Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By hmoser Date 2016-03-03 Time 09:51 Rev Time 0.00
Received By hmoser Date 2016-03-03 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By hmoser Date 2016-02-29 Time 13:43 Rev Time 0.00
Received By hmoser Date 2016-02-29 Time 13:43 Sent To  
Notes
2016-02-29 14:16:33PLAN DENIED
 1) PROVIDE PLANS SHOWING WHERE COOLER IS GOING
 PER SECTION 107 FBC 2014
 2) PROVIDE MORE INFORMATION ON LOCATION OF
 CONDENSER INSIDE OR OUT. IF CONDENSER IS GOING TO
 BE OUTSIDE WE NEED ENGINEERING ON TIEDOWN.
 PER SECTION 301.15 WIND RESISTANCE. 2014 FBC (M)
  