Plan Review Details - Permit 16020935
Plan Review Stops For Permit 16020935
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-18 Cont ID  
Sent By cthroop Date 2016-05-18 Time 10:04 Rev Time 0.00
Received By cthroop Date 2016-05-18 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By cthroop Date 2016-04-04 Time 15:07 Rev Time 0.00
Received By cthroop Date 2016-04-01 Time 11:37 Sent To  
Notes
2016-04-04 15:18:121ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROPERTY LOCATED IN FLOOD ZONE A7. MINIMUM DFE 7'
 6".
 2. SUBMIT PROPOSED FLOOD ELEVATION CERTIFICATE.
 3. SUBMIT SITE PLAN WITH DFE FOR MAIN HOUSE AND GARAGE.
 4. SUBMIT SITE DRAINAGE PLAN.
 5. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 6. ROOFING PERMIT REQUIRED.
 7. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF SYSTEM, 3M
 ROOF TILE ADHESIVE AND ICYNENE INSULATION.
 8. PROVIDE 2ND COPY OF SUBMITTAL DOCS.
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
 FBC 1612.4 DESIGN AND CONSTRUCTION.
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 15:51 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 15:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By vperez Date 2016-03-10 Time 09:03 Rev Time 0.00
Received By vperez Date 2016-03-09 Time 13:28 Sent To  
Notes
2016-03-10 09:03:50INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A NOTE TO PLANS TO INDICATE SEPARATE
 PERMIT REQUIREMENTS FOR ALL LOW VOLTAGE SYSTEMS,
 GENERATOR, ELEVATOR, DOCK AND POOL.
 2. PROVIDE GENERAL NOTE TO INDICATE REQUIRED TAMPER
 RESISTANT RECEPTACLES PER FBC RES E4002.14
 3. PROVIDE GENERAL NOTE TO INDICATE FBC EC R404.1 75%
 OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. PROVIDE MANUF. DATA SHEET FOR THE PHASE CONVERTER.
 FBC 107.3.5
 5. LABEL THE AVAILABLE FAULT CURRENT AT THE TRANSFORMER
 AND PROVIDE AIC CALCULATION FOR THE SERVICE SHOWN. FBC
 RES E3606.3
 6. LABEL MAIN DISTRIBUTION PANEL TO RATED FOR SERVICE
 ENTRANCE PER FBC RES E3606.4
 7. DELETE EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM
 METER TO MDP AS PER FBC RES E3607 GROUNDED CONDUCTOR
 NOT TO BE PARALLELED.
 8. ADD A NOTE TO RISER DIAGRAM TO INDICATE THAT THE
 GENERATOR IS A NON-SEPARATELY DERIVED SYSTEM. FBC
 107.3.5
 9. ADD A FIXTURE LEGEND FOR REFERENCE PURPOSE. FBC
 107.3.5
 10. LABEL CU-1 TO CORRELATE WITH MECHANICAL SHEETS.
 SHOWN AS AHU 1A AND 1B ON ELECTRICAL SHEETS.
 11. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-05-13 Cont ID  
Sent By gjohnson Date 2016-05-13 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2016-05-13 Time 13:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By tklarge Date 2016-03-01 Time 12:03 Rev Time 0.00
Received By tklarge Date 2016-03-01 Time 12:03 Sent To  
Notes
2016-03-01 12:07:231) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS
 PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS
 AREA.
 2) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS
 PLAN.
 3) THE GAS WATER HEATER IN THE GARAGE SHALL BE
 PROTECTED FROM PHYSICAL DAMAGE.
 4) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE
 WITH 2014 FBCR SEC.G2404.3.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES. 2014 FBCR SEC.G2407.
 6) SIZE ALL GAS LINES DOWNSTREAM OF THE REGULATORS AT
 EACH APPLIANCE. FBC 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-18 Cont ID  
Sent By cthroop Date 2016-05-18 Time 10:04 Rev Time 0.00
Received By cthroop Date 2016-05-10 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-04 Cont ID  
Sent By cthroop Date 2016-04-04 Time 15:06 Rev Time 0.00
Received By cthroop Date 2016-02-26 Time 13:16 Sent To  
Notes
2016-03-10 09:05:033/10 TO R27
2016-02-26 13:16:27R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By cthroop Date 2016-04-11 Time 14:36 Rev Time 0.00
