Plan Review Details - Permit 16021059
Plan Review Stops For Permit 16021059
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 06:00 Rev Time  
Received By jwitmer Date 2016-03-11 Time 05:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By vperez Date 2016-03-08 Time 07:29 Rev Time 0.00
Received By vperez Date 2016-03-08 Time 07:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-04 Cont ID  
Sent By fstal Date 2016-03-04 Time   Rev Time 0.00
Received By fstal Date 2016-03-04 Time 11:09 Sent To  
Notes
2016-03-04 11:06:31COMMENTS:
 LICENSED FIRE ALARM CONTRACTOR IS REQUIRED TO SUBMIT
 SHOP DRAWINGS THAT INCLUDE A STAMPED APPROVAL BY THE
 ENGINEER OF RECORD, VOLTAGE CALCULATIONS, BATTERY
 CALCULATIONS, ALL WIRE SIZES AND TYPES, AND ALL DEVICE
 TYPES AND LOCATIONS FOR APPROVAL PRIOR TO THE
 INSTALLATION OF ANY PART OF THE SYSTEM. FIRE ALARM
 INSTALLATION SHALL COMPLY WITH NFPA 70 AND 72, STATE
 AND LOCAL ORDINANCES.
  
 NFPA 72-17.14.5: MANUAL FIRE ALARM BOXES SHALL BE
 INSTALLED SO THAT THEY ARE CONSPICUOUS, UNOBSTRUCTED,
 AND ACCESSIBLE.
 NFPA 72-17.14.6: MANUAL FIRE ALARM BOXES SHALL BE
 LOCATED WITHIN 60 IN. (1.52 M) OF THE EXIT DOORWAY
 OPENING AT EACH EXIT ON EACH FLOOR.
  
 LICENSED FIRE SPRINKLER CONTRACTOR IS REQUIRED TO
 SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO
 INSTALLATION. FIRE SPRINKLER INSTALLATION SHALL COMPLY
 WITH NFPA 13, STATE AND LOCAL ORDINANCES.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-22 Cont ID  
Sent By ccole Date 2016-04-22 Time 07:36 Rev Time 0.00
Received By ccole Date 2016-04-19 Time 10:10 Sent To  
Notes
2016-04-20 10:10:31RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 06:01 Rev Time 0.00
Received By jwitmer Date 2016-02-29 Time 11:00 Sent To  
Notes
2016-03-08 07:29:453/8 TO BIN B07
2016-02-29 11:01:15B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 06:01 Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time 06:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-22 Cont ID  
Sent By ccole Date 2016-04-22 Time 07:36 Rev Time 0.00
Received By ccole Date 2016-04-22 Time 07:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 08:57 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 08:56 Sent To  
Notes
2016-03-10 09:10:071ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16021059
 3/10/16
  
 1) M1.1: IT IS NOT CLEAR HOW THE RETURN AIR SYSTEMS
 WILL FUNCTION FOR HP-1 & 2 SUPPLYING THE STORAGE AREAS-
 SEE WALL TYPE-1 DETAIL ON SHEET A-1: IT APPEARS BY THE
 DETAIL THAT THE WHOLE STORAGE AREA AND THE INDIVIDUAL
 STORAGE ROOMS WILL BE CLOSED OFF FROM FLOOR TO
 UNDERSIDE OF ROOF DECK. HOW WILL THE AIR RETURN BACK TO
 THE UNITS?
 2) M1.1: THE 8X6 TRANSFER DUCT IS UNDERSIZED PER
 SECTION 601.5.
 3) M1.1: INDICATE THE WIDTH AND GAGE OF THE STRAP
 HANGERS AND THE DIAMETER OF THE RODS SHOWN IN THE M1
 DETAIL, AND INDICATE THE TYPE AND SIZE OF FASTENERS FOR
 ANCHORING TO THE STRUCTURE ABOVE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  