| Plan Review Stops For Permit 16020955 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
17:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-04 |
Time |
18:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-04 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2016-04-04 18:59:32 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PRODUCT APPROVALS ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. | | | | | | 2) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE FABRIC IMPACT PROTECTION SYSTEM. | | | | | | 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE | | | COMPLIANCE CERTIFICATION. | | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-09 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2016-03-09 16:56:47 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE NEW WINDOWS /GLASS TYPES, STRUCTURAL MULLIONS AND | | | STORM PANELS. | | | | | | 2) FBC 107.3.5.3 INDICATE THE MEANS OF TERMITE | | | PROTECTION PROPOSED PURSUANT TO FBC-R318. | | | | | | 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE | | | COMPLIANCE CERTIFICATION. | | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-04 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-04 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2016-04-04 18:33:36 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-09 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2016-03-09 17:21:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) SMOKE ALARMS ARE REQUIRED PER FBC-R 314.3.1. | | | | | | 3) A MINIMUM OF ONE 20 AMP BRANCH CIRCUIT IS REQUIRED | | | TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). FBCR-E3703.4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-02 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2016-05-02 10:09:46 | RMCDOUGAL'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-05 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-04 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2016-04-04 10:09:09 | TO RMCDOUGA DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-18 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-16 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2016-03-17 11:22:34 | RESUB OF IMPACT FEES ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-02-25 |
Time |
10:42 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-18 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-18 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2016-03-18 07:12:23 | MU 2016-5942 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-09 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2016-03-09 16:02:18 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-04 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-04 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2016-04-04 10:08:30 | OWNER HAS INDICATED MECHANICAL WILL BE NY SEPARATE | | | DESIGN AND PERMIIT AND WILL INCLUDE A PERFORMANCE | | | ENERGY SUBMITTAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-09 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2016-03-09 16:01:49 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SCOPE OF WORK ON THE REVISION FORM INDICATES | | | THAT DUCTWORK IS TO BE RELOCATED. SUBMIT TWO COPIES OF | | | A MECHANICAL PLAN THAT SHOWS THE SIZE AND LOCATION OF | | | THE RELOCATED DUCTS, GRILLS, ETC. FBC 107.2.1 | | | | | | 2) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER IS | | | REQUIRED ON THE MECHANICAL PLANS. FBC 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2016-05-09 17:34:34 | APPROVED WITH EXCEPTIONS. | | | SUBMIT TWO SETS OF REVISED CODE COMPLIANT PLUMBING | | | RISER PLANS FOR REVIEW BEFORE FINAL PLUMBING | | | INSPECTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-05 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-04 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2016-04-05 08:42:21 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE WATER CLOSET IN THE MASTER BATH IS NOT VENTED. | | | FBC-R P3105 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-09 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2016-03-09 17:20:39 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE PLUMBING RISER DIAGRAM IS NOT DRAWN CORRECTLY. | | | DRAW THE DIAGRAM ON THE SAME PLANE. THE WAY IT IS DRAWN | | | IT APPEARS THAT THE TUB IS ON THE SECOND FLOOR AT THE | | | FIRST BATHROOM AND THE SHOWER AND DOUBLE VANITY ARE ON | | | THE FLOOR ABOVE THE CLOTHES WASHER. | | | | | | 3) THE CLOTHES WASHER REQUIRES A SEPARATE VENT AND IS | | | REQUIRED TO TIE IN DOWN STREAM OF THE BATHROOM GROUP. | | | IT CAN NOT BE WET VENTED AS SHOWN. FBCR-P3108. IT | | | REQUIRES A MINIMUM 2" VENT, TRAP AND DRAIN PIPE. FBCR - | | | P3005.4, P3102.3, P3201.7 | | | | | | 4) THE SHOWER AND TUB ARE REQUIRED TO CONNECT | | | HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET VENTED. | | | FBCR-P3108.1 | | | | | | 5) THE SHOWER IS REQUIRED TO HAVE A MINIMUM 1-1/2 INCH | | | TRAP AND FIXTURE DRAIN BASED ON A FLOW RATE OF 5.7 GPM | | | OR LESS. FBCR-P3201.7 | | | | | | 6) THE TUB IS REQUIRED TO HAVE A MINIMUM 1-1/2 INCH | | | TRAP AND FIXTURE DRAIN. FBCR-P3201.7 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-04-05 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-05 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2016-04-05 08:33:52 | PLANS APPROVED AND STAMPED BY ANGELA VANN-JONES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-09 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-03-01 |
Time |
17:38 |
Sent To |
E |
|
| Notes |
| 2016-03-01 17:40:39 | 3/1/16- FAILED NEED 2 COPIES OF A SURVEY. | | | ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR | | | [email protected] | | | 561-822-1441 | | | |
|
|