date 2016-06-10 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 09:43 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 09:43 Sent To  
Notes
2016-03-10 09:45:231ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030005
 3/10/16
  
 1) PER FLOOR PLAN NOTE #5, PLEASE PROVIDE AN AIR DEVICE
 AND DISTRIBUTION SCHEDULE ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2016-06-20 Time   Rev Time 0.00
Received By   Date 2016-06-20 Time   Sent To  
Notes
2016-06-20 14:04:37SEPERATE PLUMBING WILL BE REQUIRED IF THERE IS ANY
 CHANGES TO PLUMBING

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-03-07 Cont ID  
Sent By tklarge Date 2016-03-07 Time 05:16 Rev Time 0.00
Received By tklarge Date 2016-03-07 Time 05:02 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved