Plan Review Details - Permit 16020914
Plan Review Stops For Permit 16020914
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By J.Walker Date 2016-05-31 Time   Rev Time 0.30
Received By   Date 2016-05-31 Time   Sent To M
Notes
2016-05-31 15:22:12SEE PULL STATION NOTES ON PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-26 Cont ID  
Sent By J.Walker Date 2016-02-26 Time   Rev Time 0.25
Received By   Date 2016-02-25 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-07 Cont ID  
Sent By hmoser Date 2016-06-07 Time 13:49 Rev Time 0.00
Received By hmoser Date 2016-05-26 Time 13:13 Sent To  
Notes
2016-05-27 13:14:02RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-04 Cont ID  
Sent By hmoser Date 2016-03-04 Time 06:43 Rev Time 0.00
Received By hmoser Date 2016-02-24 Time 12:51 Sent To  
Notes
2016-02-24 12:51:40ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-06-07 Cont ID  
Sent By hmoser Date 2016-06-07 Time 13:48 Rev Time 0.00
Received By hmoser Date 2016-06-07 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-04 Cont ID  
Sent By hmoser Date 2016-03-04 Time 06:36 Rev Time 0.00
Received By hmoser Date 2016-03-03 Time 13:19 Sent To  
Notes
2016-03-04 06:35:53PLAN DENIED
 1) PLEASE SHOW HOW YOU ARE GOING TO MEET THE
 REQUIREMENT
 OF SECTION 508.1.1 MAKE UP AIR TEMPERATURE 2014 FBC (M)
 2) INSTALLATION SHALL COMPLY WITH THE FBC 2014 (M) NOT
 2010
 3) PLEASE SHOW HOW THE DUCT OUTSIDE OF THE BUILDING
 WILL MEET
 THE REQUIREMENTS OF 301.15 WIND RESISTANCE 2014 FBC (M)
 4) REFER TO SECTION 506.3.6GREASE DUCT CLEARANCES
 2014 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676