Plan Review Details - Permit 16020863
Plan Review Stops For Permit 16020863
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By scaldero Date 2016-03-03 Time 16:54 Rev Time 0.00
Received By scaldero Date 2016-03-03 Time 16:53 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-29 Cont ID  
Sent By scaldero Date 2016-02-29 Time 14:31 Rev Time 0.00
Received By scaldero Date 2016-02-29 Time 14:26 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-07 Cont ID  
Sent By ccole Date 2016-03-07 Time 07:42 Rev Time 0.00
Received By ccole Date 2016-03-02 Time 13:22 Sent To  
Notes
2016-03-02 13:23:05RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-01 Cont ID  
Sent By ccole Date 2016-03-01 Time 09:39 Rev Time 0.00
Received By ccole Date 2016-02-23 Time 12:58 Sent To  
Notes
2016-02-23 12:58:52ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By ccole Date 2016-03-07 Time 07:42 Rev Time 0.00
Received By ccole Date 2016-03-07 Time 07:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By ccole Date 2016-03-01 Time 09:39 Rev Time 0.00
Received By ccole Date 2016-03-01 Time 09:39 Sent To  
Notes
2016-03-01 09:58:241ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020863
 3/1/16
  
  
 1) CLARIFY HOW MAKE-UP AIR IS BEING SUPPLIED TO THE
 DISHWASHER HOOD: NO MUA IN THE SCHEDULE AND NO
 DEDICATED AC SUPPLY AIR NOTED OR SHOWN.
 2) INDICATE COMPLIANCE WITH SECTION 507.9 EXCEPTION FOR
 THE SS HOOD BACKING TO BE INSTALLED IN AN AREA
 EXTENDING NOT LESS THAN 18 INCHES IN ALL DIRECTIONS
 FROM THE HOOD.
 3) PROVIDE A ROOF PLAN VIEW SHOWING CLEARANCE DISTANCE
 MEASUREMENTS FROM THE FANS TO THE ROOF EDGES, AND TO
 ANY MECHANICAL AND GRAVITY EXHAUST AND AIR INLET
 LOCATIONS.
 4) SUBMIT THE NOA'S FOR THE FANS AND THE DUCT WRAP WITH
 REVIEW AND APPROVAL SIGNATURES BY THE EOR.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  