| Plan Review Stops For Permit 16020935 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-18 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-18 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-04 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-01 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2016-04-04 15:18:12 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | 1. PROPERTY LOCATED IN FLOOD ZONE A7. MINIMUM DFE 7' | | | 6". | | | 2. SUBMIT PROPOSED FLOOD ELEVATION CERTIFICATE. | | | 3. SUBMIT SITE PLAN WITH DFE FOR MAIN HOUSE AND GARAGE. | | | 4. SUBMIT SITE DRAINAGE PLAN. | | | 5. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | 6. ROOFING PERMIT REQUIRED. | | | 7. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF SYSTEM, 3M | | | ROOF TILE ADHESIVE AND ICYNENE INSULATION. | | | 8. PROVIDE 2ND COPY OF SUBMITTAL DOCS. | | | | | | FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | | SURVEY. | | | FBC 1612.4 DESIGN AND CONSTRUCTION. | | | THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES | | | LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH | | | HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF | | | ASCE 7 AND WITH ASCE 24. | | | | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-05-16 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-16 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-16 |
Time |
15:51 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-03-10 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-09 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2016-03-10 09:03:50 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE ADD A NOTE TO PLANS TO INDICATE SEPARATE | | | PERMIT REQUIREMENTS FOR ALL LOW VOLTAGE SYSTEMS, | | | GENERATOR, ELEVATOR, DOCK AND POOL. | | | 2. PROVIDE GENERAL NOTE TO INDICATE REQUIRED TAMPER | | | RESISTANT RECEPTACLES PER FBC RES E4002.14 | | | 3. PROVIDE GENERAL NOTE TO INDICATE FBC EC R404.1 75% | | | OF LAMPS TO BE HIGH EFFICACY LAMPS. | | | 4. PROVIDE MANUF. DATA SHEET FOR THE PHASE CONVERTER. | | | FBC 107.3.5 | | | 5. LABEL THE AVAILABLE FAULT CURRENT AT THE TRANSFORMER | | | AND PROVIDE AIC CALCULATION FOR THE SERVICE SHOWN. FBC | | | RES E3606.3 | | | 6. LABEL MAIN DISTRIBUTION PANEL TO RATED FOR SERVICE | | | ENTRANCE PER FBC RES E3606.4 | | | 7. DELETE EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM | | | METER TO MDP AS PER FBC RES E3607 GROUNDED CONDUCTOR | | | NOT TO BE PARALLELED. | | | 8. ADD A NOTE TO RISER DIAGRAM TO INDICATE THAT THE | | | GENERATOR IS A NON-SEPARATELY DERIVED SYSTEM. FBC | | | 107.3.5 | | | 9. ADD A FIXTURE LEGEND FOR REFERENCE PURPOSE. FBC | | | 107.3.5 | | | 10. LABEL CU-1 TO CORRELATE WITH MECHANICAL SHEETS. | | | SHOWN AS AHU 1A AND 1B ON ELECTRICAL SHEETS. | | | 11. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-13 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-13 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-01 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-01 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2016-03-01 12:07:23 | 1) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS | | | PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS | | | AREA. | | | 2) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS | | | PLAN. | | | 3) THE GAS WATER HEATER IN THE GARAGE SHALL BE | | | PROTECTED FROM PHYSICAL DAMAGE. | | | 4) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE | | | WITH 2014 FBCR SEC.G2404.3. | | | 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS | | | APPLIANCES. 2014 FBCR SEC.G2407. | | | 6) SIZE ALL GAS LINES DOWNSTREAM OF THE REGULATORS AT | | | EACH APPLIANCE. FBC 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-18 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-10 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-04 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-02-26 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2016-03-10 09:05:03 | 3/10 TO R27 | | 2016-02-26 13:16:27 | R27 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-04-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-11 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-11 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-04 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-04 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2016-04-04 15:04:52 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-17 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-05-17 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-05-17 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-03-23 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-03-23 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2016-03-23 14:24:40 | 107.2.1.3 ADDITIONAL DATA. CONFIRM CFM QUANTITIES AND | | | SIZES OF BATHROOM EXHAUST FAN DUCTS. AS PER PLANS EACH | | | FAN SPECIFIES 105 CFM @ .3 STATIC PRESSURE. PROVIDE CFM | | | QUANTITIES PER BATHROOM. 4" DUCT AS PER TRANE DUCULATOR | | | IS 70 CFM AT .3 STATIC PRESSURE. CHECK ALL EXH FANS. | | | CHECK EXH FAN #6 & #7 HEADERS AND RISER TO ROOF JACK. | | | MAKE CORRECTIONS AND RESUBMIT. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
P |
Date |
2019-04-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-23 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-23 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2019-04-23 11:42:18 | SEE BUILDING REVIEW | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-13 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-13 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-01 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-29 |