Received By cthroop Date 2016-04-11 Time 14:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By cthroop Date 2016-04-04 Time 15:03 Rev Time 0.00
Received By cthroop Date 2016-04-04 Time 13:08 Sent To  
Notes
2016-04-04 15:04:521ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By jvalido Date 2016-05-17 Time 15:49 Rev Time 0.00
Received By jvalido Date 2016-05-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-23 Cont ID  
Sent By jvalido Date 2016-03-23 Time 14:25 Rev Time 0.00
Received By jvalido Date 2016-03-23 Time 10:04 Sent To  
Notes
2016-03-23 14:24:40107.2.1.3 ADDITIONAL DATA. CONFIRM CFM QUANTITIES AND
 SIZES OF BATHROOM EXHAUST FAN DUCTS. AS PER PLANS EACH
 FAN SPECIFIES 105 CFM @ .3 STATIC PRESSURE. PROVIDE CFM
 QUANTITIES PER BATHROOM. 4" DUCT AS PER TRANE DUCULATOR
 IS 70 CFM AT .3 STATIC PRESSURE. CHECK ALL EXH FANS.
 CHECK EXH FAN #6 & #7 HEADERS AND RISER TO ROOF JACK.
 MAKE CORRECTIONS AND RESUBMIT.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2019-04-23 Cont ID  
Sent By shill Date 2019-04-23 Time 11:42 Rev Time 0.00
Received By shill Date 2019-04-23 Time 11:41 Sent To  
Notes
2019-04-23 11:42:18SEE BUILDING REVIEW
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-13 Cont ID  
Sent By gjohnson Date 2016-05-13 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2016-05-13 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By tklarge Date 2016-03-01 Time 11:58 Rev Time 0.00
Received By tklarge Date 2016-02-29 Time 06:17 Sent To  
Notes
2016-03-01 11:58:301) THE WATER SUPPLY VALVES FOR THE STACKED WASHER AND
 DRYER UNITS ON THE FIRST FLOOR LAUNDRY (#112) SHALL BE
 ACCESSIBLE. THE VALVES CANNOT BE LOCATED BEHIND THE
 UNIT UNLESS AN ACCESS PANEL IS PROVIDED IN THE STACKED
 UNIT. 2014 FBCR SEC. P2903.9.3.
 2) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS
 PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS
 AREA.
 3) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS
 PLAN.
 4) SUBMIT A ROOF DRAIN RISER DIAGRAM FOR THE ROOF
 DRAINS ON THE FLAT ROOF. SHOW THE SQUARE FOOTAGE THAT
 DRAINS INTO EACH ROOF DRAIN. INCLUDE 1/2 THE AREA OF
 THE PARAPET WALL. DRAINS SHALL DISCHARGE A MINIMUM OF 1
 FT. FROM THE EXTERIOR BUILDING WALL. 2014 FBCR SEC.
 R318.5. STORM DRAINAGE SHALL BE DESIGNED USING TABLE
 1106.3.
 5) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE
 WITH 2014 FBCR SEC.R903.4.1.
 6) THE GAS WATER HEATER IN THE GARAGE SHALL BE
 PROTECTED FROM PHYSICAL DAMAGE.
 7) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE
 WITH 2014 FBCR SEC.G2404.3.
 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES. 2014 FBCR SEC.G2407.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-05-18 Cont ID  
Sent By cthroop Date 2016-05-18 Time 10:04 Rev Time 0.00
Received By cthroop Date 2016-05-18 Time 10:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By cthroop Date 2016-04-04 Time 15:05 Rev Time 0.00
Received By cthroop Date 2016-04-04 Time 13:08 Sent To  
Notes
2016-04-04 15:06:401ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF
 2. PROVIDE PRODUCT APPROVALS FOR ICYNENE INSULATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By njwira Date 2016-05-12 Time 10:26 Rev Time 0.00
Received By njwira Date 2016-05-12 Time 10:26 Sent To  
Notes
2016-05-12 10:28:245/12/16 PASS WITH THE PRIVISO THAT A SEPORATE PERMIT IS
 REQUIRED FOR ANY FENCES/WALLS, SWIMMING POOL, DRIVEWAY
 AND LANDSCAPING.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-22 Cont ID  
Sent By dkittred Date 2016-03-22 Time 13:10 Rev Time 0.00
Received By dkittred Date 2016-03-21 Time 12:46 Sent To  
Notes
2016-03-22 13:10:39PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/22/16
  