Time |
06:17 |
Sent To |
|
|
| Notes |
| 2016-03-01 11:58:30 | 1) THE WATER SUPPLY VALVES FOR THE STACKED WASHER AND | | | DRYER UNITS ON THE FIRST FLOOR LAUNDRY (#112) SHALL BE | | | ACCESSIBLE. THE VALVES CANNOT BE LOCATED BEHIND THE | | | UNIT UNLESS AN ACCESS PANEL IS PROVIDED IN THE STACKED | | | UNIT. 2014 FBCR SEC. P2903.9.3. | | | 2) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS | | | PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS | | | AREA. | | | 3) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS | | | PLAN. | | | 4) SUBMIT A ROOF DRAIN RISER DIAGRAM FOR THE ROOF | | | DRAINS ON THE FLAT ROOF. SHOW THE SQUARE FOOTAGE THAT | | | DRAINS INTO EACH ROOF DRAIN. INCLUDE 1/2 THE AREA OF | | | THE PARAPET WALL. DRAINS SHALL DISCHARGE A MINIMUM OF 1 | | | FT. FROM THE EXTERIOR BUILDING WALL. 2014 FBCR SEC. | | | R318.5. STORM DRAINAGE SHALL BE DESIGNED USING TABLE | | | 1106.3. | | | 5) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE | | | WITH 2014 FBCR SEC.R903.4.1. | | | 6) THE GAS WATER HEATER IN THE GARAGE SHALL BE | | | PROTECTED FROM PHYSICAL DAMAGE. | | | 7) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE | | | WITH 2014 FBCR SEC.G2404.3. | | | 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS | | | APPLIANCES. 2014 FBCR SEC.G2407. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2016-05-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-18 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-18 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2016-04-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-04 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-04 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2016-04-04 15:06:40 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF | | | 2. PROVIDE PRODUCT APPROVALS FOR ICYNENE INSULATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-12 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-05-12 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-05-12 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2016-05-12 10:28:24 | 5/12/16 PASS WITH THE PRIVISO THAT A SEPORATE PERMIT IS | | | REQUIRED FOR ANY FENCES/WALLS, SWIMMING POOL, DRIVEWAY | | | AND LANDSCAPING. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-22 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2016-03-22 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2016-03-21 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2016-03-22 13:10:39 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 3/22/16 | | | | | | 1. INDICATE SETBACKS FOR MECHANICAL EQUIPMENT (E.G. AC | | | UNITS, GENERATOR, ETC.). MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK [ZLDR | | | SEC. 94-305(B)(4)]. PLEASE DEMONSTRATE COMPLIANCE. | | | | | | 2. SHEET S-2 SHOWS A WALL STRUCTURE FOR AN EXTERIOR | | | BBQ. THIS BBQ IS NOT SHOWN ON THE SITE PLAN. IS THIS | | | STRUCTURE BEING PROPOSED AT THIS TIME? IF YES, BBQ WITH | | | 8 FOOT HIGH WALL MUST COMPLY WITH ACCESSORY STRUCTURE | | | SETBACKS [ZLDR SEC. 94-304(B)(2)]. PLEASE DEMONSTRATE | | | COMPLIANCE. | | | | | | 3. IF PRIVACY WALLS AND GARDEN WALLS ARE TO BE | | | PERMITTED WITH THE SUBMITTED DOCUMENTS, A SEPARATE | | | PERMIT APPLICATION IS REQUIRED FOR THE WALLS AND | | | INDICATE HEIGHT OF ALL THE PROPOSED PRIVACY WALLS AND | | | GARDEN WALLS. PLANS INDICATE THAT THE WALL DETAIL IS | | | FOR A MAXIMUM 7 FOOT HIGH WALL, HOWEVER, WALLS WITHIN | | | THE FRONT SETBACK CANNOT EXCEED 4 FEET IN HEIGHT AND | | | WALLS WITHIN THE SIDE AND REAR SETBACKS CANNOT EXCEED 6 | | | FEET IN HEIGHT [ZLDR SEC. 94-302]. PLEASE DEMONSTRATE | | | COMPLIANCE. EASEMENT CONSENT FORMS MUST ALSO BE | | | SUBMITTED FOR IMPROVEMENTS WITHIN THE EASEMENT AREA. | | | | | | 4. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH | | | ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC. | | | 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT | | | LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE | | | PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR | | | PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT | | | LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE | | | FEET OF OPEN SPACE OR PORTION THEREOF.) YOU MAY CONTACT | | | ME TO OBTAIN DOCUMENTS TO OBTAIN CONDITIONAL APPROVAL | | | THE HOUSE PERMIT AND BE PERMITTED TO SUBMIT THE | | | LANDSCAPE PERMIT CLOSER TO THE TIME OF FINISHING | | | CONSTRUCTION OF THE HOME. | | | | | | GENERAL COMMENTS: | | | | | | A. SEPARATE PERMIT(S) AND REVIEW REQUIRED FOR DRIVEWAY, | | | HARDSCAPE, LANDSCAPING, POOL, AND FENCES. PLEASE NOTE | | | THAT UTILITY EASEMENT CONSENT FORMS ARE REQUIRED FOR | | | ANY IMPROVEMENTS WITHIN AN EASEMENT AND NEED TO BE | | | SUBMITTED IN CONJUNCTION WITH PERMIT APPLICATIONS FOR | | | THE IMPROVEMENTS. | | | | | | B. REMOVAL OR RELOCATION OF ANY TREES ON THE PROPERTY | | | WILL REQUIRE A TREE ALTERATION PERMIT THROUGH THE | | | PLANNING DIVISION. THE APPLICATION CAN BE FOUND AT THE | | | FOLLOWING LINK: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPM | | | ENT-SERVICES/FORMS/PLANNING-ZONING-FORMS | | | | | | C. ALL CODE REFERENCES CAN BE FOUND ON WWW.MUNICODE.COM | | | BY NAVIGATING TO THE CITY OF WEST PALM BEACH CODE. | | | | | | D. EASEMENT CONSENT FORM CAN BE FOUND AT THE FOLLOWING | | | LINK: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVIC | | | ES/FORMS/BUILDING-PERMIT-FORMS | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | | | | |
|
|