 1. INDICATE SETBACKS FOR MECHANICAL EQUIPMENT (E.G. AC
 UNITS, GENERATOR, ETC.). MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK [ZLDR
 SEC. 94-305(B)(4)]. PLEASE DEMONSTRATE COMPLIANCE.
  
 2. SHEET S-2 SHOWS A WALL STRUCTURE FOR AN EXTERIOR
 BBQ. THIS BBQ IS NOT SHOWN ON THE SITE PLAN. IS THIS
 STRUCTURE BEING PROPOSED AT THIS TIME? IF YES, BBQ WITH
 8 FOOT HIGH WALL MUST COMPLY WITH ACCESSORY STRUCTURE
 SETBACKS [ZLDR SEC. 94-304(B)(2)]. PLEASE DEMONSTRATE
 COMPLIANCE.
  
 3. IF PRIVACY WALLS AND GARDEN WALLS ARE TO BE
 PERMITTED WITH THE SUBMITTED DOCUMENTS, A SEPARATE
 PERMIT APPLICATION IS REQUIRED FOR THE WALLS AND
 INDICATE HEIGHT OF ALL THE PROPOSED PRIVACY WALLS AND
 GARDEN WALLS. PLANS INDICATE THAT THE WALL DETAIL IS
 FOR A MAXIMUM 7 FOOT HIGH WALL, HOWEVER, WALLS WITHIN
 THE FRONT SETBACK CANNOT EXCEED 4 FEET IN HEIGHT AND
 WALLS WITHIN THE SIDE AND REAR SETBACKS CANNOT EXCEED 6
 FEET IN HEIGHT [ZLDR SEC. 94-302]. PLEASE DEMONSTRATE
 COMPLIANCE. EASEMENT CONSENT FORMS MUST ALSO BE
 SUBMITTED FOR IMPROVEMENTS WITHIN THE EASEMENT AREA.
  
 4. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.) YOU MAY CONTACT
 ME TO OBTAIN DOCUMENTS TO OBTAIN CONDITIONAL APPROVAL
 THE HOUSE PERMIT AND BE PERMITTED TO SUBMIT THE
 LANDSCAPE PERMIT CLOSER TO THE TIME OF FINISHING
 CONSTRUCTION OF THE HOME.
  
 GENERAL COMMENTS:
  
 A. SEPARATE PERMIT(S) AND REVIEW REQUIRED FOR DRIVEWAY,
 HARDSCAPE, LANDSCAPING, POOL, AND FENCES. PLEASE NOTE
 THAT UTILITY EASEMENT CONSENT FORMS ARE REQUIRED FOR
 ANY IMPROVEMENTS WITHIN AN EASEMENT AND NEED TO BE
 SUBMITTED IN CONJUNCTION WITH PERMIT APPLICATIONS FOR
 THE IMPROVEMENTS.
  
 B. REMOVAL OR RELOCATION OF ANY TREES ON THE PROPERTY
 WILL REQUIRE A TREE ALTERATION PERMIT THROUGH THE
 PLANNING DIVISION. THE APPLICATION CAN BE FOUND AT THE
 FOLLOWING LINK: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPM
 ENT-SERVICES/FORMS/PLANNING-ZONING-FORMS
  
 C. ALL CODE REFERENCES CAN BE FOUND ON WWW.MUNICODE.COM
 BY NAVIGATING TO THE CITY OF WEST PALM BEACH CODE.
  
 D. EASEMENT CONSENT FORM CAN BE FOUND AT THE FOLLOWING
 LINK: HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVIC
 ES/FORMS/BUILDING-PERMIT-FORMS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  